Quadra-Fire 21M-ACC owner manual Mobile Home Installation

Page 18

2100 Millennium Wood Stove (ACC)

 

R

 

 

 

 

Mobile Home Installation

 

 

 

must use a Quadra-Fire Outside Air Kit Part

 

 

You6

 

 

 

OAK-ACC and (depending on floor installation, Part

 

Spark Arestor Cap

SRV7033-041) for installation in a mobile home.

 

 

 

1.

An outside air inlet must be provided for combustion See

 

 

 

page 12 for installation information.

Storm Collar

 

2.

Appliance must be secured to the mobile home structure

 

Roof Flashing

 

by bolting the pedestal through hearth pad and into

 

 

 

 

 

floor.

 

 

 

3.

Appliance must be grounded with #8 solid copper

 

 

 

grounding wire or equivalent and terminated at each end

Joist Shield/Firestop

 

 

with N.E.C. approved grounding device.

Double wall

 

 

 

 

4.

Appliance must be installed with an approved UL103 HT

 

connector pipe

 

ventilated chimney connector, UL103 HT chimney, and

 

 

 

terminal cap with spark arrestor. Never use a single wall

 

 

 

connector (stove pipe) in a mobile home installation. Use

 

 

 

only double-wall connector pipe, Dura-Vent DVL, Selkirk

 

 

 

metalbestos DS or Security DL double-wall connector or

 

 

 

any listed double-wall connector pipe.

 

 

5.

In Canada, this appliance must be connected to a 6 inch

 

Outside Air

 

(152mm) factory-built chimney conforming to CAN/ULC-

 

 

629M, STANDARD FOR FACTORY BUILT CHIMNEYS.

 

Rear Vent

 

 

 

6.

Follow the chimney and chimney connector manufacturer’s

Floor Protector

 

 

instructions when installing the flue system for use in a

 

 

mobile home.

 

 

7.

Maintain clearance to combustibles.

 

 

8.

Floor protection requirements must be followed

Outside Air Floor Vent

 

 

precisely.

 

9.

Use silicone to create an effective vapor barrier at the

Figure 18.1

 

 

location where the chimney or other component penetrates

 

 

to the exterior of the structure.

 

 

NOTE: Offsets from the vertical, not exceeding 45°, are

CAUTION

 

allowed per Section 905(a) of the Uniform Mechanical Code

THE STRUCTURAL INTEGRITY OF THE MOBILE HOME

(UMC). Offsets greater than 45° are considered horizontal

FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-

and are also allowed, providing the horizontal run does not

TAINED

exceed 75% of the vertical height of the vent. Construction,

Do NOT cut through:

clearance and termination must be in compliance with the

• Floor joist, wall, studs or ceiling trusses.

UMC Table 9C. This installation must also comply with NFPA

• Any supporting material that would affect the structural

211.

integrity.

NOTE: Top sections of chimney must be removable to allow

 

 

 

 

maximum clearance of 13.5 feet (411cm) from ground level

 

 

for transportation purposes.

 

 

 

 

10.

Burn wood only. Other types of fuels may generate

WARNING

 

poisonous gases (e.g., carbon monoxide).

Asphyxiation Risk.

11.

If unit burns poorly while an exhaust blower is on in

NEVER INSTALL IN A SLEEPING ROOM.

 

home, (i.e., range hood), increase combustion air.

 

Consumes oxygen in the room.

 

 

12.Installation shall be in accordance with the Manufacturers Home & Safety Standard (HUD) CFR 3280, Part 24.

Page 18

7039-131H

May 5, 2011

Image 18
Contents Hot glass will cause burns 7039-131H May 5Millennium Wood Stove ACC Serial No Model Name Test Lab & Report NoMfg. Date 7039-131H May 5 Table of Contents Listing and Code Approvals Appliance Certification BTU & Efficiency SpecificationsGlass Specifications Mobile Home ApprovedFire Safety Getting StartedAppliance needs to draft properly for safety Millennium Wood Stove ACC Negative PressureTools And Supplies Needed Millennium Wood Stove ACC Flue Draft ConsiderationsVenting Systems Inspect Appliance & Components Pre-Burn Check ListMillennium Wood Stove ACC Typical Stove Systems Masonry ChimneyDimensions and Clearances Appliance DimensionsBackwall / Sidewall Corner Installation See Figure InstallationRHearth Protection Requirements USA required Canada recommendedMillennium Wood Stove ACC Outside Air Kit Installation Items Needed for Installation not suppliedFloor Installation Alternative In some instances you Blower Optional 13-15/16 in mmVenting Components Chimney Systems Chimney ConnectorChimney Requirements ThimbleInstructions ComponentsAir Clearances Solid Pack Chimney with Metal Supports as a ThimbleSolid Pack Chimney with Metal Supports as a Thimble Cont’d Installing Chimney ComponentsSingle wall connector or stove pipe Chimney Height / Rise and RunPitched Roof Millennium Wood Stove ACC Chimney Termination RequirementsRule Flat RoofMobile Home Installation Door Handle Assembly Adjusting The Blower Speed Control Appliance Set-UpBurning Process Operating InstructionsOver-Firing Your Appliance Wood Selection & Storage Cont’d Wood Selection & StorageAutomatic Combustion Control ACC Air ControlsBurn Rates and Operating Efficiency Millennium Wood Stove ACC Building a Fire Incorrect Positions Opacity Smoke Initial cold start-up and all Burn SettingsMillennium Wood Stove ACC Blower Operating Instructions Snap Disc LocationMillennium Wood Stove ACC Frequently Asked Questions Odor from applianceAppliance Quick Reference Maintenance Guide Maintaining & Servicing Your ApplianceGlass Cleaning Frequency As desired Millennium Wood Stove ACC General MaintenanceCreosote Chimney Cleaning Disposal of AshesGlass Replacement When cleaning glassMillennium Wood Stove ACC Firebrick Replacement To your authorized dealerCorrect Blanket & Baffle Position on BaffleMillennium Wood Stove ACC Tube Channel Assembly Replacement Removing Tube Channel AssemblyReplacing Tube Channel Assembly Troubleshooting Start Fire Problems Possible Cause Solution21M-ACC Millennium Wood Stove21M-ACC Stocked 21M-ACC Millennium Wood Stove ACC Service And Maintenance Log Date of Service Performed By Description of ServiceMillennium Wood Stove ACC Service And Maintenance Log Cont’d Millennium Wood Stove ACC Homeowner’s Notes Millennium Wood Stove ACC Homeowner’s Notes Millennium Wood Stove ACC Warranty Policy Millennium Wood Stove ACC Contact Information