SPECIFICATIONS
CIRCUIT BREAKER & FUSED DISCONNECT SWITCH SIZES - 13.5 TO 30 kW
(continued)
kW | Volts* | Phase |
| Amp Draw |
| Breaker or | Copper | C o n d u i t | |||
|
|
| L1 |
| L2 |
| L3 | Fuse Size | Wire Size | Size | |
|
|
|
|
|
|
|
|
|
|
|
|
13.5 | 208 | 1 | 65 |
| 65 |
| - | 90 | 3 | 1" (25 mm) | |
| 208 | 3 | 38 |
| 38 |
| 38 | 50 | 8 | 1/2" (13 mm) | |
| 240 | 1 | 56.3 |
| 56.3 |
| - | 90 | 3 | 1" (25 mm) | |
| 240 | 3 | 33 |
| 33 |
| 33 | 50 | 8 | 1/2" (13 mm) | |
| 480 | 3 | 16.3 |
| 16.3 |
| 16.3 | 30 | 10 | 1/2" (13 mm) | |
| 600 | 3 | 13 |
| 13 |
| 13 | 20 | 12 | 1/2" (13 mm) | |
15 | 208 | 1 | 72 |
| 72 |
| - | 90 | 3 | 1" (25 mm) |
|
| 208 | 3 | 41.7 |
| 41.7 |
| 41.7 | 60 | 6 | 3/4" (19 mm) | |
| 240 | 1 | 62.5 |
| 62.5 |
| - | 90 | 3 | 1" (25 mm) | |
| 240 | 3 | 36.1 |
| 36.1 |
| 36.1 | 50 | 8 | 1/2" (13 mm) | |
| 380 | 3 | 23.0 |
| 23.0 |
| 23.0 | 30 | 10 | 1/2" (13 mm) | |
| 480 | 3 | 18.1 |
| 18.1 |
| 18.1 | 30 | 10 | 1/2" (13 mm) | |
| 600 | 3 | 14.5 |
| 14.5 |
| 14.5 | 20 | 12 | 1/2" (13 mm) | |
17.25 | 208 | 3 | 47.9 |
| 47.9 |
| 47.9 | 60 | 6 | 3/4" (19 mm) | |
18 | 208 | 1 | 86.5 |
| 86.5 |
| - | 125 | 1 | ||
| 240 | 1 | 75 |
| 75 |
| - | 100 | 3 | 1" (25 mm) | |
| 240 | 3 | 43.4 |
| 43.4 |
| 43.4 | 60 | 6 | 3/4" (19 mm) | |
| 380 | 3 | 27.3 |
| 27.3 |
| 27.3 | 40 | 8 | 1/2" (13 mm) | |
| 480 | 3 | 21.7 |
| 21.7 |
| 21.7 | 30 | 10 | 1/2" (13 mm) | |
| 600 | 3 | 17 |
| 17 |
| 17 | 30 | 10 | 1/2" (13 mm) | |
24 | 208 | 1 | 115.4 |
| 115.4 |
| - | 150 | 1/0 | ||
| 208 | 3 | 66.7 |
| 66.7 |
| 66.7 | 90 | 3 | 1" (25 mm) | |
| 240 | 1 | 100 |
| 100 |
| - | 125 | 1 | ||
| 240 | 3 | 57.8 |
| 57.8 |
| 57.8 | 90 | 3 | ||
| 380 | 3 | 38.0 |
| 38.0 |
| 38.0 | 50 | 8 | 1/2" (13 mm) | |
| 480 | 3 | 29.9 |
| 29.9 |
| 29.9 | 40 | 8 | 1/2" (13 mm) | |
| 600 | 3 | 23 |
| 23 |
| 23 | 30 | 10 | 1/2" (13 mm) | |
27 | 208 | 1 | 129.8 |
| 129.8 |
| - | 175 | 2/0 | ||
| 208 | 3 | 75 |
| 75 |
| 75 | 100 | 3 | 1" (25 mm) | |
| 240 | 1 | 112.5 |
| 112.5 |
| - | 150 | 1/0 | ||
| 240 | 3 | 65 |
| 65 |
| 65 | 90 | 3 | 1" (25 mm) | |
| 380 | 3 | 38.1 |
| 38.1 |
| 38.1 | 50 | 8 | 1/2" (13 mm) | |
| 480 | 3 | 32.5 |
| 32.5 |
| 32.5 | 50 | 8 | 1/2" (13 mm) | |
| 600 | 3 | 26 |
| 26 |
| 26 | 40 | 8 | 1/2" (13 mm) | |
30 | 208 | 1 | 144 |
| 144 |
| - | 200 | 3/0 | ||
| 208 | 3 | 83.3 |
| 83.3 |
| 83.3 | 125 | 1 | ||
| 240 | 1 | 125 |
| 125 |
| - | 175 | 2/0 | ||
| 240 | 3 | 72.3 |
| 72.3 |
| 72.3 | 100 | 3 | 1" (25 mm) | |
| 380 | 3 | 45.7 |
| 45.7 |
| 45.7 | 60 | 6 | 3/4" (19 mm) | |
| 480 | 3 | 36 |
| 36 |
| 36 | 50 | 8 | 1/2" (13 mm) | |
| 600 | 3 | 28.9 |
| 28.9 |
| 28.9 | 40 | 8 | 1/2" (13 mm) |
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table
Only 6, 7 & 9 kW models can be field converted to single or three phase (open delta on 3 phase). Larger branch circuit required than for balanced 3 phase of equal kW. Balanced 3 phase available, consult factory.
NOTE: 250 kcmil maximum wire size for terminal block.
Form No. | 6 |