Carrier 48EZ(N)-A installation instructions Maintenance, Air Filter, Indoor Blower and Motor

Page 32

48EZ -- A

MAINTENANCE

To ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This combination heating/cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot cooling or heating of units, refer to Tables 12, 13 and 14.

NOTE: Consult your local dealer about the availability of a maintenance contract.

!WARNING

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal injury or death and unit component damage.

The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the Owner’s Manual.

!WARNING

ELECTRICAL SHOCK AND EXPLOSION HAZARD

Failure to follow these warnings could result in personal injury or death:

1.Turn off electrical power to the unit and install a lockout tag before performing any maintenance or service on this unit.

2.Use extreme caution when removing panels and parts.

3.Never place anything combustible either on or in contact with the unit.

4.Should overheating occur or the gas supply fail to shut off, turn off external main manual gas valve to the unit. Then shut off electrical supply.

!CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

When removing access panels (see Fig. 18) or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit.

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in improper operation.

Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing.

The minimum maintenance requirements for this equipment are as follows:

1.Inspect air filter(s) each month. Clean or replace when necessary. Certain geographical locations may require more frequent inspections.

2.Inspect indoor coil, outdoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.

3.Inspect blower motor and wheel for cleanliness at the beginning of each heating and cooling season. Clean when necessary. For first heating and cooling season, inspect blower wheel bi-monthly to determine proper cleaning frequency.

4.Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary. Ensure electrical wiring is not in contact with refrigerant tubing or sharp metal edges.

5.Check and inspect heating section before each heating season. Clean and adjust when necessary.

6.Check flue hood and remove any obstructions, if necessary.

Air Filter

IMPORTANT: Never operate the unit without a suitable air filter in the return-air duct system. Always replace the filter with the same dimensional size and type as originally installed. (See Table 1 for recommended filter sizes.)

Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice during each heating and cooling season or whenever the filter(s) becomes clogged with dust and/or lint.

Indoor Blower and Motor

NOTE: All motors are prelubricated. Do not attempt to lubricate these motors.

For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel.

Cleaning the Blower Motor and Wheel

1.Remove and disassemble blower assembly as follows:

a.Remove blower access panel (see Fig. 18).

b.Disconnect 5 pin plug and 4 pin plug from indoor blower motor. Remove capacitor if required.

c.On all units, remove blower assembly from unit. Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment.

d.Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly.

e.Loosen setscrew(s) that secures wheel to motor shaft. Remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.

2.Remove and clean blower wheel as follows:

a.Ensure proper reassembly by marking wheel orientation.

b.Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.

c.Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.

d.Reassemble wheel into housing.

e.Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of shaft. Reinstall blower into unit. Reinstall capacitor.

32

Image 32
Contents Table of Contents Safety ConsiderationsReceiving and Installation IntroductionCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Roof Curb Dimensions NumberField Fabricate Ductwork Provide ClearancesRig and Place Unit InspectionInstall Flue Hood Install Gas PipingConnect Condensate Drain Rigging/Lifting of Unit See FigFire or Explosion Hazard Sediment TrapInstall Duct Connections Configuring Units for Downflow Vertical DischargePhysical Data Unit 48EZ-A Heating Inputs Physical Data Unit 48EZ-A Cont’dMaximum Gas Flow Capacity Install Electrical Connections Special Procedures for 208-V OperationHigh-Voltage Connections Unit Component Damage HazardBalance Point Setting-Thermidistat or Hybrid Thermostat PRE-START-UPControl Voltage Connections Transformer ProtectionStart-up Heating and Make Adjust- ments START-UPCheck for Refrigerant Leaks Unit Sequence of OperationUnit Damage Hazard Adjust Gas InputCheck Gas Input Start-up Cooling and Make Adjust- ments Checking and Adjusting Refrigerant Charge Indoor Airflow and Airflow AdjustmentsGas Heating Fan Speed Set-up Unit Operation HazardColor Coding for Indoor Fan Motor Leads Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Range Speed Color Dry Coil Air Delivery* Horizontal Unit 48EZ-A24-60Unit Heating Rise Motor Dry Coil Air Delivery* Horizontal Discharge Unit 48EZ-A24-60 1354 1290 1226 1158 1102 1046 981 918 843 55oF Heating Rise Medium1 48EZ ---,NA48090 48EZ ---,NA48130 Unit Heating Rise Motor Wire Horizontal and Downflow Filter Pressure Drop Table IN. W.C Unit Standard CFM Scfm SizeDownflow Cooling Standard CFM Scfm Economizer + Tons Cooling Standard CFM Scfm48EZ a 208/230-1-60 Ladder Wiring Diagram, Unit 48EZ-A 208/230-3-60 Connection Wiring Diagram, Unit 48EZ-A Cont. 208/230-3-60 Ladder Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Maintenance Cleaning the Blower Motor and WheelAir Filter Indoor Blower and MotorLimit Switch Induced Draft combustion air Blower AssemblyBurner Ignition Main BurnersRefrigerant Circuit Electrical Controls and WiringOutdoor Fan Pressure Switches Loss of Charge SwitchGas Input Indoor AirflowExplosion Hazard High-Pressure SwitchCopeland Scroll Compressor Puron Refrigerant Compressor Oil Unit Operation and Safety HazardRefrigerant System Puronr R-410A Quick Reference Guide TroubleshootingSTART-UP Checklist Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyLED OFF Troubleshooting Guide-HeatingTroubleshooting Guide-LED Error Codes Temperatures Remove and Store in Job FilesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor Amps