Carrier 48EZ(N)-A Gas Input, Indoor Airflow, Check Defrost Thermostat, Puron Items

Page 35

O

T2 C C O

DFT

 

 

 

 

 

OF2

OF1

R

T1

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

C

Y

 

 

 

 

 

 

 

 

SPEEDUP

P1

 

 

 

 

 

 

 

 

J1

P3

INTERVALTIMER

90

60 30

30 60

120

 

 

 

DFT

 

OFF

 

QUIET SHIFT

ON

 

 

 

Speedup

 

 

 

 

Quiet

Defrost interval

 

 

Pins

 

 

 

 

Shift

DIP switches

 

 

 

 

 

 

 

 

 

 

A08020

Fig. 23 - Defrost Control

48EZ -- A

!WARNING

EXPLOSION, PERSONAL INJURY AND ENVIRONMENTAL HAZARD

Failure to follow this warning could result in personal injury, death or property damage.

System under pressure. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves.

If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing using an electronic leak-detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, refer to the Check for Refrigerant Leaks section.

If no refrigerant leaks are found and low cooling performance is suspected, refer to the Checking and Adjusting Refrigerant Charge section.

Gas Input

The gas input does not require checking unless improper heating performance is suspected. If a problem exists, refer to the Start-Up section.

Indoor Airflow

The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to

the Indoor Airflow and Airflow Adjustments section to check the system airflow.

Check Defrost Thermostat

The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil (see Fig. 21). The thermostat closes at 32_F (0_C) and opens at 65_F (18_C).

Puron Items

Metering Device (Thermostatic Expansion Valve & Piston)

This unit uses both a hard shutoff, balance port TXV in the indoor coil and a piston in each side of the outdoor coil. The TXV maintains a constant superheat at the evaporator coil exit (cooling mode) resulting in higher overall system efficiency.

Pressure Switches

Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron (R-410A) systems. R-22 pressure switches must not be used as replacements for the Puron (R-410A) system.

Loss of Charge Switch

This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 20 psig. If system pressure is above this, switch should be closed. To check switch:

1. Turn off all power to unit.

35

Image 35
Contents Safety Considerations Table of ContentsProvide Unit Support Receiving and InstallationIntroduction Check Equipment48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Number Roof Curb DimensionsInspection Field Fabricate DuctworkProvide Clearances Rig and Place UnitRigging/Lifting of Unit See Fig Install Flue HoodInstall Gas Piping Connect Condensate DrainSediment Trap Fire or Explosion HazardConfiguring Units for Downflow Vertical Discharge Install Duct ConnectionsPhysical Data Unit 48EZ-A Heating Inputs Physical Data Unit 48EZ-A Cont’dMaximum Gas Flow Capacity Unit Component Damage Hazard Install Electrical ConnectionsSpecial Procedures for 208-V Operation High-Voltage ConnectionsTransformer Protection Balance Point Setting-Thermidistat or Hybrid ThermostatPRE-START-UP Control Voltage ConnectionsUnit Sequence of Operation Start-up Heating and Make Adjust- mentsSTART-UP Check for Refrigerant LeaksUnit Damage Hazard Adjust Gas InputCheck Gas Input Start-up Cooling and Make Adjust- ments Unit Operation Hazard Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Gas Heating Fan Speed Set-upColor Coding for Indoor Fan Motor Leads Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Range Speed Color Dry Coil Air Delivery* Horizontal Unit 48EZ-A24-60Unit Heating Rise Motor Dry Coil Air Delivery* Horizontal Discharge Unit 48EZ-A24-60 1354 1290 1226 1158 1102 1046 981 918 843 55oF Heating Rise Medium1 48EZ ---,NA48090 48EZ ---,NA48130 Unit Heating Rise Motor Wire Cooling Standard CFM Scfm Horizontal and Downflow Filter Pressure Drop Table IN. W.CUnit Standard CFM Scfm Size Downflow Cooling Standard CFM Scfm Economizer + Tons48EZ a 208/230-1-60 Ladder Wiring Diagram, Unit 48EZ-A 208/230-3-60 Connection Wiring Diagram, Unit 48EZ-A Cont. 208/230-3-60 Ladder Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Indoor Blower and Motor MaintenanceCleaning the Blower Motor and Wheel Air FilterMain Burners Limit SwitchInduced Draft combustion air Blower Assembly Burner IgnitionRefrigerant Circuit Electrical Controls and WiringOutdoor Fan Indoor Airflow Pressure SwitchesLoss of Charge Switch Gas InputExplosion Hazard High-Pressure SwitchCopeland Scroll Compressor Puron Refrigerant Compressor Oil Unit Operation and Safety HazardRefrigerant System Puronr R-410A Quick Reference Guide TroubleshootingSTART-UP Checklist Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeLED OFF Troubleshooting Guide-HeatingTroubleshooting Guide-LED Error Codes III. START-UP Electrical Supply Voltage Compressor Amps TemperaturesRemove and Store in Job Files Preliminary Information Model no