9
WALL AND CEILING PROTECTION
FOR SAFE AND PROPER OPERATION OF THE STOVE, FOLLOW THE VENTING INSTRUCTIONS EXACTLY.
HORIZONTAL INSTALLATION |
| VERTICAL INSTALLATION |
This application occurs when venting through an ex- terior wall. FIGURES 5, 6, & 13. Having deter- mined the air terminal loca- tion, cut and frame a hole in an exterior wall with a mini- mum square or round open- ing of 9". (As an alternative to framing, a vent pipe shield may be installed, en- suring a 1" clearance to
combustibles. See Figure 11.)
THE STOVE PIPE MUST RISE ¼" PER FOOT OF RUN.
1.Mark and cut the vent pipe shield to the determined depth of the combustible wall. Apply a bead of caulking (not supplied) to the framework or to the shield plate (in the case of a finished wall) and secure the shield through the opening to the interior wall. The final location of the vent pipe shield should maintain the required clearance to the 7" vent pipe. Do not fill this cavity with any type of material.
OR
FIGURE 12
Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the stove. Ensure that both spacer and shield maintain the required clearance to com- bustibles. Once the vent pipe is installed in its final posi- tion, apply sealant between the pipe and the firestop spacer.
This application occurs when venting through a roof. FIGURE 13. Installation kits for various roof pitches are avail- able from your Napoleon dealer. See Accessories to order the specific kit required.
1.Determine the air ter-
minal location and move |
| |
the stove into position. |
| |
Cut and frame 9 inch | FIGURE 13 | |
openings in the ceiling | ||
| ||
and the roof to provide the |
| |
minimum 1 inch clear- |
| |
ance between the stove |
| |
pipe and any combustible |
| |
material. Try to center the |
| |
exhaust pipe location |
| |
midway between two joist |
| |
to prevent having to cut |
| |
them. Use a plumb bob |
| |
to line up the center of the |
| |
openings. |
|
Do not fill this space with any type of material.
A vent pipe shield will prevent any materials such as insu- lation, from filling up the 1" air space around the pipe. FIGURE 15. Nail headers between the joist for extra sup- port.
FIGURE 14
2.Apply a bead of caulking (not supplied) to the frame- work or to the Wolf Steel vent pipe shield plate or equivalent (in the case of a finished ceiling), and secure over the open- ing in the ceiling. FIGURE 14. A firestop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. FIGURE 13. Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the stove. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its final position, apply sealant between the pipe and the firestop spacer.
3.In the attic, slide the vent
pipe collar down to cover up the open end of the shield and tighten. This will prevent any materials, such as insulation, from filling up the 1” air space around the pipe.
FIGURE 15