Quadra-Fire CASTILE-CCR, CASTILE-MBK, CASTILE-CLG Vent Information, Chimney and Exhaust Connection

Page 10

 

R

Castile Pellet Stove

 

 

 

 

 

 

 

 

4

Vent Information

 

 

 

 

 

A. Chimney and Exhaust Connection

1. Chimney & Connector: Use 3 or 4 inch (76-102mm) diameter type "L" or "PL" venting system. It can be vented vertically or horizontally.

2.Mobile Home: Approved for all listed pellet vent. If using the 3 inch (76mm) vertical Top Vent Adapter Kit or the 3 to 6 inch (76-152mm) Top Vent Offset Adapter, use listed double wall flue connector. A Quadra-Fire Outside Air Kit must be used with manufactured home installations.

3.Residential: The 3 inch (76mm) vertical Top Vent Adapter Kit and the 3 to 6 inch (76-152mm) Top Vent Offset Adapter are tested to use 24 gauge single wall flue connector or listed double wall flue connector to Class A listed metal chimneys, or masonry chimneys meeting ICBO standards for solid fuel appliances.

4. INSTALL VENT AT CLEARANCES SPECIFIED BY THE

VENT MANUFACTURER.

5. Secure exhaust venting system to the appliance with at least 3 screws. Also secure all connector pipe joints with at least 3 screws through each joint.

NOTE: All pipe must be welded seam pipe whenever pos- sible. Seal pipe joints with high temperature silicone (500°F [260°C] minimum rated only).

NOTE: If burning shelled field corn, you must use approved venting specifically designed for corn. Follow the instruc- tions from the venting manufacturer.

WARNING

Fire Hazard.

Only LISTED venting components may be used.

NO OTHER vent components may be used. Substitute or damaged vent components may impair safe operation.

WARNING

Vent surfaces get HOT, can cause burns if touched. Noncombustible shielding or guards may be required

B. Venting Termination Requirements

CAUTION

Do not terminate vent in any enclosed or semi-enclosed area such as a carport, garage, attic, crawl space, under a sun deck or porch, narrow walkway or closely fenced area, or any location that can build up a concentration of fumes such as a stairwell, covered breezeway, etc.

1. Termination must exhaust above air inlet elevation. It is recommended that at least 60 inches (1524mm) of verti- cal pipe be installed when appliance is vented directly through a wall. This will create a natural draft, which will help prevent the possibility of smoke or odor venting into the home during a power outage. It will also keep exhaust from causing a nuisance or hazard by exposing people or shrubs to high temperatures. The safest and preferred venting method is to extend the vent vertically through the roof.

2. Distance from doors and opening windows, or gravity or ventilation air inlets into building:

a.Not less than 48 inches (1219mm) below;

b.Not less than 48 inches (1219mm) horizontally from;

c.Not less than 12 inches (305mm) above.

3. Distance between bottom of termination and grade should be 24 inches (610mm) minimum. This is con- ditional upon plants in the area, and nature of grade surface. The grade surface must be a noncombustible material (i.e., rock, dirt). The grade surface must not be lawn. Distance between bottom of termination and public walkway should be 84 inches (2134mm) minimum.

4. Distance to combustible materials must be 24 inches (610mm) minimum. This includes adjacent buildings, fences, protruding parts of the structure, roof overhang, plants and shrubs, etc.

5.Termination Cap Location (Home Electrical Service)

Side-to-side clearance is to be the same as minimum clearance to vinyl inside corners.

Clearance of a termination cap below electrical service shall be the same as minimum clearance to vinyl sof- fits.

Clearance of a termination cap above electrical service will be 12 inches minimum.

Location of the vent termination must not obstruct or interfere with access to the electrical service.

Page 10

250-6422D

October 11, 2005

Image 10
Contents Castile Pellet Stove Castile Pellet Stove Location Back side of left side panelTable of Contents Listing and Code Approvals Appliance Location Design, Installation & Location Fire Safety ConsiderationsGetting Started Thermostat LocationInspect Appliance & Components and Pre-Use Check List Castile Pellet Stove Tools And Supplies NeededMeasuring Standards Fire Risk3Dimensions and Clearances Appliance DimensionsCastile Pellet Stove Clearances to Combustibles UL and ULC Castile Pellet Stove Hearth Pad Requirements UL and ULC Exception for Horizontal InstallationsHearth Pad Requirements Chimney and Exhaust Connection Vent InformationVenting Termination Requirements Example of 3 Elbow-Rear Vent Termination Calculaton Pipe Selection ChartCastile Pellet Stove Equivalent Feet of Pipe See FigureVenting Systems AlcoveDegree Straight OutCastile Pellet Stove Through The Wall Castile Pellet Stove Vertical Through The Wall & VerticalCastile Pellet Stove Masonry Alternate MasonryMobile Home 7Appliance Set-Up Outside Air Kit InstructionsInstalling the Top Vent Adapter Top Vent Adapter InstallationRear Vent and Rear Vent to Top Vent Adapter Installation Castile Pellet Stove Leg Leveling SystemOptional TOP LOG Castile Pellet Stove Thermostat Installation Operating Instructions Fuel Size And Material General Operating InformationCastile Pellet Stove Before Your First Fire Fire CharacteristicsFeed Rate Adjustment Instructions Starting Your First FireFrequently Asked Questions Castile Pellet Stove Iginition CyclesSymption TroubleshootingPossible Cause Corrective Action Page Page Types of Fuel Cleaning Ash Pan Frequency As needed10Maintaining & Servicing Your Appliance TaskCleaning Rods Heat Exchanger TubesCleaning Convection Blower Requires No Lubrication Cleaning the Exhaust Path Frequency As neededCleaning the Hopper Cleaning Exhaust Blower Requires No LubricationCastile Pellet Stove High Ash Fuel Content Maintenance SectionConvection Blower Replacement Exhaust Blower ReplacementIgniter Replacement Thumb ScrewGlass Replacement Reference Materials Component FunctionSnap Disc #1 Convection Blower 125F Vacuum SwitchWiring Harness See .1 below Snap Disc #2 Thermostat Override 175tFCastile Pellet Stove Component Locations Castile Pellet Stove Exploded Views Description Part NumberBeg. Manufacture Date September Part DescriptionCastile Pellet Stove Service Parts and Accessories Service PartsAccessories AppliancesService and Maintenance LOG Date of Service Performed By Description of ServiceCastile Pellet Stove Service and Maintenance LOG Cont’d Lifetime Warranty Castile Pellet Stove Warranty PolicyContact Information Telephone