8 Installing Vent Pipe and Appliance
A. Vent Limits
The abbreviations listed in this vent table key are used in the vent diagrams.
Description
Minimum Vertical Run Length 13 ft. (4.0 m)
Maximum Vertical Run Length 40 ft. (12 m)
See Figure 8.13 for horizontal venting with optional SLP venting configuration.
Vertical terminations are measured to top of chimney.
This appliance is listed for use with
WARNING! Risk of Fire/Explosion/Asphyxiation! Do NOT connect this gas appliance to a chimney flue serving a separate solid fuel or gas burning appliance.
•May impair safe operation of this appliance or other appliances connected to the flue.
•Vent this appliance directly outside.
•Use separate vent system for this appliance.
CAUTION! ALL vent specifications MUST be followed. This product is tested and listed to these specifications. Appli- ance performance will suffer if specifications are not followed.
B. Venting Components
CAUTION! Risk of Cuts/Abrasions/Flying Debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp.
The vertical vent termination system installed on this model includes:
•Flexible vent pipe for exhaust air (included with vent kit).
•One length of 3 in. (76 mm) flexible vent pipe for combustion air (included with vent kit).
•One
•One vertical termination cap (included with vent kit).
C. Connecting Vent Pipe
Reference instructions in the termination kit.
•Install the
•Secure the exhaust flexible vent pipe to the exhaust starting collar on to of the appliance with three screws and seal with stove cement rated for continuous exposure to 649 ºC (1200 ºF) or higher. See Figure 8.1.
•Use 3 screws to attach the section of inlet air vent to the inlet collar on the collar slide plate and seal with stove cement rated for continuous exposure to 649 ºC (1200 ºF) or higher. See Figure 8.1. NOTE: The collar slide plate may be removed from appliance to aid installation.
ADAPTER
V = 13 FT. (4.0 m) MINIMUM 40 FT. (12 m) MAXIMUM
TERMINATION
CAP
INLET
COLLAR
EXHAUST
COLLAR
EXHAUST
AIR
VENT PIPE
INLET AIR
VENT PIPE
INLET AIR STARTING COLLAR
LOCKING TAB
SEAL WITH STOVE CEMENT 1200º F (649ºC) OR HIGHER
STARTING COLLAR BRACKET
EXHAUST STARTING COLLAR
INLET AIR STARTING COLLAR
| NOTE: TO ACHIEVE OPTIMUM PERFOR- |
|
| MANCE OF INSERT, MINIMIZE OR AVOID |
|
STARTING COLLAR BRACKET | BENDS IN EXHAUST VENT PIPE. |
|
EXHAUST STARTING COLLAR |
|
|
Figure 8.1 |
|
|
Heat & Glo • | 23 |