Lochinvar 065, 495, 000 - 2 Terminal Strip Connection Options, Table J, Nominal AMP Draw Data

Page 22

Hydronic Heating Boilers and Domestic Water Heaters

INSTALLATION

Continued

TABLE - J

Nominal AMP Draw Data

TABLE

AMP Draw Data

 

Btu/Hr

 

 

 

Approximate

Input

Controls

Fan

Total Amps

 

 

 

 

 

495,000

4.6

3.4

 

8.0

645,000

4.6

3.4

 

8.0

745,000

4.6

3.4

 

8.0

985,000

4.6

3.4

 

8.0

1,255,000

4.6

3.4

 

8.0

1,435,000

4.6

3.8

 

8.4

 

 

 

 

 

1,795,000

4.6

3.8

 

8.4

 

 

 

 

 

2,065,000

4.6

3.8

 

8.4

 

 

 

 

 

IMPORTANT: Do not block access to the electrical cover plate when installing electrical conduit.

External EMS Connection to Terminal Strip for Stage Firing Control of Burners

This unit is equipped with a factory installed terminal strip for connection of an energy management system (EMS) to the burner stages. The EMS terminal strip is located in the unit's junction box. Ensure that all wiring used for connection to this terminal strip is properly sized per the recommendations in TABLE-L. When connecting an EMS to this terminal strip to sequence on each stage of burner operation, the unit's internal thermostat or electronic sequencer should be set as an additional high limit control. This will prevent problems between the set points of the EMS and the boiler's internal controller.

Terminal Strip Connection Options

(Models 985,000 - 2,065,000 Btu/hr Only)

Figure 23A - Models 495,000 - 745,000 Btu/hr Control Panel Component Location Drawing

Figure 23B - Models 985,000 - 2,065,000 Btu/hr Control Panel Component Location Drawing

Figure 24A shows the position of jumpers as shipped from the factory for stand-alone operation of boilers or water heaters.

Figure 24B shows connections to the terminal strip for Remote ON/OFF control of the boiler or water heater. The 1C-1NO jumper must be removed when making these wiring connections. This remote ON/OFF control will provide an Enable/Disable signal to the unit and allow the unit to operate based on the stage set points, until the remote ON/OFF signal is cancelled.

Figure 24C shows the connections necessary to operate the unit as a two-stage (High/Low Fire) boiler or water heater from an Energy Management System (EMS). The actual set point temperatures are controlled by the EMS. The High Fire Offset on the electronic temperature control in the unit must be set to zero and the set point must be set to a value which will function as an upper limit for proper operation under this two-stage control from an EMS.

Figure 24D shows the Continuous and Intermittent terminals. External safety devices connected to these terminals will function to protect the unit. Devices connected to the Intermittent terminals (B1 and B2) are monitored only when there is an active Call for Heat. Devices connected to the Continuous terminals (A1 and A2) are monitored continuously and will activate an alarm (if the unit is equipped with the alarm option) anytime the safety device senses an abnormal condition. An additional wire may be field-installed from these safety devices to terminals A3 or B3 (as appropriate) to activate an alarm (if the unit is equipped with the alarm option).

22

Image 22
Contents Domestic Water Heaters Save this manual for future referenceHydronic Heating Boilers and Domestic Water Heaters Safety Information General Product InformationHydronic Heating Boilers and Domestic Water Heaters Product Identification Front and Rear ViewClearances from Combustible Construction InstallationBase for Combustible Floors Shut-Down and Draining Outdoor Boiler InstallationHydronic System Antifreeze Pump OperationFreeze Protection for a Heating Boiler System if required Installing Combustion Air FilterCombustion Air Filter Combustion Air Options One OpeningExhaust Fans Installation VentingGeneral Information Venting SupportTABLE-A Flue Pipe Sizes Vent System OptionsTable B TABLE-CFlue Outlet Piping Conventional Negative Draft VentingNegative Draft Common Venting SystemsOutdoor Installation Venting Masonry Chimney InstallationsOutdoor Vent/Air Inlet Location Table DOutdoor Vent Kits Outdoor Vent KitGas Piping Gas Pressure TestInput Max Min Connecting Gas Piping to Unit Gas Train and ControlsChecking Gas Supply Pressure Combination Gas ValvesVenting of Combination Gas Valves Gas Manifold Pressure Adjustment Measuring Gas Supply Pressure at Combination Gas ValveNET Manifold Pressure Regulator Pressure Less Front Chamber PressureRelief Valve Water Flow SwitchLow Water Cutoff If EquippedTable J Terminal Strip Connection OptionsNominal AMP Draw Data Water Connections Heating Boilers Only General Plumbing RulesPrimary/Secondary Boiler Piping Radiant Floor and Snow Melt Heating Systems Low Temperature Return Water SystemsInput LTV Valve Kit Btu/hr Table L Installation with a Chilled Water SystemSystem Temperature Rise Chart Based on Btu/hr Input 10ºF 20ºF 30ºF 40ºF 50ºF 60ºFBoiler Bypass Requirements Temperature/Pressure GaugeBoiler Flow Rate Filling the SystemOperation Lighting InstructionsLocating Temperature Control To Turn Off Gas To ApplianceSet Point Temperature Control SettingsTable M Maximum Set Point DeterminationShutdown Outdoor Air Reset OptionHigh-Fire Offset Outdoor Air Max O.A. MaxBoiler Application Temperature Control SensorsPlacement of Sensors Water Heater ApplicationHot Surface Igniter and Ignition Control Module Remote Wire ConnectionWire Maximum Gauge Table NIgnition and Control Timings Diagnostic Status IndicationHot Surface Ignition Control Module Ignition Module Lockout FunctionsTable O Status LED Diagnostic CodesTable P Domestic Water Heaters Required Temperature RiseTemperature Rise Chart Water Velocity ControlCirculating Pump Pipe Sizing ChartWater Chemistry Table RDomestic Water Potable Hot Water Temperature Control SettingsDomestic Water Temperatures Minimum Pump PerformanceOptional Relief Valve High Water Temperature Limit ControlLocation of Cold Water Supply Piping Connections Thermal ExpansionCleaning Maintenance Flue Gas Passageways Cleaning ProceduresElectrical Heat Exchanger CleaningCombustion and Ventilation Air Set Up Procedure Cleaning and MaintenanceAdjustment Procedure 495,000 1,255,000 Btu/hr Models Servicing Hot Surface Igniter and Ignition Module Sequence of Operation Ignition System CheckoutManual Reset High-Limit Thermostat Power SupplyON/OFF Rocker Switch Safety Device TerminalsIgnition Module Electronic Temperature ControllerHeat Transfer Process Gas Valves, Burner Schematic Diagram BTU/HRHI-LIMITS PWR SW Main Unit GAS Valves Blower Pressure Switch Wiring Diagram 15AMPSControl BOX Connections Control BOX Connections

000 - 2, 065, 495 specifications

Lochinvar 000 - 2,495,065 is a cutting-edge water heating solution designed to meet the needs of modern residential and commercial applications. This high-efficiency unit combines advanced engineering with robust technologies, providing unmatched performance and reliability.

One of the standout features of the Lochinvar 000 - 2,495,065 is its high thermal efficiency, which often exceeds 95%. Utilizing condensing technology, the unit harnesses heat from exhaust gases, allowing it to recover otherwise lost energy, thereby reducing operational costs significantly. This efficiency not only lowers energy bills for users but also lessens the environmental impact by minimizing greenhouse gas emissions.

The Lochinvar 000 - 2,495,065 is equipped with a lightweight stainless steel heat exchanger. This construction ensures exceptional corrosion resistance and longevity, extending the lifespan of the unit while maintaining optimal performance. The stainless steel design also contributes to faster heating times, making it ideal for high-demand environments.

In terms of control technologies, the Lochinvar 000 - 2,495,065 features an intuitive touchscreen interface. This user-friendly design allows for seamless operation, real-time monitoring, and easy adjustments to temperature settings. Additionally, it facilitates remote diagnostics, promoting efficient maintenance and reducing downtime, which is crucial for busy facilities.

For enhanced safety, the Lochinvar 000 - 2,495,065 includes multiple safety mechanisms, such as over-temperature protection, flame safeguard, and leak detection systems. These safety features ensure secure operation and give users peace of mind.

Moreover, the unit is compatible with various fuel sources, including natural gas and propane, making it versatile and adaptable to different infrastructure requirements. This flexibility ensures that the Lochinvar 000 - 2,495,065 can be integrated into various settings, from residential homes to large commercial buildings.

Another significant characteristic is its compact design, allowing for easy installation in tight spaces. The footprint of the Lochinvar 000 - 2,495,065 makes it an ideal solution for applications where space is at a premium, without compromising on performance.

In summary, Lochinvar 000 - 2,495,065 represents a premium choice for water heating solutions, merging advanced technologies, high efficiency, and user-friendly design to cater to a wide range of heating needs while ensuring safety and sustainability.