Lochinvar 402 - 2072 operation manual Inspect and clean the heat exchanger, Review with owner

Page 75

9 Maintenance (continued)

Inspect and clean the heat exchanger

1.While burners are removed, check the heat exchanger surface for sooting. If present, heat exchanger must be cleaned and problem corrected. Proceed as follows.

2.Remove gas manifold(s)/orifice assemblies as described in steps 1 through 5 in Burner Removal and Cleaning, page 74.

3.Disconnect wiring from the hot surface igniter and hose from the burner pressure tap.

4.Remove inner jacket panel mounting screws and slide door assembly out toward front of the unit. Use caution to prevent damage to the refractory and hot surface igniter.

5.Check “V” baffles and frame runners along front and back edges of heat exchanger. Remove and clean if necessary.

6.Remove soot from heat exchanger with a stiff bristle brush. Use a vacuum to remove loose soot from surfaces and inner chamber.

7.The heat exchanger can be removed by sliding towards the front of the unit. Once the heat exchanger is removed from the unit, a garden hose can be used to wash the tubes to ensure that all soot is removed from the heat exchanger surfaces. Note: Do not wet the unit’s refractory.

8.Ensure that all burner ports are cleaned to remove any soot. See Burner Removal and Cleaning, page 74.

9.Carefully reinstall the heat exchanger, “V” baffles, and frame runners if removed from the unit. Note: Make sure frame runners seal securely where they contact the front and rear compartment refractory.

10.Carefully reinstall inner jacket panels, burners, manifolds, wires and hoses. Use new gasket material to ensure a proper air seal.

11.Reassemble all gas and water piping. Test for gas leaks.

NOTICE

Upon completion of any testing on the gas

 

system, leak test all gas connections with a

 

 

soap and water solution while main burners

 

are operating. Do not spray soap and water

 

solution on the SMART SYSTEM control

 

module housing. The use of an excessive

 

amount of soap and water solution can

 

damage the control. Immediately repair

 

any leak found in the gas train or related

 

components. Do not operate an appliance

 

with a leak in the gas train, valves, or related

 

piping.

12.Reassemble outer jacket panels.

13.Cycle unit and check for proper operation.

Installation & Operation Manual

HEAT

EXCHANGER

Figure 9-3_Location of the Heat Exchanger Inside Jacket

Review with owner

1.Review the Copper-fin II User’s Information Manual with the owner.

2.Emphasize the need to perform the maintenance schedule specified in the Copper-fin II User’s Information Manual (and in this manual as well).

3.Remind the owner of the need to call a licensed contractor should the appliance or system exhibit any unusual behavior.

4.Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.

Oiled bearing circulators

Inspect the pump every six (6) months and oil as necessary. Use SAE 30 non-detergent oil or lubricant specified by the pump manufacturer.

75

Image 75
Contents Save this manual for future reference Models 402Contents Please read before proceeding Special instructionsRemoval of Combustion Chamber Lining or Base Panels Owner warning Safety informationCopper-fin II How it works Copper-fin II How it works Copper-fin II How it works Copper-fin =B=R Rating RatingsFreeze protection Determine unit locationLocation of unit Indoor clearances from combustible constructionCombustion and ventilation air Outdoor boiler installationLocation Hydronic systems anti-freezeMinimum Recommended Combustion AIR Supply to Equipment Room Outside Combustion Air Using Direct VentingCombustion air filter Exhaust fansCAT I Negative pressure non-condensing VentingIdentify your appliance’s vent system CAT IV Flue pipe materialsDirect Vent see General information Venting supportBarometric damper location Common Venting Systems Conventional negative draft venting seeNegative draft Flue outlet pipingMasonry chimney installations Vertical vent termination clearances and locationInspection of a masonry chimney 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Sidewall air inlet Vertical DirectAire venting seeCombustion air inlet piping Length of air inlet pipeVertical Rooftop Air Inlet Combined air inlet pointsClearances Directaire Kits Model Horizontal KIT Vertical KIT Venting of flue productsSidewall vent termination clearances and location Sidewall venting seeSidewall with fan Sidewall venting terminationSidewall venting without fan Drain tee installationModels 402 Venting of flue products Horizontal DirectAire venting Powered Venting seeDirect venting see Flue outlet pipingVertical DV venting termination Combustion air inlet piping Masonry chimney installationHorizontal DV venting termination Horizontal Vent Termination Clearances and LocationSealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipe Connecting the air inlet pipe to the unitAir inlet piping materials Length of air inlet pipeVertical Combustion Air Inlet Clearances Multiple sidewall direct vent installationsVertical and sidewall combustion air inlet Horizontal combustion air inlet clearancesOutdoor installation see Outdoor vent/air inlet locationOutdoor vent cap kit Gas connection Connecting to gas supplyGas connections Gas pressure testCombination gas valves Gas train and controlsVenting of combination gas valves Checking gas supply pressure GAS Piping Size ChartHeat exchanger Water flow switchWater connections Inlet and outlet connectionsWater connections heating boilers only Heating boiler installationsRelief valve Piping of the boiler systemLTV Valve Kits Model LTV Valve KIT Minimum boiler water temperaturesLow Temperature Return Water Systems Low temperature bypass requirementsMaximum Flow for Heating Boiler Low system water volumeThree way valves in system Radiant floor and snow melt heating systemsDHW installation Temperature / pressure gaugeTypical heating boiler installations Installation with a chilled water systemDiameter GPM4Primary/Secondary Piping of Multiple Boilers Floor Drain Heating Supply Loop 6Primary/Secondary Piping with Buffer Tank AMP Draw Data Installation must comply withElectrical connections Boiler operating control moduleDHW Domestic Hot Water thermostat Line voltage connectionsEMS or remote thermostat connection Low voltage connectionsSystem supply sensor recommended use Louver proving switchAlarm contacts Louver relay4Low Voltage Field Wiring Connections Wiring of the cascadeStart-up Start the boiler Check thermostat circuitsCheck vent and air piping Placing the boiler in operation1Lighting Instructions Configuration of the cascade Set DHW operationSet clock How the control module operates Operating informationGeneral How the appliance operatesProtection features Temperature controlBoiler temperature regulation Outdoor reset operation, if used boilers onlyCascade DHW, Night Setback, and Ramp Delay operation with cascade DAY Switching on SequenceSequence of the cascade Operation Display Sequence of operationCopper-fin II control module MENU/EXIT Display Screen ENTER/RESET UpdownTo save parameters and exit programming Access modesInstaller UserStatus display screens Syssup ***F Inlet ***FInlet Open Inlet ShortedFAN Speed Unit Pump DelayDHW Pump Delay STG DemandMIX VAL POS ** % Operation of the cascadeMaximum Water Flow Temperature Rise AT Full Rate Fire 90 GPM FlowModel Temperature Rise F Domestic water heatersWater chemistry 1Typical Water Heater Piping with Storage Tank 2Single Water Heater Piping with Two Storage Tanks 3Multiple Water Heater Piping with a Single Storage Tank 4Multiple Water Heater Piping with Multiple Storage Tanks Ft. Hd Pump operationHeat exchanger Minimum Pump PerformanceThermostat adjustment procedure Minimum water temperatures domestic hot water useDomestic water temperatures Location of Cold Water Supply Piping Connections Optional relief valveThermal expansion Cathodic protectionMaintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Ignition system checkout Check all wiringCheck control settings Check relief valve Inspect/replace hot surface igniterCheck flue gas passageways Inspect and clean burnerPerform start-up and checks Check burner flameInspect and clean the heat exchanger Review with ownerOiled bearing circulators Digital Harness Connection diagramSplay Ladder DiagramFlow Switch
Related manuals
Manual 44 pages 7.23 Kb Manual 44 pages 18.25 Kb Manual 44 pages 8.33 Kb

402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.