Quadra-Fire 7051-158B owner manual Edge 60 Pellet Fireplace Through the Wall, Straight Out, Degree

Page 46

R

EDGE 60 Pellet Fireplace

L. Through the Wall

Horizontal termination cap must be a minimum of 12 inches (305mm) from the wall. Approved for mobile home installations. Must use 3 or 4 inch (76mm-102mm) “L” or “PL” Listed pellet venting and a Quadra-Fire Outside Air Kit in ALL installations.

NOTE:

In Canada, where passage through a wall or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365

Straight Out

0 in. (0mm) to Standoff

6in.

(152mm) Minimum

From Glass

Horizontal

Wall Termination

Thimble Cap

12 in. (305mm) Minimum

Non-combustible

Hearth Extension

Figure 45.1

NOTICE! See Section 8 “Avoiding Smoke and Odors” to minimize soot damage to exterior walls of the house and to prevent re-entry of soot or ash into the house for horizontal vent confi guration

45 Degree

Illustration shows venting going in both directions.

 

Choose which one is best for your installation.

12 IN. (305MM)

MINIMUM

WALL

THIMBLE

12 IN. (305MM)

MINIMUM

1-1/6 IN.( 27MM)

MINIMUM

1-16 IN.

(27MM)

MINIMUM

Figure 45.2

Page 46

7051-158B

December 6, 2011

Image 46 Contents
Natural Curved Tuscan Studio Hot glass will cause burnsEdge 60 Pellet Fireplace Serial Number LabelTable of Contents Edge 60 Pellet Fireplace Edge 60 Pellet Fireplace Listing and Code Approvals User’s Guide Operating InstructionsCombustible/Non-Combustible Materials Edge 60 Pellet Fireplace Fire SafetyFuel Material and Fuel Storage General Operating Information Power SwitchAuto-Clean Firepot System Before Your First FireStarting Your First Fire Edge 60 Pellet Fireplace Filling the Hopper with FuelIgnition Cycles Manual Mode Auto-Clean CycleAutomatic Mode Soft Start Cycle SS-Low / SS-MedBattery Back-up System Optional Edge 60 Pellet Fireplace Battery Back-up System Cont’d Clear SpaceMaintaining & Servicing Your Appliance Quick Reference Maintenance ChartCleaning or Inspection Before Servicing Your ApplianceAccessing Components for Maintenance Edge 60 Pellet Fireplace High Ash Fuel Content MaintenanceCleaning Ash Pan Auto-Clean System Inspection & CleaningDisposal of Ashes Frequency As needed Cleaning Heat Exchanger, Drop Tube & Exhaust Shop Vac* Example Micro Cleaning KitClinker Cleaning the Glass Cleaning the HopperCleaning Convection Blower Do Not Use Lubrication Cleaning Exhaust Blower Do Not Use LubricationChimney Inspection and Cleaning Troubleshooting for Homeowner Frequently Asked QuestionsPossible Cause Corrective Action Appliance Location Getting StartedFloor Support Inspect Appliance and Components Checklist to Help Determine LocationTools And Supplies Needed DescriptionCrush Hazard Material is installed. See Item GRecommended Sequence Recommended Locations Framing Dimensions & ClearancesOutside Air Kit is Required for All installations Hearth ExtensionSealing at the Penetration of Building Envelope Frame the FireplaceEdge 60 Pellet Fireplace Construct the Chase 27.1Behind the Mounting Frame Edge 60 Pellet Fireplace Finishing MaterialFlush with the Mounting Frame Protrudes Beyond the Mounting FrameOpening Clearances for the Curved Tuscan and Natural Fronts Opening Clearances for the Studio Front Edge 60 Pellet Fireplace Mantel Fuel Loading Clearances Rise to run ratioEdge 60 Pellet Fireplace Non-Combustible Materials Combustible MaterialsPosition the Fireplace Installation of FireplaceSub-Floor Material & Securing Fireplace Crush Hazard Power Supply Cord Wall Control Wire Shock HazardVertical Installation Back Side of Wall Control with Cover OffVertical Installation Cont’d Horizontal Installation Do not Terminate Vent Vent InformationVenting Termination Minimum Requirements Termination must exhaust above air inlet elevationEdge 60 Pellet Fireplace Avoiding Smoke and Odors Edge 60 Pellet Fireplace Negative Pressure Draft Equivalent Feet of Pipe Edge 60 Pellet Fireplace Chimney and Exhaust ConnectionExample of 3 Elbow-Rear Vent Termination Calculation Edge 60 Pellet Fireplace Pipe Selection Chart Altitude in Thousands of FeetLeft Rear Corner Right Rear Corner Rear of Fireplace Outside Air Inlet LocationsEdge 60 Pellet Fireplace Outside Air Kit Installation Install Outside Air KitVertical Interior Typical Installation Through the Wall & Vertical ExteriorStraight Out Choose which one is best for your installationEdge 60 Pellet Fireplace Through the Wall DegreeMobile Home Installation Rebox. Figures 47.1 Optional Log Set Placement InstructionsAppliance Set-Up Rebox. Figures 47.3Front Installation Replacement Parts Glass ReplacementConvection Blower Replacement Baffl e Removal & Replacement Troubleshooting For Installers Error MessageTop View Fireplace DimensionsReference Materials Rear ViewEdge 60 Pellet Fireplace Component Functions Vacuum Switch Power SupplyPower Switch Overheat Sensor Snap DiscEdge 60 Pellet Fireplace Component Locations View of Left RearEdge 60 Pellet Fireplace Service And Maintenance Log Date of Service Performed By Description of ServiceContact Information Hearth & Home Technologies