8 Domestic water heaters

Figure 8-5_Danger Warning

Location of Cold Water Supply Piping Connections

Incorrect piping of the cold water supply to the system may result in excessive low temperature operation causing condensate formation on the primary heat exchanger and operational problems. The cold water supply piping must be installed in the discharge piping from the heater to the storage tank. This allows the cold water to be tempered in the storage tank before entering the heater. See typical installation drawings provided in this manual for correct piping (FIG.’s 8-1 thru 8-4). Higher water temperatures reduce the volume of condensate formed.

￿ CAUTION

Setting the temperature selector to higher

settings provides hotter water, which

 

increases the risk of scald injury.

￿WARNING Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect

the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.

Optional adjustable auxiliary high water temperature limit control

ADJUSTABLE AUXILIARY HIGH WATER TEMPERATURE LIMIT CONTROL (OPTION)

Installation & Operation Manual

A high limit control is located on the inside of the left front panel, as shown in FIG. 8-6. The setting of this control knob limits maximum discharge water temperature. The water heater temperature limit control is adjustable up to a maximum setting of 210°F (99°C). This water heater also includes a fixed high water temperature limit control set to 200° (93.3°C). The RESET key on the display must be pushed whenever water temperature has exceeded the set point of the limit. The temperature of the water in the heat exchanger must drop a minimum of 15°F (8.3°C) below the setting of the high limit control before the reset function can be activated. A high limit message will be shown in the Operator Interface when water temperature exceeds the high water temperature limit control set point.

NOTICE

The high limit control will not reset until the

water temperature has dropped below the set

 

 

point of the high limit.

Optional relief valve

This water heater is normally supplied with a temperature and pressure relief valve sized in accordance with applicable codes. Units may be supplied with an optional pressure only relief valve. When a water heater is equipped with this optional relief valve and is piped to a separate storage vessel, the storage vessel must have a properly installed temperature and pressure relief valve which complies with local codes.

Thermal expansion

A relief valve that discharges periodically may be due to thermal expansion in a closed system. A water heater installed in a closed system, such as one with a backflow preventer or check valve installed in the cold water supply, shall be provided with means to control expansion. Contact the water supplier or local plumbing inspector on how to correct this situation. Never plug or cap the relief valve discharge.

Cathodic protection

Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the hot water begins to flow. There should be no smoking or open flames near the faucet at the time it is open.

Figure 8-6_Adjustable Auxiliary High Water Temperature Limit Control

70

Image 70
Contents Models 402 Save this manual for future referenceContents Special instructions Please read before proceedingRemoval of Combustion Chamber Lining or Base Panels Safety information Owner warningCopper-fin II How it works Copper-fin II How it works Copper-fin II How it works Ratings Copper-fin =B=R RatingIndoor clearances from combustible construction Determine unit locationLocation of unit Freeze protectionHydronic systems anti-freeze Outdoor boiler installationLocation Combustion and ventilation airOutside Combustion Air Using Direct Venting Minimum Recommended Combustion AIR Supply to Equipment RoomExhaust fans Combustion air filterCAT IV Flue pipe materials VentingIdentify your appliance’s vent system CAT I Negative pressure non-condensingDirect Vent see Venting support General informationBarometric damper location Flue outlet piping Conventional negative draft venting seeNegative draft Common Venting SystemsVertical vent termination clearances and location Masonry chimney installationsInspection of a masonry chimney 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Length of air inlet pipe Vertical DirectAire venting seeCombustion air inlet piping Sidewall air inletCombined air inlet points Vertical Rooftop Air InletClearances Venting of flue products Directaire Kits Model Horizontal KIT Vertical KITSidewall venting termination Sidewall venting seeSidewall with fan Sidewall vent termination clearances and locationDrain tee installation Sidewall venting without fanModels 402 Horizontal DirectAire venting Powered Venting see Venting of flue productsFlue outlet piping Direct venting seeVertical DV venting termination Horizontal Vent Termination Clearances and Location Masonry chimney installationHorizontal DV venting termination Combustion air inlet pipingLength of air inlet pipe Connecting the air inlet pipe to the unitAir inlet piping materials Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipeHorizontal combustion air inlet clearances Multiple sidewall direct vent installationsVertical and sidewall combustion air inlet Vertical Combustion Air Inlet ClearancesOutdoor vent/air inlet location Outdoor installation seeOutdoor vent cap kit Gas pressure test Connecting to gas supplyGas connections Gas connectionGas train and controls Combination gas valvesVenting of combination gas valves GAS Piping Size Chart Checking gas supply pressureInlet and outlet connections Water flow switchWater connections Heat exchangerPiping of the boiler system Heating boiler installationsRelief valve Water connections heating boilers onlyLow temperature bypass requirements Minimum boiler water temperaturesLow Temperature Return Water Systems LTV Valve Kits Model LTV Valve KITRadiant floor and snow melt heating systems Low system water volumeThree way valves in system Maximum Flow for Heating BoilerInstallation with a chilled water system Temperature / pressure gaugeTypical heating boiler installations DHW installationGPM Diameter4Primary/Secondary Piping of Multiple Boilers Floor Drain Heating Supply Loop 6Primary/Secondary Piping with Buffer Tank Boiler operating control module Installation must comply withElectrical connections AMP Draw DataLow voltage connections Line voltage connectionsEMS or remote thermostat connection DHW Domestic Hot Water thermostatLouver relay Louver proving switchAlarm contacts System supply sensor recommended useWiring of the cascade 4Low Voltage Field Wiring ConnectionsStart-up Placing the boiler in operation Check thermostat circuitsCheck vent and air piping Start the boiler1Lighting Instructions Set DHW operation Configuration of the cascadeSet clock How the appliance operates Operating informationGeneral How the control module operatesTemperature control Protection featuresOutdoor reset operation, if used boilers only Boiler temperature regulationCascade DAY Switching on Sequence DHW, Night Setback, and Ramp Delay operation with cascadeSequence of the cascade Sequence of operation Operation DisplayMENU/EXIT Display Screen ENTER/RESET Updown Copper-fin II control moduleUser Access modesInstaller To save parameters and exit programmingStatus display screens Inlet Shorted Inlet ***FInlet Open Syssup ***FSTG Demand Unit Pump DelayDHW Pump Delay FAN SpeedOperation of the cascade MIX VAL POS ** %Domestic water heaters Temperature Rise AT Full Rate Fire 90 GPM FlowModel Temperature Rise F Maximum Water FlowWater chemistry 1Typical Water Heater Piping with Storage Tank 2Single Water Heater Piping with Two Storage Tanks 3Multiple Water Heater Piping with a Single Storage Tank 4Multiple Water Heater Piping with Multiple Storage Tanks Minimum Pump Performance Pump operationHeat exchanger Ft. HdMinimum water temperatures domestic hot water use Thermostat adjustment procedureDomestic water temperatures Cathodic protection Optional relief valveThermal expansion Location of Cold Water Supply Piping ConnectionsService technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check relief valve Inspect/replace hot surface igniter Check all wiringCheck control settings Ignition system checkoutCheck burner flame Inspect and clean burnerPerform start-up and checks Check flue gas passagewaysReview with owner Inspect and clean the heat exchangerOiled bearing circulators Connection diagram Digital HarnessSplay Diagram LadderFlow Switch
Related manuals
Manual 44 pages 7.23 Kb Manual 44 pages 18.25 Kb Manual 44 pages 8.33 Kb

402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.