Carrier 48EZ(N)-A Pre-Start-Up, Control Voltage Connections, Transformer Protection

Page 13

Control Voltage Connections

Do not use any type of power-stealing thermostat. Unit control problems may result.

Use no. 18 American Wire Gage (AWG) color-coded, insulated (35_C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35_C minimum) wires.

Locate the seven (eight on 3-phase) low voltage thermostat leads in 24 volt splice box. See Fig. 9 for connection diagram. Run the low-voltage leads from the thermostat, through the control wiring inlet hole grommet (Fig. 2 and 3), and into the low-voltage splice box. Provide a drip loop before running wires through panel. Secure and strain relief all wires so that they do not interfere with operation of unit. A gray wire is standard on 3-phase unit for connection to an economizer.

Balance Point Setting-Thermidistat or Hybrid

Thermostat

BALANCE POINT TEMPERATURE-The “balance point” temperature is a setting which affects the operation of the heating mode. This is a field-selected input temperature (range 5 to 55_F) (-15 to 12_C) where the Thermidistat or dual fuel thermostat will monitor outdoor air temperature and decide whether to enable or disable the heat pump. If the outdoor temperature is above the “balance point”, the heat pump will energize first to try to satisfy the indoor temperature demand. If the heat pump does not make a sufficient improvement within a reasonable time period (i.e. 15 minutes), then the gas furnace will come on to satisfy the indoor temperature demand. If the outdoor temperature is below the “balance point”, the heat pump will not be allowed to operate (i.e. locked out), and the gas furnace will be used to satisfy the indoor temperature. There are three separate concepts which are related to selecting the final “balance point” temperature. Read each of the following carefully to determine the best “balance point” in a hybrid installation:

1.Capacity Balance Temperature: This is a point where the heat pump cannot provide sufficient capacity to keep up with the indoor temperature demand because of declining outdoor temperature. At or below this point, the furnace is needed to maintain proper indoor temperature.

2.Economic Balance Temperature: Above this point, the heat pump is the most cost efficient to operate, and below this point the furnace is the most cost efficient to operate. This can be somewhat complicated to determine and it involves knowing the cost of gas and electricity, as well as the efficiency of the furnace and heat pump. For the most economical operation, the heat pump should operate above this temperature (assuming it has sufficient capacity) and the furnace should operate below this temperature.

3.Comfort Balance Temperature: When the heat pump is operating below this point, the indoor supply air feels uncomfortable (i.e. too cool). This is purely subjective and will depend on the homeowner’s idea of comfort. Below this temperature the gas furnace should operate in order to satisfy the desire for indoor comfort.

Transformer Protection

The transformer is of the energy-limiting type. It is set to withstand a 30-sec. overload or shorted secondary condition. If an overload or short is present, correct overload condition and check for blown fuse on gas control board or Interface Fan Board. Replace fuse as required with correct size and rating.

PRE-START-UP

!WARNING

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury, death or property damage.

1.Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.

2.Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.

3.Do not remove compressor terminal cover until all electrical sources are disconnected and tagged.

4.Relieve and recover all refrigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals.

5.Never attempt to repair soldered connection while refrigerant system is under pressure.

6.Do not use torch to remove any component. System contains oil and refrigerant under pressure.

To remove a component, wear protective goggles and proceed as follows:

a.Shut off electrical power to unit and install lockout tag.

b.Relieve and reclaim all refrigerant from system using both high- and low-pressure ports.

c.Cut component connecting tubing with tubing cutter and remove component from unit.

d.Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.

Proceed as follows to inspect and prepare the unit for initial start-up:

1.Remove access panels (see Fig. 18).

2.Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit.

3.Make the following inspections:

a.Inspect for shipping and handling damages such as broken lines, loose parts, disconnected wires, etc.

b.Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak.

c.Leak test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, see the Check for Refrigerant Leaks section.

d.Inspect all field- and factory-wiring connections. Be sure that connections are completed and tight.

e.Ensure wires do not touch refrigerant tubing or sharp sheet metal edges.

f.Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb.

!WARNING

FIRE, EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death or property damage.

Do not purge gas supply into the combustion chamber. Do not use a match or other open flame to check for gas leaks. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.

48EZ -- A

13

Image 13
Contents Safety Considerations Table of ContentsIntroduction Receiving and InstallationCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Number Roof Curb DimensionsProvide Clearances Field Fabricate DuctworkRig and Place Unit InspectionInstall Gas Piping Install Flue HoodConnect Condensate Drain Rigging/Lifting of Unit See FigSediment Trap Fire or Explosion HazardConfiguring Units for Downflow Vertical Discharge Install Duct ConnectionsPhysical Data Unit 48EZ-A Maximum Gas Flow Capacity Physical Data Unit 48EZ-A Cont’dHeating Inputs Special Procedures for 208-V Operation Install Electrical ConnectionsHigh-Voltage Connections Unit Component Damage HazardPRE-START-UP Balance Point Setting-Thermidistat or Hybrid ThermostatControl Voltage Connections Transformer ProtectionSTART-UP Start-up Heating and Make Adjust- mentsCheck for Refrigerant Leaks Unit Sequence of OperationCheck Gas Input Adjust Gas InputUnit Damage Hazard Start-up Cooling and Make Adjust- ments Indoor Airflow and Airflow Adjustments Checking and Adjusting Refrigerant ChargeGas Heating Fan Speed Set-up Unit Operation HazardContinuous Fan Operation Two Cooling Fan Speeds Set-up Dehumidification feature usedColor Coding for Indoor Fan Motor Leads Unit Heating Rise Motor Dry Coil Air Delivery* Horizontal Unit 48EZ-A24-60Range Speed Color Dry Coil Air Delivery* Horizontal Discharge Unit 48EZ-A24-60 1354 1290 1226 1158 1102 1046 981 918 843 55oF Heating Rise Medium1 48EZ ---,NA48090 48EZ ---,NA48130 Unit Heating Rise Motor Wire Unit Standard CFM Scfm Size Horizontal and Downflow Filter Pressure Drop Table IN. W.CDownflow Cooling Standard CFM Scfm Economizer + Tons Cooling Standard CFM Scfm48EZ a 208/230-1-60 Ladder Wiring Diagram, Unit 48EZ-A 208/230-3-60 Connection Wiring Diagram, Unit 48EZ-A Cont. 208/230-3-60 Ladder Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Cleaning the Blower Motor and Wheel MaintenanceAir Filter Indoor Blower and MotorInduced Draft combustion air Blower Assembly Limit SwitchBurner Ignition Main BurnersOutdoor Fan Electrical Controls and WiringRefrigerant Circuit Loss of Charge Switch Pressure SwitchesGas Input Indoor AirflowCopeland Scroll Compressor Puron Refrigerant High-Pressure SwitchExplosion Hazard Refrigerant System Unit Operation and Safety HazardCompressor Oil START-UP Checklist TroubleshootingPuronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeTroubleshooting Guide-LED Error Codes Troubleshooting Guide-HeatingLED OFF Remove and Store in Job Files TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor Amps