Lochinvar 402 - 2072 operation manual Ratings, Copper-fin =B=R Rating

Page 8

Ratings

Copper-fin II

I=B=R Rating

Model Number

Input

 

Gross

Net

 

Output

I=B=R

 

MBH

 

MBH

Ratings

 

(Note 4)

 

 

Water,

 

 

 

MBH

Note: Change “N” to

 

 

 

 

 

 

 

 

 

“L” for L.P. gas models.

Min

 

Max

(Note 1)

(Note 2)

 

 

 

 

 

 

CFN0402

250

 

399

339

295

 

CFN0502

250

 

500

425

370

CFN0652

250

 

650

553

481

CFN0752

250

 

750

638

555

CFN0992

360

 

990

842

732

CFN1262

360

 

1260

1071

931

CFN1442

360

 

1440

1224

1064

CFN1802

360

 

1800

1530

1330

CFN2072

630

 

2070

1760

1530

CHN0402

250

 

399

339

295

CHN0502

250

 

500

425

370

CHN0652

250

 

650

553

481

CHN0752

250

 

750

638

555

CHN0992

360

 

990

842

732

CHN1262

360

 

1260

1071

931

CHN1442

360

 

1440

1224

1064

CHN1802

360

 

1800

1530

1330

CHN2072

630

 

2070

1760

1530

 

 

 

 

 

 

Installation & Operation Manual

Other Specifications

Appliance

 

 

Air / Vent

Water

Water

Gas

Sizes

Content

Connections

Connections

 

Gallons

 

 

(Note 3)

 

 

 

 

 

 

 

1.6

2"

1-1/4"

6"

1.7

2"

1-1/4"

6"

2.0

2"

1-1/4"

8"

2.1

2"

1-1/4"

8"

2.2

2-1/2"

2"

10"

2.6

2-1/2"

2"

12"

2.9

2-1/2"

2"

12"

3.3

2-1/2"

2"

12"/14"

3.6

2-1/2"

2"

12"/14"

 

 

 

 

1.6

2"

1-1/4"

6"

1.7

2"

1-1/4"

6"

2.0

2"

1-1/4"

8"

2.1

2"

1-1/4"

8"

2.2

2-1/2"

2"

10"

2.6

2-1/2"

2"

12"

2.9

2-1/2"

2"

12"

3.3

2-1/2"

2"

12"/14"

3.6

2-1/2"

2"

12"/14"

 

 

 

 

NOTICE

Notes:

Maximum allowed working pressure is located on the rating plate.

1.The ratings are based on standard test procedures prescribed by the United States Department of Energy.

2.Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.

3.Copper-fin II’s require special gas venting. Use only the vent materials and methods specified in the Copper-fin II Installation and Operation Manual.

4.The Copper-fin II is orificed for operation up to 2000 feet altitude, and including up to 4,500 feet, with no field adjustments. The appliance will de-rate by 4% for each 1000 feet above sea level up to 4,500 feet. Consult the factory for installations above 4,500 feet elevation.

8

Image 8
Contents Models 402 Save this manual for future referenceContents Removal of Combustion Chamber Lining or Base Panels Please read before proceedingSpecial instructions Safety information Owner warningCopper-fin II How it works Copper-fin II How it works Copper-fin II How it works Ratings Copper-fin =B=R RatingDetermine unit location Location of unitIndoor clearances from combustible construction Freeze protectionOutdoor boiler installation LocationHydronic systems anti-freeze Combustion and ventilation airOutside Combustion Air Using Direct Venting Minimum Recommended Combustion AIR Supply to Equipment RoomExhaust fans Combustion air filterVenting Identify your appliance’s vent systemCAT IV Flue pipe materials CAT I Negative pressure non-condensingDirect Vent see Barometric damper location General informationVenting support Conventional negative draft venting see Negative draftFlue outlet piping Common Venting SystemsInspection of a masonry chimney Masonry chimney installationsVertical vent termination clearances and location 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Vertical DirectAire venting see Combustion air inlet pipingLength of air inlet pipe Sidewall air inletClearances Vertical Rooftop Air InletCombined air inlet points Venting of flue products Directaire Kits Model Horizontal KIT Vertical KITSidewall venting see Sidewall with fanSidewall venting termination Sidewall vent termination clearances and locationDrain tee installation Sidewall venting without fanModels 402 Horizontal DirectAire venting Powered Venting see Venting of flue productsVertical DV venting termination Direct venting seeFlue outlet piping Masonry chimney installation Horizontal DV venting terminationHorizontal Vent Termination Clearances and Location Combustion air inlet pipingConnecting the air inlet pipe to the unit Air inlet piping materialsLength of air inlet pipe Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipeMultiple sidewall direct vent installations Vertical and sidewall combustion air inletHorizontal combustion air inlet clearances Vertical Combustion Air Inlet ClearancesOutdoor vent cap kit Outdoor installation seeOutdoor vent/air inlet location Connecting to gas supply Gas connectionsGas pressure test Gas connectionVenting of combination gas valves Combination gas valvesGas train and controls GAS Piping Size Chart Checking gas supply pressureWater flow switch Water connectionsInlet and outlet connections Heat exchangerHeating boiler installations Relief valvePiping of the boiler system Water connections heating boilers onlyMinimum boiler water temperatures Low Temperature Return Water SystemsLow temperature bypass requirements LTV Valve Kits Model LTV Valve KITLow system water volume Three way valves in systemRadiant floor and snow melt heating systems Maximum Flow for Heating BoilerTemperature / pressure gauge Typical heating boiler installationsInstallation with a chilled water system DHW installationGPM Diameter4Primary/Secondary Piping of Multiple Boilers Floor Drain Heating Supply Loop 6Primary/Secondary Piping with Buffer Tank Installation must comply with Electrical connectionsBoiler operating control module AMP Draw DataLine voltage connections EMS or remote thermostat connectionLow voltage connections DHW Domestic Hot Water thermostatLouver proving switch Alarm contactsLouver relay System supply sensor recommended useWiring of the cascade 4Low Voltage Field Wiring ConnectionsStart-up Check thermostat circuits Check vent and air pipingPlacing the boiler in operation Start the boiler1Lighting Instructions Set clock Configuration of the cascadeSet DHW operation Operating information GeneralHow the appliance operates How the control module operatesTemperature control Protection featuresCascade Boiler temperature regulationOutdoor reset operation, if used boilers only Sequence of the cascade DHW, Night Setback, and Ramp Delay operation with cascadeDAY Switching on Sequence Sequence of operation Operation DisplayMENU/EXIT Display Screen ENTER/RESET Updown Copper-fin II control moduleAccess modes InstallerUser To save parameters and exit programmingStatus display screens Inlet ***F Inlet OpenInlet Shorted Syssup ***FUnit Pump Delay DHW Pump DelaySTG Demand FAN SpeedOperation of the cascade MIX VAL POS ** %Temperature Rise AT Full Rate Fire 90 GPM Flow Model Temperature Rise FDomestic water heaters Maximum Water FlowWater chemistry 1Typical Water Heater Piping with Storage Tank 2Single Water Heater Piping with Two Storage Tanks 3Multiple Water Heater Piping with a Single Storage Tank 4Multiple Water Heater Piping with Multiple Storage Tanks Pump operation Heat exchangerMinimum Pump Performance Ft. HdDomestic water temperatures Thermostat adjustment procedureMinimum water temperatures domestic hot water use Optional relief valve Thermal expansionCathodic protection Location of Cold Water Supply Piping ConnectionsOwner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check all wiring Check control settingsCheck relief valve Inspect/replace hot surface igniter Ignition system checkoutInspect and clean burner Perform start-up and checksCheck burner flame Check flue gas passagewaysOiled bearing circulators Inspect and clean the heat exchangerReview with owner Connection diagram Digital HarnessSplay Diagram LadderFlow Switch
Related manuals
Manual 44 pages 7.23 Kb Manual 44 pages 18.25 Kb Manual 44 pages 8.33 Kb

402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.