Lochinvar 065, 495, 000 - 2 service manual Operation, Lighting Instructions

Page 28

Hydronic Heating Boilers and Domestic Water Heaters

INSTALLATION

Continued

8.Recheck all air vents as described in step 4.

9.Inspect the liquid level in the expansion tank. The system must be full and under normal operating pressure to ensure proper water level in the expansion tank. Ensure that diaphragm type expansion tanks are properly charged and not water logged.

10.Start the boiler according to the operating instructions in this manual. Operate the system, including the pump, boiler and radiation units, for one hour.

11.Recheck the water level in the expansion tank. If it exceeds half the tank volume, open the tank to reduce the water level. Recheck pressure charge on diaphragm type tanks.

12.Shut down the entire system and vent all radiation units and high points in the system.

13.Close the water makeup valve and check the strainer and pressure reducing valve for sediment or debris. Reopen the water makeup valve.

14.Verify system pressure with the boiler pressure gauge before beginning regular operation.

15.Within three days of startup, recheck and bleed all air vents and the expansion tank using these instructions.

WATER TREATMENT

In hard water areas, water treatment should be used to reduce the introduction of minerals to the system. Minerals in the water can collect in the heat exchanger tubes and cause noise on operation. Excessive build up of minerals in the heat exchanger can cause a non-warrantable failure.

OPERATION

FOR YOUR SAFETY READ BEFORE OPERATING

￿WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A.This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

B.BEFORE OPERATING, smell around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electric switch; do not use any phone in your building.

• Immediately call your gas supplier from a neighbors phone.

• Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

C.Use only your hand to turn the gas control lever. Never use tools. If the lever will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D.Do not use this boiler if any part has been under water. Immediately call a qualified service technician to replace the boiler. The possible damage to a flooded boiler can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.

Lighting Instructions

1.STOP! Read the safety information.

2.Set the temperature control to the desired settings (see Setting Temperature Control, page 29).

3.Loosen the knurled knob at the bottom of the control panel cover (see Figure 31).

4.Grasp the bottom of the control panel cover and pull out and down.

5.Locate the ON/OFF switch inside the control area. The switch is located to the left of the control panel (see Figure 32).

6.Turn the power switch to the “OFF” position.

7.This unit is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.

28

Image 28
Contents Domestic Water Heaters Save this manual for future referenceHydronic Heating Boilers and Domestic Water Heaters Safety Information General Product InformationHydronic Heating Boilers and Domestic Water Heaters Product Identification Front and Rear ViewClearances from Combustible Construction InstallationBase for Combustible Floors Outdoor Boiler Installation Hydronic System AntifreezeShut-Down and Draining Pump OperationFreeze Protection for a Heating Boiler System if required Installing Combustion Air FilterCombustion Air Filter Combustion Air Options One OpeningInstallation Venting General InformationExhaust Fans Venting SupportTABLE-A Vent System Options Table BFlue Pipe Sizes TABLE-CConventional Negative Draft Venting Negative DraftFlue Outlet Piping Common Venting SystemsOutdoor Installation Venting Masonry Chimney InstallationsTable D Outdoor Vent KitsOutdoor Vent/Air Inlet Location Outdoor Vent KitGas Piping Gas Pressure TestInput Max Min Connecting Gas Piping to Unit Gas Train and ControlsChecking Gas Supply Pressure Combination Gas ValvesVenting of Combination Gas Valves Gas Manifold Pressure Adjustment Measuring Gas Supply Pressure at Combination Gas ValveNET Manifold Pressure Regulator Pressure Less Front Chamber PressureWater Flow Switch Low Water CutoffRelief Valve If EquippedTable J Terminal Strip Connection OptionsNominal AMP Draw Data Water Connections Heating Boilers Only General Plumbing RulesPrimary/Secondary Boiler Piping Radiant Floor and Snow Melt Heating Systems Low Temperature Return Water SystemsInput LTV Valve Kit Btu/hr Installation with a Chilled Water System System Temperature Rise Chart Based on Btu/hr InputTable L 10ºF 20ºF 30ºF 40ºF 50ºF 60ºFTemperature/Pressure Gauge Boiler Flow RateBoiler Bypass Requirements Filling the SystemOperation Lighting InstructionsLocating Temperature Control To Turn Off Gas To ApplianceTemperature Control Settings Table MSet Point Maximum Set Point DeterminationOutdoor Air Reset Option High-Fire OffsetShutdown Outdoor Air Max O.A. MaxTemperature Control Sensors Placement of SensorsBoiler Application Water Heater ApplicationRemote Wire Connection Wire Maximum GaugeHot Surface Igniter and Ignition Control Module Table NDiagnostic Status Indication Hot Surface Ignition Control ModuleIgnition and Control Timings Ignition Module Lockout FunctionsTable O Status LED Diagnostic CodesTable P Required Temperature Rise Temperature Rise ChartDomestic Water Heaters Water Velocity ControlPipe Sizing Chart Water ChemistryCirculating Pump Table RPotable Hot Water Temperature Control Settings Domestic Water TemperaturesDomestic Water Minimum Pump PerformanceHigh Water Temperature Limit Control Location of Cold Water Supply Piping ConnectionsOptional Relief Valve Thermal ExpansionCleaning Maintenance Flue Gas Passageways Cleaning ProceduresElectrical Heat Exchanger CleaningCombustion and Ventilation Air Set Up Procedure Cleaning and MaintenanceAdjustment Procedure 495,000 1,255,000 Btu/hr Models Servicing Hot Surface Igniter and Ignition Module Sequence of Operation Ignition System CheckoutPower Supply ON/OFF Rocker SwitchManual Reset High-Limit Thermostat Safety Device TerminalsIgnition Module Electronic Temperature ControllerHeat Transfer Process Gas Valves, Burner Schematic Diagram BTU/HRHI-LIMITS PWR SW Main Unit GAS Valves Blower Pressure Switch Wiring Diagram 15AMPSControl BOX Connections Control BOX Connections

000 - 2, 065, 495 specifications

Lochinvar 000 - 2,495,065 is a cutting-edge water heating solution designed to meet the needs of modern residential and commercial applications. This high-efficiency unit combines advanced engineering with robust technologies, providing unmatched performance and reliability.

One of the standout features of the Lochinvar 000 - 2,495,065 is its high thermal efficiency, which often exceeds 95%. Utilizing condensing technology, the unit harnesses heat from exhaust gases, allowing it to recover otherwise lost energy, thereby reducing operational costs significantly. This efficiency not only lowers energy bills for users but also lessens the environmental impact by minimizing greenhouse gas emissions.

The Lochinvar 000 - 2,495,065 is equipped with a lightweight stainless steel heat exchanger. This construction ensures exceptional corrosion resistance and longevity, extending the lifespan of the unit while maintaining optimal performance. The stainless steel design also contributes to faster heating times, making it ideal for high-demand environments.

In terms of control technologies, the Lochinvar 000 - 2,495,065 features an intuitive touchscreen interface. This user-friendly design allows for seamless operation, real-time monitoring, and easy adjustments to temperature settings. Additionally, it facilitates remote diagnostics, promoting efficient maintenance and reducing downtime, which is crucial for busy facilities.

For enhanced safety, the Lochinvar 000 - 2,495,065 includes multiple safety mechanisms, such as over-temperature protection, flame safeguard, and leak detection systems. These safety features ensure secure operation and give users peace of mind.

Moreover, the unit is compatible with various fuel sources, including natural gas and propane, making it versatile and adaptable to different infrastructure requirements. This flexibility ensures that the Lochinvar 000 - 2,495,065 can be integrated into various settings, from residential homes to large commercial buildings.

Another significant characteristic is its compact design, allowing for easy installation in tight spaces. The footprint of the Lochinvar 000 - 2,495,065 makes it an ideal solution for applications where space is at a premium, without compromising on performance.

In summary, Lochinvar 000 - 2,495,065 represents a premium choice for water heating solutions, merging advanced technologies, high efficiency, and user-friendly design to cater to a wide range of heating needs while ensuring safety and sustainability.