Desa CCL3930PTA Determining FRESH-AIR Flow for Heater Location, Confined and Unconfined Space

Page 5

AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation (Cont.) Determining Fresh-Air Flow for Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow for Heater Loca- tion, below.

Confined and Unconfined Space

National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Uncon- fined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

39,000

Btu/Hr

Total

=

79,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For morevisit www..com

107124-01E

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSafety Information Table of ContentsProduct Identification Unpacking Product Features AIR for Combustion and VentilationLocal Codes Determining if You Have a Confined or Uncon- fined Space Determining FRESH-AIR Flow for Heater LocationConfined and Unconfined Space Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Check GAS Type InstallationMinimum Noncombustible Material Clearances If Using MantelMantel Clearances Determining Minimum Mantel Clearance When Using a HoodFloor Clearances Determining Minimum Mantel ClearanceInstallation Items Needed Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Attaching Flexible Gas Hose to Heater Gas Regulator Connecting to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping systemDual Burner Smoky Mountain Oak Models Installing LogsPressure Testing Heater Gas Connections Dual Burner Premium Aged Split Oak Models Installing Middle Log #2Installing Front Log #4 Dual Burner Biltmore Split Oak Models Installing Middle Log #2 CCL3930PTA ShownInstalling Crossover Log #5 CCL3930PTA Shown Single Burner Seasonal Oak Models Installing Front LogLighting Instructions For Your Safety Read Before LightingOperating Heater Variable Control Operation Manual Lighting ProcedureTo Turn OFF GAS to Appliance Shutting Off HeaterElectrode Thermocouple Thermostat Control Operation Inspecting BurnersPilot Flame Pattern Burner Primary AIR HolesLogs Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Observed Problem Possible Cause Remedy TroubleshootingFor more Visit www Com Gas leak. See Warning statement For Masonry and Factory-built Metal Fireplace Optional Positioning of Thermostat Sensing BulbAccessories Replacement PartsService Hints Technical ServiceSingle Burner Seasonal OAK Models SpecificationsDual Burner Biltmore Split OAK Models Variable Manually-Controlled Illustrated Parts BreakdownCGD3930P, CCL3018P CCL3924P Parts ListThermostatically-Controlled Smoky Mountain Oak Models CGD3018PT CGD3924PT CGD3930PTCGD3924PT and CGD3930PT Thermostatically-Controlled Biltmore Split Oak Model CCL3018PTKEY Part Number CCL3018PT Description QTY CCL3924PT CCL3930PTA Biltmore Split Oak Model Thermostatically-ControlledVariable Manually-Controlled Seasonal Oak Models Description QTY Seasonal Oak ModelsParts Central Owners Registration Form Postage Required 107124-01E Keep this Warranty Warranty Information