Lochinvar 065, 495, 000 - 2 service manual Electronic Temperature Controller, Ignition Module

Page 46

Hydronic Heating Boilers and Domestic Water Heaters

Electronic Temperature Controller

(Operator)

A 2-stage electronic temperature controller is provided on the unit and it serves to maintain a user selectable temperature set point. Ultimately, the temperature controller delivers 24VAC to the ignition module and pressure switch when it senses heat mode is desired. It also activates the pump relay. If more heat is needed, it activates the high fire stage.

Ignition Module

(Controlled by Electronic Temperature Controller)

One ignition module is provided on the unit. Upon sensing the 24VAC delivered to it by the electronic temperature controller, the ignition module checks for a shorted pressure switch and then, provided the air switch isn't shorted, supplies 120VAC to its blower output relay and waits for a pressure switch signal.

Two Speed Blower (Controlled by Ignition Module and Relay Board)

A single 2-speed blower on the 985,000 - 2,065,000 Btu/hr models (single 1-speed blower on the 495,000 - 745,000 Btu/hr models) provide combustion air to the unit. The blower is provided with a high and low speed tap. The blower operates in tandem with the ignition module when a call for heat signal is received. Depending upon the number of stages in operation, the blower's speed may increase or decrease accordingly.

Pressure Switch (Activated by Blower Turning On)

One pressure switch is provided to monitor the blower On/Off operation. Upon a call for heat, 24VAC is delivered to the pressure switch. If the blower generates adequate air pressure, the pressure switch closes to deliver 24VAC to the ignition module pressure switch monitoring input terminal.

Prepurge (Ignition Module Function)

Once the ignition module sees a 24VAC input from the pressure switch, it runs the blower for approximately 15 seconds in order to purge the combustion chamber of any unburned fuel/air mixture.

Trial for Ignition (Ignition Module Function)

Once the ignition module has completed its prepurge period, it turns on the hot surface igniter. Once the hot surface igniter's current draw reaches a proper level, the ignition module begins a trial for ignition period of approximately 25 seconds to allow time for the igniter to reach the ignition temperature necessary to ignite the fuel/air mixture.

Igniter (Controlled by Ignition Module)

One igniter is provided in order to ignite the fuel/air mixture and its on/off operation is controlled by the ignition module.

Relay Board (Controlled by Electronic Temperature Controller and Ignition Module)

A small relay board is provided on the 985,000 - 2,065,000 Btu/hr models to switch the blower from low to high speed and to deliver power from the low fire stage (Stage 1) to the high fire stage (Stage 2) depending upon the electronic thermostat's settings.

Ignition (Ignition Module Function)

Once the trial for ignition period has been completed, the ignition module sends 24VAC to the gas valves on the low fire stage (Stage 1). Gas valves should open and allow gas to flow to the burners in Stage 1 being energized. The fuel/air mixture should ignite from the hot surface igniter. Once this voltage has been sent to the valves, the hot surface igniter is turned off. The ignition module then monitors the status of the flame and will either allow ignition to continue or shut down the gas valves should flame not be proven and proceed to a Flame Failure condition. If flame was proven briefly during the ignition period, the module may not proceed to Flame Failure, but rather post-purge and then go into another trial for ignition.

Heat Transfer Process (Gas Valves, Burner,

and Heat Exchanger)

Once flame has been proven, the ignition module will hold the gas valves open as long as there is proof of flame and a call for heat is present. If the low fire stage cannot provide enough heat to raise the system temperature, the electronic temperature controller turns on the high fire stage. The high fire stage will operate until the system water temperature shows a gain that can be handled by low fire operation. The high fire stage shuts off at this point. When the low-fire stage alone produces more heat than is required, the electronic temperature controller turns off the call for heat.

Post-Purge(Ignition Module Function)

When 24VAC is removed from the ignition module's thermostat input, the module turns off the gas valves and maintains the blower for approximately 25 seconds in order to allow the combustion chamber to be purged of all combustion by-products.

Pump Delay (Electronic Thermostat Function)

When the electronic thermostat removes 24VAC from the ignition module, it continues to hold the pump relay on for 30 seconds in order to get the remaining heat out of the combustion chamber. The pump then turns off to prevent the heat in the water from going back into the combustion chamber and up the flue.

Idle (Electronic Thermostat Function)

After completion of the post-purge cycle, the unit will go into an idle state whereby the electronic thermostat continuously monitors the water temperature until the water temperature drops to levels that require additional heat.

46

Image 46
Contents Domestic Water Heaters Save this manual for future referenceHydronic Heating Boilers and Domestic Water Heaters Safety Information General Product InformationHydronic Heating Boilers and Domestic Water Heaters Product Identification Front and Rear ViewClearances from Combustible Construction InstallationBase for Combustible Floors Shut-Down and Draining Outdoor Boiler InstallationHydronic System Antifreeze Pump OperationFreeze Protection for a Heating Boiler System if required Installing Combustion Air FilterCombustion Air Filter Combustion Air Options One OpeningExhaust Fans Installation VentingGeneral Information Venting SupportTABLE-A Flue Pipe Sizes Vent System OptionsTable B TABLE-CFlue Outlet Piping Conventional Negative Draft VentingNegative Draft Common Venting SystemsOutdoor Installation Venting Masonry Chimney InstallationsOutdoor Vent/Air Inlet Location Table DOutdoor Vent Kits Outdoor Vent KitGas Piping Gas Pressure TestInput Max Min Connecting Gas Piping to Unit Gas Train and ControlsChecking Gas Supply Pressure Combination Gas ValvesVenting of Combination Gas Valves Gas Manifold Pressure Adjustment Measuring Gas Supply Pressure at Combination Gas ValveNET Manifold Pressure Regulator Pressure Less Front Chamber PressureRelief Valve Water Flow SwitchLow Water Cutoff If EquippedTable J Terminal Strip Connection OptionsNominal AMP Draw Data Water Connections Heating Boilers Only General Plumbing RulesPrimary/Secondary Boiler Piping Radiant Floor and Snow Melt Heating Systems Low Temperature Return Water SystemsInput LTV Valve Kit Btu/hr Table L Installation with a Chilled Water SystemSystem Temperature Rise Chart Based on Btu/hr Input 10ºF 20ºF 30ºF 40ºF 50ºF 60ºFBoiler Bypass Requirements Temperature/Pressure GaugeBoiler Flow Rate Filling the SystemOperation Lighting InstructionsLocating Temperature Control To Turn Off Gas To ApplianceSet Point Temperature Control SettingsTable M Maximum Set Point DeterminationShutdown Outdoor Air Reset OptionHigh-Fire Offset Outdoor Air Max O.A. MaxBoiler Application Temperature Control SensorsPlacement of Sensors Water Heater ApplicationHot Surface Igniter and Ignition Control Module Remote Wire ConnectionWire Maximum Gauge Table NIgnition and Control Timings Diagnostic Status IndicationHot Surface Ignition Control Module Ignition Module Lockout FunctionsTable O Status LED Diagnostic CodesTable P Domestic Water Heaters Required Temperature RiseTemperature Rise Chart Water Velocity ControlCirculating Pump Pipe Sizing ChartWater Chemistry Table RDomestic Water Potable Hot Water Temperature Control SettingsDomestic Water Temperatures Minimum Pump PerformanceOptional Relief Valve High Water Temperature Limit ControlLocation of Cold Water Supply Piping Connections Thermal ExpansionCleaning Maintenance Flue Gas Passageways Cleaning ProceduresElectrical Heat Exchanger CleaningCombustion and Ventilation Air Set Up Procedure Cleaning and MaintenanceAdjustment Procedure 495,000 1,255,000 Btu/hr Models Servicing Hot Surface Igniter and Ignition Module Sequence of Operation Ignition System CheckoutManual Reset High-Limit Thermostat Power SupplyON/OFF Rocker Switch Safety Device TerminalsIgnition Module Electronic Temperature ControllerHeat Transfer Process Gas Valves, Burner Schematic Diagram BTU/HRHI-LIMITS PWR SW Main Unit GAS Valves Blower Pressure Switch Wiring Diagram 15AMPSControl BOX Connections Control BOX Connections

000 - 2, 065, 495 specifications

Lochinvar 000 - 2,495,065 is a cutting-edge water heating solution designed to meet the needs of modern residential and commercial applications. This high-efficiency unit combines advanced engineering with robust technologies, providing unmatched performance and reliability.

One of the standout features of the Lochinvar 000 - 2,495,065 is its high thermal efficiency, which often exceeds 95%. Utilizing condensing technology, the unit harnesses heat from exhaust gases, allowing it to recover otherwise lost energy, thereby reducing operational costs significantly. This efficiency not only lowers energy bills for users but also lessens the environmental impact by minimizing greenhouse gas emissions.

The Lochinvar 000 - 2,495,065 is equipped with a lightweight stainless steel heat exchanger. This construction ensures exceptional corrosion resistance and longevity, extending the lifespan of the unit while maintaining optimal performance. The stainless steel design also contributes to faster heating times, making it ideal for high-demand environments.

In terms of control technologies, the Lochinvar 000 - 2,495,065 features an intuitive touchscreen interface. This user-friendly design allows for seamless operation, real-time monitoring, and easy adjustments to temperature settings. Additionally, it facilitates remote diagnostics, promoting efficient maintenance and reducing downtime, which is crucial for busy facilities.

For enhanced safety, the Lochinvar 000 - 2,495,065 includes multiple safety mechanisms, such as over-temperature protection, flame safeguard, and leak detection systems. These safety features ensure secure operation and give users peace of mind.

Moreover, the unit is compatible with various fuel sources, including natural gas and propane, making it versatile and adaptable to different infrastructure requirements. This flexibility ensures that the Lochinvar 000 - 2,495,065 can be integrated into various settings, from residential homes to large commercial buildings.

Another significant characteristic is its compact design, allowing for easy installation in tight spaces. The footprint of the Lochinvar 000 - 2,495,065 makes it an ideal solution for applications where space is at a premium, without compromising on performance.

In summary, Lochinvar 000 - 2,495,065 represents a premium choice for water heating solutions, merging advanced technologies, high efficiency, and user-friendly design to cater to a wide range of heating needs while ensuring safety and sustainability.