Quadra-Fire 21M-ACC Chimney Requirements, Venting Components Chimney Systems, Chimney Connector

Page 14

2100 Millennium Wood Stove (ACC)

R

 

Chimney Requirements

 

Venting Components

B. Chimney Systems

A.5

 

Chimney Connector:

Prefabricated Metal Chimney

 

It is also known as flue pipe or stove pipe. The chimney connector joins the stove to the chimney. It must be a 6 inch (152mm) minimum diameter 24 gauge mild steel black or 26 gauge blued steel, or an approved air-insulated double wall venting pipe.

Thimble:

A manufactured or site-constructed device installed in combustible walls through which the chimney connector passes to the chimney. It is intended to keep the walls from igniting. Site constructed thimbles must meet NFPA 211 Standards. Prefabricated must be suitable for use with selected chimney and meet UL103 Type HT Standards. Follow instructions provided by the manufacturer for manufactured thimbles for masonry chimney and prefabricated chimneys.

Chimney:

The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements specified in Section 5B.

Listed Termination Cap

Roof Brace (if required)

Storm Collar

Flashing

Trim Collar on

Listed Chimney

Inside Wall

Insulated " T "

 

Chimney

Wall Support

Connector

 

 

Thimble

Floor

 

Protector

 

Must be minimum 6 inch (152mm) diameter (ID) high temperature chimney listed to UL 103 HT (2100oF) or ULC S629M.

Must use components required by the manufacturer for installation.

Must maintain clearances required by the manufacturer for installation.

Refer to manufacturers instructions for installation.

NOTE: In Canada when using a factory-built chimney it must be safety listed, Type UL103 HT (2100oF) CLASS “A” or conforming to CAN/ULC-S629M, STANDARD FOR 650oC

FACTORY-BUILT CHIMNEYS.

Listed Termination Cap

Storm Collar

Flashing

Listed Chimney

Ceiling Support

Chimney

Connector

Floor

Protector

Figure 14.1 Prefabricated Exterior Chimney

Figure 14.2 - Prefabricated Interior Chimney

Page 14

7039-131H

May 5, 2011

Image 14
Contents Hot glass will cause burns 7039-131H May 5Mfg. Date 7039-131H May 5 Millennium Wood Stove ACCSerial No Model Name Test Lab & Report No Table of Contents Listing and Code Approvals Appliance Certification BTU & Efficiency SpecificationsGlass Specifications Mobile Home ApprovedFire Safety Getting StartedAppliance needs to draft properly for safety Millennium Wood Stove ACC Negative PressureTools And Supplies Needed Millennium Wood Stove ACC Flue Draft ConsiderationsVenting Systems Inspect Appliance & Components Pre-Burn Check ListMillennium Wood Stove ACC Typical Stove Systems Masonry ChimneyDimensions and Clearances Appliance DimensionsBackwall / Sidewall Corner Installation See Figure InstallationRHearth Protection Requirements USA required Canada recommendedFloor Installation Alternative In some instances you Millennium Wood Stove ACC Outside Air Kit InstallationItems Needed for Installation not supplied Blower Optional 13-15/16 in mmVenting Components Chimney Systems Chimney ConnectorChimney Requirements ThimbleInstructions ComponentsAir Clearances Solid Pack Chimney with Metal Supports as a ThimbleSolid Pack Chimney with Metal Supports as a Thimble Cont’d Installing Chimney ComponentsSingle wall connector or stove pipe Chimney Height / Rise and RunPitched Roof Millennium Wood Stove ACC Chimney Termination RequirementsRule Flat RoofMobile Home Installation Door Handle Assembly Adjusting The Blower Speed Control Appliance Set-UpBurning Process Operating InstructionsOver-Firing Your Appliance Wood Selection & Storage Cont’d Wood Selection & StorageAutomatic Combustion Control ACC Air ControlsBurn Rates and Operating Efficiency Millennium Wood Stove ACC Building a Fire Incorrect Positions Opacity Smoke Initial cold start-up and all Burn SettingsMillennium Wood Stove ACC Blower Operating Instructions Snap Disc LocationAppliance Millennium Wood Stove ACC Frequently Asked QuestionsOdor from appliance Quick Reference Maintenance Guide Maintaining & Servicing Your ApplianceGlass Cleaning Frequency As desired Millennium Wood Stove ACC General MaintenanceCreosote Chimney Cleaning Disposal of AshesGlass Replacement When cleaning glassMillennium Wood Stove ACC Firebrick Replacement To your authorized dealerCorrect Blanket & Baffle Position on BaffleReplacing Tube Channel Assembly Millennium Wood Stove ACC Tube Channel Assembly ReplacementRemoving Tube Channel Assembly Troubleshooting Start Fire Problems Possible Cause Solution21M-ACC Millennium Wood Stove21M-ACC Stocked 21M-ACC Millennium Wood Stove ACC Service And Maintenance Log Date of Service Performed By Description of ServiceMillennium Wood Stove ACC Service And Maintenance Log Cont’d Millennium Wood Stove ACC Homeowner’s Notes Millennium Wood Stove ACC Homeowner’s Notes Millennium Wood Stove ACC Warranty Policy Millennium Wood Stove ACC Contact Information