Lochinvar 065, 495, 000 - 2 Cleaning Maintenance, Flue Gas Passageways Cleaning Procedures

Page 40

Hydronic Heating Boilers and Domestic Water Heaters

CLEANING AND

MAINTENANCE

Listed below are items that must be checked to ensure safe reliable operations. Verify proper operation after servicing.

￿CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

Appliance Area

Keep appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.

Water Circulating Pump

Inspect pump every six months and oil as necessary. Use SAE

30non-detergent oil or lubricant specified by pump manufacturer.

Burner Flames

Visually check main burner flames at each start up after long shutdown periods or at least every six months. Burner viewports are located on the right and left sides of the unit.

Figure 43 - Flame Pattern Illustration

￿WARNING: The areas around the burner viewports are hot. Direct contact with unit could result in burns.

Normal Flame: A normal flame is blue with slight yellow tips, has a well-defined inner cone, and displays no lifting flames.

Yellow Tips: The usual causes for yellow tips on the burner flame are burner air flow blockage or partial obstruction.

Yellow Flames: The usual causes for yellow flames are primary air flow blockage to the burner(s) or excessive gas input. Correct this condition immediately.

Lifting Flames: The usual causes for lifting flames are over firing the burner(s), excessive primary air, or high draft.

If you observe improper flame patterns, examine the venting system, ensure proper gas supply, and ensure adequate supply of combustion and ventilation air.

Flue Gas Passageways Cleaning Procedures

Any sign of soot around the outer jacket, at the burners or in the areas between the fins on the copper heat exchanger indicates a need for cleaning. The following cleaning procedures must only be performed by a qualified serviceman or installer. Proper service is required to maintain safe operation. Properly installed and adjusted units seldom need flue cleaning.

IMPORTANT: All gaskets on disassembled components must be replaced with new gaskets on reassembly. Gasket kits are available from your distributor.

Burner Removal and Cleaning

1.Turn off main power to unit.

2.Turn off main manual gas shutoff to unit.

3.Remove the front outer jacket panels.

4. Disconnect manifold from gas train using union(s) just below each gas valve(s).

5.Remove mounting screws from manifold mounting brackets. Pull the manifold/orifice assembly away from burners. Repeat for each manifold assembly.

6. Remove two mounting screws from burner and slide burner out toward front of unit. Use caution to prevent damage to burners, refractory, hot surface igniter or wiring.

7.Remove soot from burners with a stiff bristle brush. Dirt may be removed from burner ports by rinsing the burner thoroughly with water. Drain and dry burners before re- installing. Damaged burners must be replaced.

When installed in a dusty and dirty location, the burners may require cleaning on a 3 to 6 month schedule or as needed, based on severity of contamination. Contaminants can be drawn in with the combustion air. Non combustible particulate matter such as dust, dirt, concrete dust or dry wall dust can block burner ports and cause non-warrantable failure. The standard inlet air filter will help eliminate dust and dirt from entering the unit. Use extreme care when operating a unit for temporary heat during new construction. The burners could require a thorough cleaning before the unit is placed in service.

40

Image 40
Contents Domestic Water Heaters Save this manual for future referenceHydronic Heating Boilers and Domestic Water Heaters Safety Information General Product InformationHydronic Heating Boilers and Domestic Water Heaters Product Identification Front and Rear ViewClearances from Combustible Construction InstallationBase for Combustible Floors Outdoor Boiler Installation Hydronic System AntifreezeShut-Down and Draining Pump OperationFreeze Protection for a Heating Boiler System if required Installing Combustion Air FilterCombustion Air Filter Combustion Air Options One OpeningInstallation Venting General InformationExhaust Fans Venting SupportTABLE-A Vent System Options Table BFlue Pipe Sizes TABLE-CConventional Negative Draft Venting Negative DraftFlue Outlet Piping Common Venting SystemsOutdoor Installation Venting Masonry Chimney InstallationsTable D Outdoor Vent KitsOutdoor Vent/Air Inlet Location Outdoor Vent KitGas Piping Gas Pressure TestInput Max Min Connecting Gas Piping to Unit Gas Train and ControlsChecking Gas Supply Pressure Combination Gas ValvesVenting of Combination Gas Valves Gas Manifold Pressure Adjustment Measuring Gas Supply Pressure at Combination Gas ValveNET Manifold Pressure Regulator Pressure Less Front Chamber PressureWater Flow Switch Low Water CutoffRelief Valve If EquippedTable J Terminal Strip Connection OptionsNominal AMP Draw Data Water Connections Heating Boilers Only General Plumbing RulesPrimary/Secondary Boiler Piping Radiant Floor and Snow Melt Heating Systems Low Temperature Return Water SystemsInput LTV Valve Kit Btu/hr Installation with a Chilled Water System System Temperature Rise Chart Based on Btu/hr InputTable L 10ºF 20ºF 30ºF 40ºF 50ºF 60ºFTemperature/Pressure Gauge Boiler Flow RateBoiler Bypass Requirements Filling the SystemOperation Lighting InstructionsLocating Temperature Control To Turn Off Gas To ApplianceTemperature Control Settings Table MSet Point Maximum Set Point DeterminationOutdoor Air Reset Option High-Fire OffsetShutdown Outdoor Air Max O.A. MaxTemperature Control Sensors Placement of SensorsBoiler Application Water Heater ApplicationRemote Wire Connection Wire Maximum GaugeHot Surface Igniter and Ignition Control Module Table NDiagnostic Status Indication Hot Surface Ignition Control ModuleIgnition and Control Timings Ignition Module Lockout FunctionsTable O Status LED Diagnostic CodesTable P Required Temperature Rise Temperature Rise ChartDomestic Water Heaters Water Velocity ControlPipe Sizing Chart Water ChemistryCirculating Pump Table RPotable Hot Water Temperature Control Settings Domestic Water TemperaturesDomestic Water Minimum Pump PerformanceHigh Water Temperature Limit Control Location of Cold Water Supply Piping ConnectionsOptional Relief Valve Thermal ExpansionCleaning Maintenance Flue Gas Passageways Cleaning ProceduresElectrical Heat Exchanger CleaningCombustion and Ventilation Air Set Up Procedure Cleaning and MaintenanceAdjustment Procedure 495,000 1,255,000 Btu/hr Models Servicing Hot Surface Igniter and Ignition Module Sequence of Operation Ignition System CheckoutPower Supply ON/OFF Rocker SwitchManual Reset High-Limit Thermostat Safety Device TerminalsIgnition Module Electronic Temperature ControllerHeat Transfer Process Gas Valves, Burner Schematic Diagram BTU/HRHI-LIMITS PWR SW Main Unit GAS Valves Blower Pressure Switch Wiring Diagram 15AMPSControl BOX Connections Control BOX Connections

000 - 2, 065, 495 specifications

Lochinvar 000 - 2,495,065 is a cutting-edge water heating solution designed to meet the needs of modern residential and commercial applications. This high-efficiency unit combines advanced engineering with robust technologies, providing unmatched performance and reliability.

One of the standout features of the Lochinvar 000 - 2,495,065 is its high thermal efficiency, which often exceeds 95%. Utilizing condensing technology, the unit harnesses heat from exhaust gases, allowing it to recover otherwise lost energy, thereby reducing operational costs significantly. This efficiency not only lowers energy bills for users but also lessens the environmental impact by minimizing greenhouse gas emissions.

The Lochinvar 000 - 2,495,065 is equipped with a lightweight stainless steel heat exchanger. This construction ensures exceptional corrosion resistance and longevity, extending the lifespan of the unit while maintaining optimal performance. The stainless steel design also contributes to faster heating times, making it ideal for high-demand environments.

In terms of control technologies, the Lochinvar 000 - 2,495,065 features an intuitive touchscreen interface. This user-friendly design allows for seamless operation, real-time monitoring, and easy adjustments to temperature settings. Additionally, it facilitates remote diagnostics, promoting efficient maintenance and reducing downtime, which is crucial for busy facilities.

For enhanced safety, the Lochinvar 000 - 2,495,065 includes multiple safety mechanisms, such as over-temperature protection, flame safeguard, and leak detection systems. These safety features ensure secure operation and give users peace of mind.

Moreover, the unit is compatible with various fuel sources, including natural gas and propane, making it versatile and adaptable to different infrastructure requirements. This flexibility ensures that the Lochinvar 000 - 2,495,065 can be integrated into various settings, from residential homes to large commercial buildings.

Another significant characteristic is its compact design, allowing for easy installation in tight spaces. The footprint of the Lochinvar 000 - 2,495,065 makes it an ideal solution for applications where space is at a premium, without compromising on performance.

In summary, Lochinvar 000 - 2,495,065 represents a premium choice for water heating solutions, merging advanced technologies, high efficiency, and user-friendly design to cater to a wide range of heating needs while ensuring safety and sustainability.