Carrier 48EZ(N)-A Two Cooling Fan Speeds Set-up Dehumidification feature used

Page 18

48EZ -- A

2.Remove the current speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 13) and place vinyl cap over the connector on the wire.

3.Connect the desired speed tap wire to the “LOW” terminal on the interface fan board (IFB).

Two Cooling Fan Speeds Set-up (Dehumidification feature used)

IMPORTANT: Dehumidification control must open control circuit on humidity rise above set point.

Use of the dehumidification cooling fan speed requires use of either a 24 VAC dehumidistat or a thermostat which includes control of a 24 VAC dehumidistat connection. In either case, the dehumidification control must open the control circuit on humidity rise above the dehumidification set point.

1.Remove fan speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 13).

2.Determine correct normal cooling fan speed for unit and application. Add the wet coil pressure drop in Table 9 to the system static to determine the correct cooling airflow speed in Table 7 that will deliver the nominal cooling airflow as listed in Table 1 for each size.

3.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the normal cooling fan speed and place desired speed tap wire on “HIGH” on the interface board.

4.Refer to airflow tables (Table 7) to determine allowable speeds for the dehumidification cooling fan speed. In Table 7, speeds that are not allowed for dehumidification cooling are shaded.

5.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the dehumidification cooling fan speed and place desired speed tap wire on the “LOW” connection on the interface board (IFB). Verify that static pressure is in the acceptable range for the speed tap to be used for dehumidification cooling.

6.Use any spare vinyl plugs to cap any unused speed tap wires.

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB “LOW” speed when the DH control lead is not energized, or IFB “HIGH” speed when the DH lead is energized (see Fig. 13).

NOTE: For heat pump operation, the recommended airflow is 350 to 450 CFM for each 12,000 Btuh of rated cooling capacity.

Table 6 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med---High Speed

Red = Med Speed

Pink = Med---Low Speed

Blue = Low Speed

 

 

 

 

GAS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

HIGH

LOW

 

COM

 

 

 

 

 

 

QC6

 

 

QC7

 

QC4

 

QC3

 

 

 

 

 

 

 

K2

 

 

 

 

 

 

K1

DCR

QCR

CDM/C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RL3

C8

R1L

Q1

 

 

D2

C

 

 

 

 

 

 

 

 

 

 

24VAC/R

 

 

 

 

RI0

 

 

 

 

 

 

 

 

QC1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JM6

 

RI2

 

 

 

 

 

 

 

 

 

 

Q3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C9

 

C4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G1JM5

RI

DL

 

 

 

 

 

 

 

 

 

 

 

 

 

3 AMP

OILL C2

D6

D4

 

 

 

 

 

 

G2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A7

R9

 

AB

A15

 

 

 

 

 

F1

 

 

 

 

 

 

 

 

 

 

 

 

 

C0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C3

 

 

R4

RL4

D5

D3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW3

 

 

 

P3

 

 

R2

 

R3

 

R5

R6

 

 

 

 

 

 

 

 

 

JW7

QCB

 

 

P2

 

 

 

 

 

 

 

SDL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW2

 

 

 

 

 

 

Y

Y

R

U

C

24VAC

 

 

 

JW4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW1

 

P1

 

 

 

 

 

 

 

SSTZ-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W2

Y2/

G

Y1/

C

R

 

 

 

 

 

 

 

 

 

 

DH

Y

 

 

 

A09058

Fig. 13 - Interface Fan Board (IFB)

18

Image 18
Contents Table of Contents Safety ConsiderationsCheck Equipment Receiving and InstallationIntroduction Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Roof Curb Dimensions NumberRig and Place Unit Field Fabricate DuctworkProvide Clearances InspectionConnect Condensate Drain Install Flue HoodInstall Gas Piping Rigging/Lifting of Unit See FigFire or Explosion Hazard Sediment TrapInstall Duct Connections Configuring Units for Downflow Vertical DischargePhysical Data Unit 48EZ-A Physical Data Unit 48EZ-A Cont’d Maximum Gas Flow CapacityHeating Inputs High-Voltage Connections Install Electrical ConnectionsSpecial Procedures for 208-V Operation Unit Component Damage HazardControl Voltage Connections Balance Point Setting-Thermidistat or Hybrid ThermostatPRE-START-UP Transformer ProtectionCheck for Refrigerant Leaks Start-up Heating and Make Adjust- mentsSTART-UP Unit Sequence of OperationAdjust Gas Input Check Gas InputUnit Damage Hazard Start-up Cooling and Make Adjust- ments Gas Heating Fan Speed Set-up Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Unit Operation HazardTwo Cooling Fan Speeds Set-up Dehumidification feature used Continuous Fan OperationColor Coding for Indoor Fan Motor Leads Dry Coil Air Delivery* Horizontal Unit 48EZ-A24-60 Unit Heating Rise MotorRange Speed Color Dry Coil Air Delivery* Horizontal Discharge Unit 48EZ-A24-60 1354 1290 1226 1158 1102 1046 981 918 843 55oF Heating Rise Medium1 48EZ ---,NA48090 48EZ ---,NA48130 Unit Heating Rise Motor Wire Downflow Cooling Standard CFM Scfm Economizer + Tons Horizontal and Downflow Filter Pressure Drop Table IN. W.CUnit Standard CFM Scfm Size Cooling Standard CFM Scfm48EZ a 208/230-1-60 Ladder Wiring Diagram, Unit 48EZ-A 208/230-3-60 Connection Wiring Diagram, Unit 48EZ-A Cont. 208/230-3-60 Ladder Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Air Filter MaintenanceCleaning the Blower Motor and Wheel Indoor Blower and MotorBurner Ignition Limit SwitchInduced Draft combustion air Blower Assembly Main BurnersElectrical Controls and Wiring Outdoor FanRefrigerant Circuit Gas Input Pressure SwitchesLoss of Charge Switch Indoor AirflowHigh-Pressure Switch Copeland Scroll Compressor Puron RefrigerantExplosion Hazard Unit Operation and Safety Hazard Refrigerant SystemCompressor Oil Troubleshooting START-UP ChecklistPuronr R-410A Quick Reference Guide Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyTroubleshooting Guide-Heating Troubleshooting Guide-LED Error CodesLED OFF Preliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor Amps