9 Gas Information

A. Gas Pressure Requirements

Pressure requirements for Supreme-N-I30AU and Su- preme-P-I30AU fireplaces are shown in table below.

Two taps are provided on the front of the gas control for a test gauge connection to measure the inlet and outlet pressures.

The fireplace and its individual shut-off valve must be dis- connected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 6 kPa.

If the fireplace must be isolated from the gas supply pip- ing system by closing an individual shut-off valve, it must be of the handle-less type.

WARNING

Fire Risk

Explosion Risk

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 6 kPa.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 6 kPa.

ON/OFF/REMOTE

SWITCH

GAS VALVE

CONTROL

 

MODULE

DC ADAPTER

Figure 11.1. Valve Components

B. Gas Connection

Note: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality.

Note: Before the first firing of the appliance, the gas supply line should be purged of any trapped air.

Note: Consult local building regulations to properly size the gas supply line leading to the (Rp 1/2 in.) hook-up at the unit.

Incoming gas line should be piped into the valve compart- ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2) threaded gas inlet connection on the manual shutoff valve.

IMPORTANT NOTICE: (Items 1, 2 and 3 applies to

 

ALL Heat & Glo gas appliances)

 

1.1/2 in. GAS LINE: Run through cavity 70 mm above finished hearth level, NOT RIGID, NOT CLIPPED, with minimum 500 mm into cavity and 120 mm back from plaster face.

2.PVC (COMPOSITE) GASLINE must terminate minimum 500 mm short of gas heater. Copper pipe MUST be the final connection to the gas heater.

3.ISOLATING SWITCH: Location within 1 metre of fireplace, subject to mantelpiece etc. Check to ensure it remains clear of any mantelpiece instal- lation.

Leak test all gas line points and the gas control valve prior to and after starting the gas appliance.

WARNING

CHECK FOR GAS LEAKS

Explosion Risk

Fire Risk

Asphyxiation Risk

Check all fittings and connections.

Do not use open flame.

After the gas line installation is complete, all connections must be tightened and checked for leaks with a commercially-available, non- corrosive leak check solution. Be sure to rinse off all leak check solution following testing.

Fittings and connections may have loosened during shipping and handling.

 

 

Natural Gas

Propane

 

Inlet Gas Pressure

1.13

- 3.40 kPa

2.75 - 3.40 kPa

 

Outlet (Manifold) Gas Pressure

.80

- .95 kPa

2.36 - 2.61 kPa

 

Maximum Gas Consumption

31.9 MJ/h

30.9 MJ/h

 

Burner Injector

DMS 36 (2.70 mm)

DMS 52 (1.61 mm)

Pilot Injector

 

.023

.014

An in-line regulator MUST be installed if the gas pressure exceeds 3.40 kPa. Failure to install a regulator could damage valve.

36

Heat & Glo • Supreme-N-I30AU, Supreme-P-I30AU2222-900 Rev. P • 6/12

Image 36
Contents Models SUPREME-N-I30AU SUPREME-P-I30AU SAI Global Ref No GSCS20181What to do if you smell gas HOT SurfacesMODELSSupreme-N-I30AU,Supreme-P-I30AU Congratulations Homeowner Reference InformationTable of Contents User GuideAustralian Warranty Information Limited Lifetime WarrantyOther Rights Perth Listing and Code Approvals Gas Fireplace Safety Operating Instructions User GuideYour Fireplace Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesIPI Battery Tray/Battery Installation Clear SpaceModule Reset Nine Hour Safety Shutdown FeatureBefore Lighting Fireplace Lighting Instructions IPI Final inspection byWhat to do if YOU Smell GAS GAS ValveFrequently Asked Questions Issue SolutionsAfter Appliance is Lit Maintenance and Service Maintenance Tasks-Service Technician Gasket Seal and Glass Assembly InspectionLogs FireboxGetting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Fireplace Size Requirements Minimum Fireplace OpeningTOP View Front View Side View Fireplace OpeningMantel and Wall Projections SUPREME-I30AUTermination Locations Vent Termination Minimum ClearancesInstallation Preparation Installing Vent Pipe and Appliance Connecting Vent PipeVent Limits Venting ComponentsPage Placing, Securing and Leveling Appliance Installing Adaptor and Termination Cap MasonryFactory Built Damper Flashing Kit OptionalModel Flue Termination Approval Direct Vent Flex Liner Accessory Kits Vent Kits ComponentsFor Horizontal Terminations using the SLP-TRAP2 Flue TerminationHeat Shield Requirements for Horizontal Termination Must adhere to pipe clearances Colinear to Coaxial Adapter Must adhere to pipe clearances Alternate built-in options Minimum construction requirementsSLP-TVHW Minimum TotalLink Adapter Maximum TotalNON-COMBUSTIBLE Base Under Unit Flue Starter Plate Gas Information Gas ConnectionWiring Requirements IntelliFire PlusTM Ignition System WiringElectrical Information Optional Accessories Requirements Fan Wiring DiagramKit Contents Installation PrecautionsREM300-HNG-AU Instructions Fireplace Specific InformationChanging Temperature Scale Installation of Remote Control HousingAUX300CE Module Installation Fan InstallationProgramming the RC300AU to the Control Module Idle When Remote is in on Mode Standby modeDisplay Screen Function ButtonsAbout on Mode About OFF ModeAdjusting Flame Height Adjusting Fan SpeedAdjusting Thermostat Adjusting TimerSetting the Child Lock Power OutageFrequently Asked Questions/Troubleshooting Symptom Possible Cause Corrective ActionFinishing Clearances to Mantels or other Combustibles above ApplianceAppliance Setup Install the Log Assembly Pilot AS Sembly LOG PIN Grate TinesCorner LOG Flush With LOG TAB For LOG #6Air Shutter Setting Air Shutter SettingsLatches Required to Complete Insert Installation Decorative Fronts and SurroundsOptional Accessories Optional RC300AU Remote Optional BRICK-SI30 KitIPI+ Troubleshooting Symptom Possible Cause Corrective ActionIntelliFire Plus Ignition System If the pilot continues Maintenance Tasks Inspect Maintenance TasksAppliance Dimension Diagram Model DimensionsReference Materials SUPREME-I30-AUService Parts Log Set AssemblyMetal Insert, IPI Description Comments Part Number#15 Valve Assembly SUPREME-N-I30AU, SUPREME-P-I30AU Contact Information

SUPREME-P-I30AU, SUPREME-N-I30AU specifications

The Heat & Glo LifeStyle SUPREME-P-I30AU and SUPREME-N-I30AU are premium gas fireplaces designed to create a cozy, inviting atmosphere while offering modern technological features and exceptional performance. These units are perfect additions to any home, blending elegance with practicality.

One of the standout features of the SUPREME series is its versatile design. The fireplaces are available in both linear and traditional styles, allowing homeowners to choose the configuration that best complements their living space. With a sleek, modern aesthetic, the SUPREME-P-I30AU offers a panoramic view of the flames, making it a captivating focal point in any room.

These models are equipped with advanced heating capabilities. The powerful heat output ensures that the fireplace can effectively warm spaces ranging from medium to large. Homeowners can enjoy optimal comfort during the colder months, knowing they have a reliable source of heat at their disposal.

Another key characteristic is the innovative IntelliFire technology, which automates the ignition system and monitors the flame to ensure safe and efficient operation. This feature not only enhances the user experience but also minimizes energy consumption by allowing the unit to alternate between different flame settings based on the home's heating needs.

Installation is made easy with the SUPREME series, thanks to its flexible venting options. The fireplaces can be vented either vertically or horizontally, making them suitable for various home layouts. Additionally, the units are designed for easy access to components, simplifying maintenance and ensuring longevity.

Both the SUPREME-P-I30AU and SUPREME-N-I30AU come with a range of aesthetic options for customization, including different media choices such as logs, glass, and stones. This allows users to tailor the appearance of their fireplace to match their personal style and home décor.

Safety features are paramount in the design of the SUPREME series. The fireplaces include advanced safety controls and thermal sensors to prevent overheating and ensure peace of mind for users.

In summary, the Heat & Glo LifeStyle SUPREME-P-I30AU and SUPREME-N-I30AU stand out due to their stylish designs, powerful heating capabilities, innovative technologies, and customizable options, making them ideal choices for anyone looking to enhance their home with a functional and aesthetically pleasing gas fireplace.