Carrier 48EZ(N)-A Troubleshooting, START-UP Checklist, Puronr R-410A Quick Reference Guide

Page 38

48EZ -- A

Servicing Systems on Roofs and with Synthetic materials

POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.

Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve.

Synthetic Roof Precautionary Procedure

1.Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10x10 ft (3x3 m) area.

2.Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent run-offs, and protect drop cloth from tears caused by tools or components.

3.Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run-offs through the louvered openings in the unit base.

4.Perform required service.

5.Remove and dispose of any oil contaminated material per local codes.

Liquid Line Filter Drier

This filter drier is specifically designed to operate with Puron. Use only factory-authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system.

Puron (R-410A) Refrigerant Charging

Refer to unit information plate and charging chart. Some R-410A refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position. For cylinders equipped with a dip tube, charge Puron units with cylinder in upright position and a commercial metering device in manifold hose. Charge refrigerant into suction-line.

TROUBLESHOOTING

Use the Troubleshooting Guides (See Tables 12-14) if problems occur with these units.

START-UP CHECKLIST

Use Start-Up checklist to ensure proper start-up procedures are followed.

PURONR (R-410A) QUICK REFERENCE GUIDE

SPuron refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron

SPuron refrigerant cylinders are rose colored.

SRecovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

SPuron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating

SManifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low-side retard. S Use hoses with minimum 700 psig service pressure rating.

S Leak detectors should be designed to detect HFC refrigerant. S Puron, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil.

S Do not use liquid-line filter driers with rated working pressures less than 600 psig. S Do not leave Puron suction line filter driers in line longer than 72 hrs.

S Do not install a suction-line filter drier in liquid line.

S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing. S A factory approved liquid-line filter drier is required on every unit.

S Do NOT use an R-22 TXV.

S Never open system to atmosphere while it is under a vacuum.

S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers. Evacuate to 500 microns prior to recharging.

S Do not vent Puron into the atmosphere.

S Observe all warnings, cautions, and bold text.

S All indoor coils must be installed with a hard shutoff Puron TXV metering device.

38

Image 38
Contents Table of Contents Safety ConsiderationsCheck Equipment Receiving and InstallationIntroduction Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Roof Curb Dimensions NumberRig and Place Unit Field Fabricate DuctworkProvide Clearances InspectionConnect Condensate Drain Install Flue HoodInstall Gas Piping Rigging/Lifting of Unit See FigFire or Explosion Hazard Sediment TrapInstall Duct Connections Configuring Units for Downflow Vertical DischargePhysical Data Unit 48EZ-A Heating Inputs Physical Data Unit 48EZ-A Cont’dMaximum Gas Flow Capacity High-Voltage Connections Install Electrical ConnectionsSpecial Procedures for 208-V Operation Unit Component Damage HazardControl Voltage Connections Balance Point Setting-Thermidistat or Hybrid ThermostatPRE-START-UP Transformer ProtectionCheck for Refrigerant Leaks Start-up Heating and Make Adjust- mentsSTART-UP Unit Sequence of OperationUnit Damage Hazard Adjust Gas InputCheck Gas Input Start-up Cooling and Make Adjust- ments Gas Heating Fan Speed Set-up Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Unit Operation HazardColor Coding for Indoor Fan Motor Leads Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Range Speed Color Dry Coil Air Delivery* Horizontal Unit 48EZ-A24-60Unit Heating Rise Motor Dry Coil Air Delivery* Horizontal Discharge Unit 48EZ-A24-60 1354 1290 1226 1158 1102 1046 981 918 843 55oF Heating Rise Medium1 48EZ ---,NA48090 48EZ ---,NA48130 Unit Heating Rise Motor Wire Downflow Cooling Standard CFM Scfm Economizer + Tons Horizontal and Downflow Filter Pressure Drop Table IN. W.CUnit Standard CFM Scfm Size Cooling Standard CFM Scfm48EZ a 208/230-1-60 Ladder Wiring Diagram, Unit 48EZ-A 208/230-3-60 Connection Wiring Diagram, Unit 48EZ-A Cont. 208/230-3-60 Ladder Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Air Filter MaintenanceCleaning the Blower Motor and Wheel Indoor Blower and MotorBurner Ignition Limit SwitchInduced Draft combustion air Blower Assembly Main BurnersRefrigerant Circuit Electrical Controls and WiringOutdoor Fan Gas Input Pressure SwitchesLoss of Charge Switch Indoor AirflowExplosion Hazard High-Pressure SwitchCopeland Scroll Compressor Puron Refrigerant Compressor Oil Unit Operation and Safety HazardRefrigerant System Puronr R-410A Quick Reference Guide TroubleshootingSTART-UP Checklist Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyLED OFF Troubleshooting Guide-HeatingTroubleshooting Guide-LED Error Codes Preliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor Amps