Hatco IMPERIAL "S Specifications, Circuit Breaker & Fused Disconnect Switch Sizes 4 to 12 kW

Page 7

SPECIFICATIONS

CIRCUIT BREAKER & FUSED DISCONNECT SWITCH SIZES - 4 TO 12 kW

kW

Volts*

Phase

 

Amp Draw

 

 

Breaker or

Copper

Conduit

 

 

 

L1

 

L2

 

L3

 

Fuse Size

Wire Size

Size

 

 

 

 

 

 

 

 

 

 

 

 

4

208

1

19

 

19

 

-

30

10

1/2" (13 mm)

 

240

1

17

 

17

 

-

30

10

1/2" (13 mm)

 

480

1

8

 

8

 

-

15

14

1/2" (13 mm)

5

208

1

24

 

24

 

-

30

10

1/2" (13 mm)

 

240

1

21

 

21

 

-

30

10

1/2" (13 mm)

 

480

1

10

 

10

 

-

15

14

1/2" (13 mm)

6

208

1

29

 

29

 

-

40

8

1/2" (13 mm)

 

208

3

14

 

25

 

14

40

8

1/2" (13 mm)

 

240

1

25

 

25

 

-

40

8

1/2" (13 mm)

 

240

3

13

 

22

 

13

30

10

1/2" (13 mm)

 

380

3

9.2

 

9.2

 

9.2

15

14

1/2" (13 mm)

 

480

3

6

 

11

 

6

15

14

1/2" (13 mm)

 

600

3

5.7

 

5.7

 

5.7

15

14

1/2" (13 mm)

7

208

1

34

 

34

 

-

50

8

1/2" (13 mm)

 

208

3

17

 

29

 

17

40

8

3/4" (19 mm)

 

240

1

29

 

29

 

-

40

8

1/2" (13 mm)

 

240

3

15

 

25

 

15

40

8

1/2" (13 mm)

 

380

3

11.4

 

11.4

 

11.4

15

14

1/2" (13 mm)

 

480

3

7

 

13

 

7

20

12

1/2" (13 mm)

 

600

3

6.7

 

6.7

 

6.7

15

14

1/2" (13 mm)

9

208

1

43

 

43

 

-

60

6

1/2" (13 mm)

 

208

3

22

 

38

 

22

50

8

1/2" (13 mm)

 

240

1

38

 

38

 

-

50

8

1/2" (13 mm)

 

240

3

19

 

33

 

19

50

8

1/2" (13 mm)

 

380

3

13.3

 

13.3

 

13.3

20

12

1/2" (13 mm)

 

480

3

9

 

16

 

9

20

12

1/2" (13 mm)

 

600

3

8.7

 

8.7

 

8.7

15

14

1/2" (13 mm)

9.9

208

1

47.5

 

47.5

 

-

60

6

1/2" (13 mm)

 

208

3

27.5

 

27.5

 

27.5

40

8

1/2" (13 mm)

10.4

208

3

28.8

 

28.8

 

28.8

40

8

1/2" (13 mm)

10.5

208

1

51

 

51

 

-

70

4

3/4" (19 mm)

 

208

3

29

 

29

 

29

40

8

1/2" (13 mm)

 

240

1

44

 

44

 

-

60

6

1/2" (13 mm)

 

240

3

25.3

 

25.3

 

25.3

40

8

1/2" (13 mm)

 

480

3

12.6

 

12.6

 

12.6

20

12

1/2" (13 mm)

 

600

3

10

 

10

 

10

15

14

1/2" (13 mm)

11.4

240

1

47.5

 

47.5

 

-

60

6

1/2" (13 mm)

 

240

3

27.5

 

27.5

 

27.5

40

8

1/2" (13 mm)

 

480

3

13.7

 

13.7

 

13.7

20

12

1/2" (13 mm)

12

208

1

58

 

58

 

-

90

3

1" (25 mm)

 

208

3

33

 

33

 

33

50

8

1/2" (13 mm)

 

240

1

50

 

50

 

-

70

6

1/2" (13 mm)

 

240

3

29

 

29

 

29

40

8

1/2" (13 mm)

 

380

3

19.1

 

19.1

 

19.1

30

10

1/2" (13 mm)

 

480

3

14.5

 

14.5

 

14.5

20

12

1/2" (13 mm)

 

600

3

11.6

 

11.6

 

11.6

15

14

1/2" (13 mm)

 

 

 

 

 

 

 

 

 

 

 

 

Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table 310-16. Conduit size based on conductors plus ground wire sizing per Table C1 from Appendix C.

Only 6, 7 & 9 kW models can be field converted to single or three phase (open delta on 3 phase). Larger branch circuit required than for balanced 3 phase of equal kW. Balanced 3 phase available, consult factory.

NOTE: 250 kcmil maximum wire size for terminal block.

5

Form No. EBOOSTERM-0406

Image 7
Contents Electric Booster Water Heaters Important Owner Information ContentsIntroduction Important Safety Information Important Safety Information Important Safety Information Compact Models C Series Model DescriptionsALL Models Imperial Models S SeriesCircuit Breaker & Fused Disconnect Switch Sizes 4 to 12 kW SpecificationsFuse Size Wire Size Volts Phase Amp Draw Breaker or Copper N d u i tCircuit Breaker & Fused Disconnect Switch Sizes 36 to 57 kW Boosters Rated AT 30F 16C Rise Sizing Chart for LOW-TEMP DishmachinesSpecifications Electric Compact Booster Imperial Booster Booster Heater Sizing ChartWM-5C FW4 Stpc Stpcw Capacity MINI-COMPACT MC Series Model 40F 22C Rise 70F 39C Rise Shipping WeightCapacity Imperial S Series Capacity Compact C SeriesDimensions Imperial S Series Dimensions MINI-COMPACT MC Series InstallationLocation Installing Legs Mounting Brackets with Hardware Temperature/Pressure GaugeTemperature Pressure Relief Valve Leg Pressure Reducing ValveFor Installing Pressure Pressure and Temperature Relief ValvesPlumbing Connections TEMPERATURE/PRESSURE GaugesPressure Reducing Valve Blended Phosphate Water Treatment System OptionalRefer to , 9, 10, 11 or InletPlumbing Connections Imperial S Series Form No. EBOOSTERM-0406 Outlet General ELECTRICAL-ALL Sizes and VoltagesSystem START-UP OperationShut Down General MaintenanceHigh Temperature Limit Safety Switch Thermostat AdjustmentBlended Phosphate Treatment System Optional Shock Absorber AccessoriesStainless Steel Adjustable Legs Floor Mounting HardwareTroubleshooting Symptom Probable Cause Corrective Action Troubleshooting Troubleshooting Product Warranty Hatco Limited WarrantyForm No. EBOOSTERM-0406 Form No. EBOOSTERM-0406 Form No. EBOOSTERM-0406 Hatco Authorized Parts Distributors