TROUBLESHOOTING
WARNING
To avoid any injury or damage, the booster heater must only be serviced by qualified personnel.
WARNING
To avoid any injury or damage to the booster heater turn the power OFF at the disconnect switch/circuit breaker and allow to cool before performing any maintenance.
SYMPTOM | PROBABLE CAUSE | CORRECTIVE ACTION | |
Water at dishmachine is not | Gauge(s) not working | Check temperature of water with | |
properly. | a thermometer to be certain gauges | ||
at the proper temperature. | |||
| are working correctly. If not, replace | ||
|
| ||
|
| gauge(s). | |
|
|
| |
| Thermostat set too low. | Adjust or recalibrate (page 27). If | |
|
| thermostat will not recalibrate properly, | |
|
| replace it. | |
|
|
| |
| Booster heater has more than | If located farther than (5) linear feet | |
| (5) linear feet (1524 mm) of | (1524 mm), pipes should be wrapped in | |
| water pipe to the dishwasher, | insulation, and/or a recirculating system | |
| causing the water to cool off | installed. | |
| inside the pipe. |
| |
Heating elements burn out. | Tank inadvertently | Make sure tank is full of water | |
| drained leaving elements | at all times. Check low water | |
| in a dry condition. | system for proper operation. | |
|
|
| |
| Lime buildup in tank causing | Clean or delime tanks periodically. A water | |
| elements to split and burn out. | softener or blended phosphate treatment | |
|
| system may be required. | |
|
|
| |
Relief valve dribbles. | No pressure reducing valve | A pressure reducing valve with high | |
| installed or incorrect valve | pressure bypass must be installed in the | |
| installed causing pressure | incoming water line to allow water to | |
| expand back into the feed line. | ||
|
|
| |
| Bypass in pressure reducing | Clean bypass or replace with new valve | |
| valve may be blocked. | with built in bypass. | |
|
|
| |
| Check valve or | Remove check valve or | |
| valve installed in the feed line. | to allow for water expansion or install a | |
|
| back pressure relief valve on the incoming | |
|
| water line, Hatco part number | |
|
| 03.02.039.00. | |
|
|
| |
Relief valve opens. | Unit is overheating. | Thermostat may be set too high | |
|
| or is sticking. Recalibrate (page 27) | |
|
| or replace the thermostat. | |
|
|
| |
| Contactor may be sticking in | Replace contactor(s). | |
| closed position not allowing |
| |
| unit to cycle off. |
| |
|
|
|
Form No. | 32 |