Carrier 48EZ(N)-A installation instructions 48EZ ---,NA48130

Page 24

24

 

 

 

 

 

 

 

 

 

 

 

 

 

48EZ-- A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 7 (cont) - Dry Coil Air Delivery* - Horizontal Discharge - Unit 48EZ-A24-60

 

 

 

 

 

 

 

 

UNIT

 

HEATING RISE

 

MOTOR

 

WIRE

 

 

 

 

EXTERNAL STATIC PRESSURE (in. W.C.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE

 

SPEED

 

COLOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

 

0.4

0.5

0.6

 

0.7

0.8

0.9

 

 

 

 

 

 

 

 

CFM

1402

1351

1311

 

1263

1224

1172

 

1136

1080

1041

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

NA

 

NA

NA

NA

 

 

 

 

 

Low

 

Blue

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

NA

 

NA

NA

NA

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1457

1404

1367

 

1318

1284

1233

 

1197

1144

1104

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

NA

 

NA

NA

NA

 

 

 

 

 

Med---Low

 

Pink

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

NA

 

NA

NA

NA

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1736

1695

1642

 

1601

1553

1512

 

1465

1427

1381

 

 

 

35 --- 65oF

 

 

 

 

Heating Rise

55

57

59

 

60

62

64

 

NA

NA

NA

 

48EZ( ---,N)A48130

 

 

Medium2

 

Red

(oF)

 

 

 

 

(19 --- 36oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

31

32

33

 

33

34

35

 

NA

NA

NA

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

2149

2111

2062

 

2026

1980

1945

 

1905

1864

1793

 

 

 

 

 

 

 

 

Heating Rise

45

46

47

 

48

49

50

 

51

52

54

 

 

 

 

 

Med---High1

 

Orange

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

25

25

26

 

26

27

28

 

28

29

30

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

2344

2306

2259

 

2203

2141

2070

 

1991

1902

1803

 

 

 

 

 

 

 

 

Heating Rise

41

42

43

 

44

45

47

 

48

51

53

 

 

 

 

 

High

 

Black

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

23

23

24

 

24

25

26

 

27

28

30

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1445

1389

1341

 

1281

1236

1189

 

1139

1072

1027

 

 

 

 

 

 

 

 

Heating Rise

47

49

51

 

53

55

57

 

60

63

NA

 

 

 

 

 

Low1

 

Blue

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

26

27

28

 

29

31

32

 

33

35

NA

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1678

1635

1602

 

1558

1513

1474

 

1438

1404

1349

 

 

 

 

 

 

 

 

Heating Rise

41

42

42

 

44

45

46

 

47

48

50

 

 

 

 

 

Med---Low

 

Pink

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

23

23

24

 

24

25

26

 

26

27

28

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1927

1893

1858

 

1824

1791

1759

 

1720

1689

1640

 

 

 

35 --- 65oF

 

 

 

 

Heating Rise

35

36

37

 

37

38

39

 

40

40

41

 

48EZ( ---,N)A60090

 

 

Medium2

 

Red

(oF)

 

 

 

 

(19 --- 36oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

20

20

20

 

21

21

21

 

22

22

23

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

2131

2088

2065

 

2013

1982

1941

 

1888

1860

1785

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

35

 

36

37

38

 

 

 

 

 

Med---High

 

Orange

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

19

 

20

20

21

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

2461

2409

2339

 

2286

2192

2140

 

2062

1968

1874

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

NA

 

NA

35

36

 

 

 

 

 

High

 

Black

(oF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Rise

NA

NA

NA

 

NA

NA

NA

 

NA

19

20

 

 

 

 

 

 

 

 

(oC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 24
Contents Table of Contents Safety ConsiderationsReceiving and Installation IntroductionCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Roof Curb Dimensions NumberField Fabricate Ductwork Provide ClearancesRig and Place Unit InspectionInstall Flue Hood Install Gas PipingConnect Condensate Drain Rigging/Lifting of Unit See FigFire or Explosion Hazard Sediment TrapInstall Duct Connections Configuring Units for Downflow Vertical DischargePhysical Data Unit 48EZ-A Physical Data Unit 48EZ-A Cont’d Maximum Gas Flow CapacityHeating Inputs Install Electrical Connections Special Procedures for 208-V OperationHigh-Voltage Connections Unit Component Damage HazardBalance Point Setting-Thermidistat or Hybrid Thermostat PRE-START-UPControl Voltage Connections Transformer ProtectionStart-up Heating and Make Adjust- ments START-UPCheck for Refrigerant Leaks Unit Sequence of OperationAdjust Gas Input Check Gas InputUnit Damage Hazard Start-up Cooling and Make Adjust- ments Checking and Adjusting Refrigerant Charge Indoor Airflow and Airflow AdjustmentsGas Heating Fan Speed Set-up Unit Operation HazardTwo Cooling Fan Speeds Set-up Dehumidification feature used Continuous Fan OperationColor Coding for Indoor Fan Motor Leads Dry Coil Air Delivery* Horizontal Unit 48EZ-A24-60 Unit Heating Rise MotorRange Speed Color Dry Coil Air Delivery* Horizontal Discharge Unit 48EZ-A24-60 1354 1290 1226 1158 1102 1046 981 918 843 55oF Heating Rise Medium1 48EZ ---,NA48090 48EZ ---,NA48130 Unit Heating Rise Motor Wire Horizontal and Downflow Filter Pressure Drop Table IN. W.C Unit Standard CFM Scfm SizeDownflow Cooling Standard CFM Scfm Economizer + Tons Cooling Standard CFM Scfm48EZ a 208/230-1-60 Ladder Wiring Diagram, Unit 48EZ-A 208/230-3-60 Connection Wiring Diagram, Unit 48EZ-A Cont. 208/230-3-60 Ladder Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Maintenance Cleaning the Blower Motor and WheelAir Filter Indoor Blower and MotorLimit Switch Induced Draft combustion air Blower AssemblyBurner Ignition Main BurnersElectrical Controls and Wiring Outdoor FanRefrigerant Circuit Pressure Switches Loss of Charge SwitchGas Input Indoor AirflowHigh-Pressure Switch Copeland Scroll Compressor Puron RefrigerantExplosion Hazard Unit Operation and Safety Hazard Refrigerant SystemCompressor Oil Troubleshooting START-UP ChecklistPuronr R-410A Quick Reference Guide Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyTroubleshooting Guide-Heating Troubleshooting Guide-LED Error CodesLED OFF Temperatures Remove and Store in Job FilesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor Amps