D. Chimney Termination Requirements
Follow manufacturer’s instructions for clearance, securing flashing and terminating the chimney.
•Must have an approved and listed cap
•Must not be located where it will become plugged by snow or other material
•Must terminate at least 3 feet (91cm) above the roof and at least 2 feet (61cm) above any portion of the roof within 10 feet (305cm).
•Must be located away from trees or other struc- tures
NOTE:
•Chimney performance may vary.
•Trees, buildings, roof lines and wind conditions affect performance.
•Chimney height may need adjustment if smoking or overdraft occurs.
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper flue draft.
Less than 10 ft. (305cm)
2 ft. (61cm)
10 ft. (305cm) To Nearest Roofline
3 ft. (91cm)
Minimum
2 ft. (61cm) | 3 ft. (91cm) |
| Minimum |
Pitched Roof
Figure 17.1
10 ft. (305cm) or more | Less than 10 ft. (305cm) |
|
|
Wall or Parapet
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum | 3 ft. (91cm) Minimum |
|
Figure 17.2 | Flat Roof |
|