Honeywell Gas Control Valve (Fig. 50)
The Honeywell valve fitted to this unit is suitable for use with LP or Natural Gas. It is converted to the required gas application by installing a
a)Using a suitable small screwdriver, lift out the cen- tral regulator cap from the “HI/LO” knob on the valve.
b)Unscrew the exposed conversion screw.
c)Insert the new color coded conversion screw. Do not overtighten the screw; it must be finger- tight.
d)Refit the regulator cap.
e)Mount conversion label supplied with the conver- sion screw to the valve in a visible position.
10.Reassemble fireplace in the reverse order, except for the window frame assembly. Leave this off until after unit has been checked for leaks and the gas supply has been bled.
11.After bleeding the gas line and checking for leaks with a soap solution, replace the window frame as- sembly.
12.Fire up the unit. Check for flame impingement on the logs, adjusting them as necessary.
13.Check manifold and supply pressures against the appliance specifications.
The procedure for converting from one gas to another is the same regardless of the initial gas used. The only variations are
in orifice sizes and component part num- bers. Your authorized service provider will ensure correct parts are used.