Stovax 8544LUC-P8544LUC, ASHDON 8546LUC-P8546LUC, 8545LUC, P8545LUC Vertical & Horizontal Flue

Page 15

INSTALLATION INSTRUCTIONS

INSTALLATION

3.2 TOP EXIT

3.2.1There are two types of top exit flues available, one with a vertical terminal, the other with a horizontal terminal. Minimum and maximum flue lengths are shown in Diagram 3 under Site Requirements, 1.4. There is an optional decorative collar, part No. 8548, to cover the gap between the top plate and the flue.

THIS MUST BE IN PLACE BEFORE THE FLUE IS INSTALLED.

IMPORTANT: WHEN INSTALLING A TOP EXIT FLUE REFER TO THE TECHNICAL SPECIFICATIONS ON THIS PAGE FOR THE APPROPRIATE SIZE RESTRICTOR.

VERTICAL & HORIZONTAL FLUE

TABLE A - TOP EXIT FLUE - VERTICAL AND HORIZONTAL RESTRICTORS

Vertical Flue Height

Horizontal Length

Restrictor Size

From Top of Stove

 

 

 

 

 

500mm to 1490mm

250mm to 1000mm

No restrictor

 

 

 

1500mm to 3000mm

250mm to 5000mm

75mm Ø

 

 

 

3.2.2The appliance is factory set for rear exit, therefore for top exit the spigots and blanking plates must be reversed. See diagram 5. Take care not to drop or damage the gaskets. If a restrictor is required fit this between the small outlet spigot and the air duct. See diagram 5. The large outer spigot must be fitted with the flue fixing hole facing forward.

5

3.2.3If the horizontal terminal is used assemble the required amount of vertical flue including the 90° elbow onto the stove. Drill through the fixing hole in the spigot using a 3.5mm drill and secure with the screw provided. Do not forget the optional decorative collar if you have purchased one. A wall plate is supplied to secure the flue to the inside wall. Bend the tab to 90° and loosely place on the elbow.

6

AR0628

3.2.4To determine the height of the hole for the horizontal flue, measure from the hearth to the centre of the elbow. See Diagram 6.

TAKE CARE WHEN MARKING OUT FOR THE FLUE. IT IS DIFFICULT TO MOVE AFTER INSTALLATION.

A 152mm (6") diameter hole is required to install the flue. This can be achieved by either:

a)Core Drill

b)Hammer & Chisel

It is advisable to drill small holes around the circumference when using method b). Make good at both ends of the hole.

3.2.5The final length of horizontal flue pipe incorporates the terminal. This is the only section that can be shortened.

DO NOT ATTEMPT TO SHORTEN ANY OTHER SECTION OF FLUE PIPE.

The fixing holes for the wall plate can only be marked on the wall. Use the wall plate as a template. The securing tab can be either on top or underneath the flue. See diagram 7.

AR0627

15

Image 15
Contents Clarendon & Ashdon Log Effect Stove Range Contents Appliance Commissioning Checklist Flue Check Pass FailGAS Check Turning OFF the Stove User InstructionsGeneral Lighting the StoveCleaning the Fire Handling & Disposal of Fire CeramicsFuel BED Arrangements Never Operate the Stove When the Door is Removed Servicing Installation DetailsFlame Failure Device ‘RUNNING IN’Technical Specification Installation InstructionsSite Requirements Flue and Chimney RequirementsTimber Framed Buildings TOP Exit Rear FlueTOP Flue UP & OUT with Additional Bend ALL AppliancesOptional Extra Flue Lengths & Bends Minimum Clearance Installation of the GAS SupplyVentilation Appliance LocationInstallation of the Stove InstallationControl Upgrade Safety PrecautionsDo not FIX the Flue AT this Stage Do not Attempt to Shorten ANY Other Section of Flue Pipe Vertical & Horizontal FlueTOP Exit Vertical Flue Table a TOP Exit Vertical only Including OffsetRemove ANY Cardboard Fitment Remaining Fuelbed Arrangements Lighting Commissioning CommissioningIgnition Functional Check Servicing / Fault Finding ChartsServicing Instructions Servicing RequirementsPilot will not Stay LIT or Fire Goes OUT in USE Flame Failure Functional CheckReplacing Parts Main BurnerPilot Unit Ignition Lead Main Injector Magnetic Safety ValvePiezo GAS ValvePrimary Aeration Plate Changing Between GAS TypesShort Spares List Service Records Member of the Stovax Group