Vermont Casting RDVOD manual Gas Specifications, Gas Inlet and Manifold Pressures, High Elevations

Page 6

Gas Specifications

 

 

 

 

 

 

Max.

Min.

 

 

 

 

 

 

Input

Input

 

Model

Fuel

Gas Control

BTU/h

BTU/h

 

RDVODRN

Nat

 

Millivolt

35,000

25,000

 

RDVODRP

Prop

 

Millivolt

35,000

27,500

 

RDVODRFN

Nat

Comfort Control

35,000

25,000

 

RDVODRFP

Prop

Comfort Control

35,000

27,500

Weight: Fully assembled; 350 lbs.

 

 

 

 

 

 

 

Gas Inlet and Manifold Pressures

 

 

 

 

 

 

 

 

 

 

 

Natural

 

LP (Propane)

 

Inlet Minimum

 

5.5” w.c.

 

11.0” w.c.

 

Inlet Maximum

 

14.0” w.c.

 

14.0” w.c.

 

Manifold Pressure

 

3.5” w.c.

 

10” w.c.

 

 

 

 

 

 

 

 

Radiance Direct Vent/Natural Vent

Certified to:

ANSI Z21.88b-2002 / CSA 2.33b-2002

Vented Gas Fireplace Heaters

The installation of your Vermont Castings stove must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 - latest edition, or CSA B149.1 Installation code. (EXCEPTION: Do not derate this appliance for altitude up to 4,500 feet (1,370m). Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c. for LP Gas.

High Elevations

Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.

For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.

In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).

WARNING: Improper installation, adjust- ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

Radiance Direct Vent /Natural Vent Gas Heater

Horizontal Termination -

Direct Vent ONLY

The vent must rise vertically a minimum of 24” (610mm) off the top of the unit, before the first elbow. The hori- zontal run may extend up to 20’ (6m) and include a vertical rise of up to 40’ (12m). (Fig. 7) Horizontal termi- nation must also meet the criteria shown in Figures 10 through 12.

Approved vent systems must terminate above and including the heavy line in Figure 7.

Two 45˚ elbows may be substituted for each single 90˚ elbow.

With a rise between 2’ - 5’, one 90˚ or two 45˚ elbows may be used.

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pipe.)

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

top

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

feet)(inRunVertical collarflueappliancetheto the

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

May

use

up

to

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

three 90°

Elbows

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

���

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

���

 

 

 

 

 

One

90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elbow

 

 

 

 

 

 

 

Unacceptable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Venting

Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

� � � � � � � � �� �� �� �� �� �� �� �� �� �� ��

Horizontal Run (in feet)

ST134a

Fig. 7 Horizontal vent termination window.

20004188

7

Image 6
Contents Radiance Direct Vent/Natural Vent Gas Heater Installation & Operating Instructions Radiance Direct Vent/Natural Vent Stove Dimensions Radiance dimensionsInstallation Requirements Locating The StoveClearance Requirements Wall Centerline from Floor Wall and Ceiling ClearancesHearth Requirements High Elevations Gas SpecificationsGas Inlet and Manifold Pressures Horizontal Termination Direct Vent onlyRestictor Plate is used on Direct Vent installations only Vertical Termination Direct Vent onlyVent Termination Clearances Location of Vent Termination Canadian Installations US Installations General Venting Information Termination LocationVenting Requirements Natural Vent Only Plate supplied with the stove is not usedVenting Requirements and Options Direct Vent only Approved Vent System ComponentsTools Required Assembly ProceduresParts Bag Contents Unpack and Assemble LegsInstall the Optional Fan Remove rear shroudFor Canadian installations The venting system must Venting System Assembly Direct Vent General InformationInstall the Vent Adapter Pipe Attach the Inner Vent Assembly to the stoveSide Wall Termination Assembly Install the Outer Adapter Pipe. Orient the vertiDiscard the inner starter pipe shipped with the log Measure the horizontal length Vertical Through the Roof Vent Assembly Vent Termination Below GradeVenting System Assembly Natural Vent General Information Install firestops and attic insulation shieldInstall the Vent Pipe Install Log SetInstall the left and right rear logs and the right log Connect the Gas Supply LineBurner Information Install ON/OFF SwitchInstall the Mesh and Grille Thermostat Connection optionalOperation Flame & Temperature AdjustmentFlame Characteristics Your First FireLighting and Operating Instructions To Turn Off Gas To HeaterTroubleshooting / Honeywell #8420 Gas Control System Symptom Possible Causes Corrective ActionOn Manual Mode Shut Off ProcedureTransmitter Operation Off Mode Delay Timer ModeLocal Path On Path Auto Path Change Between F/C Temperature Units Auto ModeFan Override During Auto Mode Disable Thermostat FunctionAll Models Air Shutter AdjustmentInjector Orifice Size Matrix Conversion to Natural Gas Input BTU/hMaintenance Gasket Replacement Inspect the Vent System AnnuallyCheck the Gas Flame Regularly Wiring Diagrams BLKRadiance Direct Vent/Natural Vent Gas Heater Rdvod DescriptionRadiance Direct Vent/Natural Vent Gas Heater Rdvod Fuel Conversion Kits Shell Enamel Parts Radiance Direct Vent / Natural VentOptional Accessories Limited Lifetime Warranty Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %