Stovax 8547LUC-P8547LUC, ASHDON 8546LUC-P8546LUC, 8545LUC, P8545LUC manual Rear Flue, TOP Exit

Page 10

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1.2 REAR FLUE 8526

Terminal dimensions:

395 x 200 x 200 mm (H x W x D)

Cut to length as required on site.

2

AR0630

Guard Supplied.

1.3 TOP EXIT

Two types of top exit flue terminal are available, horizontal and vertical. For a horizontal terminal, decide on the terminal position and measure the height from the top of the appliance to the centre of the required hole. For minimum and maximum flue dimensions see diagram 3.

Access must be either above or at the side of the installation to allow the flue to be assembled on top of the appliance. When a horizontal terminal is used, the vertical sections are assembled first, then the 90-degree elbow and finally the horizontal section including the terminal. If a masonry installation is to be built, a suitable lintel must be used to support the opening.

Only the horizontal terminal section can be reduced in size.

Refer to Balanced Flue Technical Information for details of flue length.

1.4 TOP FLUE UP & OUT KIT (8523/8523AN)

Vertical from the top of the appliance then horizontally out. (See diagram 3.)

The basic kit comprises:

1 x 500mm vertical length

1 x 500mm terminal length (cut to length on site) 1 x 90 degree elbow

1 x wall plate

1 x 75mm restrictor fixing screws

The kit is the minimum required. Extra lengths may be added to the vertical and horizontal (see section 1.5), with reference to Diagram 3.

Extra lengths may be added (see section 1.5), with reference to diagram 3 and the installation instructions of the appliance.

3

AR1619

Refer to Table A under 3.2, Installation for identifying when to use the restrictor.

10

Image 10
Contents Clarendon & Ashdon Log Effect Stove Range Contents Flue Check Pass Fail Appliance Commissioning ChecklistGAS Check Lighting the Stove User InstructionsGeneral Turning OFF the StoveHandling & Disposal of Fire Ceramics Cleaning the FireFuel BED Arrangements Never Operate the Stove When the Door is Removed ‘RUNNING IN’ Installation DetailsFlame Failure Device ServicingInstallation Instructions Technical SpecificationFlue and Chimney Requirements Site RequirementsTimber Framed Buildings Rear Flue TOP ExitALL Appliances TOP Flue UP & OUT with Additional BendOptional Extra Flue Lengths & Bends Appliance Location Installation of the GAS SupplyVentilation Minimum ClearanceSafety Precautions InstallationControl Upgrade Installation of the StoveDo not FIX the Flue AT this Stage Vertical & Horizontal Flue Do not Attempt to Shorten ANY Other Section of Flue PipeTable a TOP Exit Vertical only Including Offset TOP Exit Vertical FlueRemove ANY Cardboard Fitment Remaining Fuelbed Arrangements Lighting Commissioning CommissioningServicing Requirements Servicing / Fault Finding ChartsServicing Instructions Ignition Functional CheckFlame Failure Functional Check Pilot will not Stay LIT or Fire Goes OUT in USEMain Burner Replacing PartsPilot Unit Ignition Lead GAS Valve Magnetic Safety ValvePiezo Main InjectorChanging Between GAS Types Primary Aeration PlateShort Spares List Service Records Member of the Stovax Group