Lochinvar 495, 065 Boiler Flow Rate, Boiler Bypass Requirements, Temperature/Pressure Gauge

Page 27

Installation and Service Manual

Boiler Flow Rate

￿CAUTION: The maximum flow rate for models 495,000 - 745,000 Btu/hr is 60 GPM and 90 GPM on 985,000 - 2,065,000 models. Do not exceed the maximum flow rate of the heating boiler.

If higher flow rates are required through the boiler, an optional Cupro-Nickel heat exchanger is available. When using a Cupro-Nickel heat exchanger, GPM can be increased by 30 percent. Consult the factory for specific application requirements.

The heat exchanger is generally capable of operating within the design flow rates of the building heating system. Should the flow rate exceed the maximum allowable flow rate through the boiler an external bypass must be installed. The bypass should be fully sized with a balancing valve to allow for proper adjustment of flow. Flow rate can be determined by measuring the temperature rise through the boiler.

Boiler Bypass Requirements

The installer must ensure that the boiler is supplied with adequate flow without excessive temperature rise. It is recommended that this boiler be installed with a bypass in the piping if the maximum recommended flow rate is exceeded. The bypass will help to ensure that the boiler can be supplied with adequate water flow. Flow rates exceeding the maximum recommended flow will result in erosion of the boiler tubes. A typical bypass with a valve is shown in Figure 30 will allow control of boiler flow.

Temperature/Pressure Gauge

This boiler is equipped with a dial type temperature/pressure gauge. This gauge is factory installed in the outlet side of the heat exchanger. The gauge has one scale to read system pressure and a separate scale to read water temperature in degrees, Fahrenheit.

Figure 30 - Boiler Bypass Piping for High Flow Systems

Filling the System

All air must be purged from the system for proper operation. An air scoop and air vent must be located close to the boiler outlet and there should be a minimum distance between the cold water feed and the system purge valve.

1.Close all drain cocks and air vents.

2.Open the makeup water valve and slowly fill the system.

3.If a makeup water pump is employed, adjust the pressure to provide a minimum of 12 psi at the highest point in the system. If a pressure regulator is also installed in the line, it should be adjusted to the same pressure.

4.Close all valves. Purge one circuit at a time as follows:

A.Open one circuit drain valve and let the water drain for at least five minutes. Ensure that there are no air bubbles visible in the water stream before closing the drain valve.

B.Repeat this procedure for each circuit.

5.Open all valves after all circuits have been purged. Make sure there are no system leaks.

￿CAUTION: Do not use petroleum based stop leak products. All system leaks must be repaired. The constant addition of make-up water can cause damage to the boiler heat exchanger due to scale accumulation. Scale reduces flow and heat transfer, causing overheating of the heat exchanger.

6.Run the system circulating pump for a minimum of 30 minutes with the boiler turned off.

7.Open all strainers in the system and check for debris.

27

Image 27
Contents Save this manual for future reference Domestic Water HeatersHydronic Heating Boilers and Domestic Water Heaters General Product Information Safety InformationHydronic Heating Boilers and Domestic Water Heaters Front and Rear View Product IdentificationInstallation Clearances from Combustible ConstructionBase for Combustible Floors Pump Operation Outdoor Boiler InstallationHydronic System Antifreeze Shut-Down and DrainingInstalling Combustion Air Filter Freeze Protection for a Heating Boiler System if requiredCombustion Air Filter One Opening Combustion Air OptionsVenting Support Installation VentingGeneral Information Exhaust FansTABLE-A TABLE-C Vent System OptionsTable B Flue Pipe SizesCommon Venting Systems Conventional Negative Draft VentingNegative Draft Flue Outlet PipingMasonry Chimney Installations Outdoor Installation VentingOutdoor Vent Kit Table DOutdoor Vent Kits Outdoor Vent/Air Inlet LocationGas Pressure Test Gas PipingInput Max Min Gas Train and Controls Connecting Gas Piping to UnitCombination Gas Valves Checking Gas Supply PressureVenting of Combination Gas Valves Measuring Gas Supply Pressure at Combination Gas Valve Gas Manifold Pressure AdjustmentRegulator Pressure Less Front Chamber Pressure NET Manifold PressureIf Equipped Water Flow SwitchLow Water Cutoff Relief ValveTerminal Strip Connection Options Table JNominal AMP Draw Data General Plumbing Rules Water Connections Heating Boilers OnlyPrimary/Secondary Boiler Piping Low Temperature Return Water Systems Radiant Floor and Snow Melt Heating SystemsInput LTV Valve Kit Btu/hr 10ºF 20ºF 30ºF 40ºF 50ºF 60ºF Installation with a Chilled Water SystemSystem Temperature Rise Chart Based on Btu/hr Input Table LFilling the System Temperature/Pressure GaugeBoiler Flow Rate Boiler Bypass RequirementsLighting Instructions OperationTo Turn Off Gas To Appliance Locating Temperature ControlMaximum Set Point Determination Temperature Control SettingsTable M Set PointOutdoor Air Max O.A. Max Outdoor Air Reset OptionHigh-Fire Offset ShutdownWater Heater Application Temperature Control SensorsPlacement of Sensors Boiler ApplicationTable N Remote Wire ConnectionWire Maximum Gauge Hot Surface Igniter and Ignition Control ModuleIgnition Module Lockout Functions Diagnostic Status IndicationHot Surface Ignition Control Module Ignition and Control TimingsStatus LED Diagnostic Codes Table OTable P Water Velocity Control Required Temperature RiseTemperature Rise Chart Domestic Water HeatersTable R Pipe Sizing ChartWater Chemistry Circulating PumpMinimum Pump Performance Potable Hot Water Temperature Control SettingsDomestic Water Temperatures Domestic WaterThermal Expansion High Water Temperature Limit ControlLocation of Cold Water Supply Piping Connections Optional Relief ValveFlue Gas Passageways Cleaning Procedures Cleaning MaintenanceHeat Exchanger Cleaning ElectricalCombustion and Ventilation Air Cleaning and Maintenance Set Up ProcedureAdjustment Procedure 495,000 1,255,000 Btu/hr Models Servicing Hot Surface Igniter and Ignition Module Ignition System Checkout Sequence of OperationSafety Device Terminals Power SupplyON/OFF Rocker Switch Manual Reset High-Limit ThermostatElectronic Temperature Controller Ignition ModuleHeat Transfer Process Gas Valves, Burner BTU/HR Schematic DiagramHI-LIMITS PWR SW Main Unit GAS Valves Blower Pressure Switch 15AMPS Wiring DiagramControl BOX Connections Control BOX Connections

000 - 2, 065, 495 specifications

Lochinvar 000 - 2,495,065 is a cutting-edge water heating solution designed to meet the needs of modern residential and commercial applications. This high-efficiency unit combines advanced engineering with robust technologies, providing unmatched performance and reliability.

One of the standout features of the Lochinvar 000 - 2,495,065 is its high thermal efficiency, which often exceeds 95%. Utilizing condensing technology, the unit harnesses heat from exhaust gases, allowing it to recover otherwise lost energy, thereby reducing operational costs significantly. This efficiency not only lowers energy bills for users but also lessens the environmental impact by minimizing greenhouse gas emissions.

The Lochinvar 000 - 2,495,065 is equipped with a lightweight stainless steel heat exchanger. This construction ensures exceptional corrosion resistance and longevity, extending the lifespan of the unit while maintaining optimal performance. The stainless steel design also contributes to faster heating times, making it ideal for high-demand environments.

In terms of control technologies, the Lochinvar 000 - 2,495,065 features an intuitive touchscreen interface. This user-friendly design allows for seamless operation, real-time monitoring, and easy adjustments to temperature settings. Additionally, it facilitates remote diagnostics, promoting efficient maintenance and reducing downtime, which is crucial for busy facilities.

For enhanced safety, the Lochinvar 000 - 2,495,065 includes multiple safety mechanisms, such as over-temperature protection, flame safeguard, and leak detection systems. These safety features ensure secure operation and give users peace of mind.

Moreover, the unit is compatible with various fuel sources, including natural gas and propane, making it versatile and adaptable to different infrastructure requirements. This flexibility ensures that the Lochinvar 000 - 2,495,065 can be integrated into various settings, from residential homes to large commercial buildings.

Another significant characteristic is its compact design, allowing for easy installation in tight spaces. The footprint of the Lochinvar 000 - 2,495,065 makes it an ideal solution for applications where space is at a premium, without compromising on performance.

In summary, Lochinvar 000 - 2,495,065 represents a premium choice for water heating solutions, merging advanced technologies, high efficiency, and user-friendly design to cater to a wide range of heating needs while ensuring safety and sustainability.