OPERATION / MAINTENANCE
Purge all gas lines with the glass door open. Assure that a continuous gas flow is at the burner before closing the door. Allow several minutes
TURBO BURNER OPERATION
AND MAINTENANCE
The purpose of the turbo burner is to increase heat output or BTUs of the unit and will only operate when the main burner is functioning. To turn the turbo burner on, simply depress the burner control knob (located in the valve com- partment at the left hand side below the piezo ignitor) and rotate the knob
The turbo burner flame can be observed on the reflective surface in the back right corner of the firebox.
The burner flame height may now adjusted to achieve the heat output required. Because the flame is very efficient it will burn a very blue, almost transparent colour.
OPERATING INSTRUCTIONS
To turn off the burner, rotate the control knob clockwise to 'high'; depress the knob and turn to 'off'.
The
When lit for the first time, the fireplace will emit a slight odour for a few hours. This is a normal temporary condi- tion caused by the curing of the logs and the
MODEL GS50 ONLY
SPILL SWITCH
This is a thermally activated switch, attached to the back of the chimney adapter, which senses the change in temperature and shuts down the gas valve in the event of a severe downdraft of air or a blocked or disconnected vent. It acts as a safety
blocked or has no "draw", the spill switch will automatically shut off the supply of gas within about
TAMPERING WITH THE SWITCH CAN RESULT IN CAR- BON MONOXIDE (CO) POISONING AND POSSIBLE DEATH.
VENTING ACTION CHECK: ACHECK FOR CORRECT VENTING ACTION MUST BE MADE BEFORE THE IN- STALLED STOVE IS LEFT WITH THE CUSTOMER. Test in the following manner:
1.Close all doors and windows in the room / start exhaust fans in the
home / turn fireplace blower off (if
equipped).FIGURE 38
2.Set controls to "high" and light the unit.
3.Wait 5 minutes. Light a match and extend it 1" into the hole located above the spill switch bracket on the adapter.
4.Venting action is satisfactory if the flame stays lit. Vent- ing action is unsatisfactory if the flame extinguishes.
5.If venting action is unsatisfactory, turn the unit off, wait 10 minutes and try again. If the match does not stay lit, turn the unit off and check for vent blockage or restriction. If nec- essary, consult with a qualified inspector.