Goodman Mfg CVC9/95, MVC95 Horizontal Applications & Considerations, HorizontalFurnace

Page 11

HORIZONTAL APPLICATIONS & CONSIDERATIONS

HORIZONTAL APPLICATIONS & CONSIDERATIONS

When using the horizontal alternate vent configuration, you must

 

use the RF000142 vent drain kit. See following illustration.

Horizontal applications, in particular, may dictate many of the installation’s specifics such as airflow direction, ductwork connec- tions, flue and combustion air pipe connections, etc. The basic application of this furnace as a horizontal furnace differs only slightly from an upright installation. When installing a furnace horizontally, additional consideration must be given to the following:

 

FURNACE MUST BE LEVEL

ALTERNATE VENT/FLUE

FROM END TO END

FURNACE MUST BE LEVEL

AND COMBUSTION AIR

INTAKE LOCATIONS

OR SLIGHTLY TILTED FORWARD

 

WITH THE DOORS 0" - 3/4"

 

BELOW THE BACK PANEL

“FIELD-SUPPLIED DRAIN HOSE” FROM VENT-

DRAIN CONNECTED TO

CONDENSATE DRAIN LINE WITH “FIELD- SUPPLIED CONNECTOR”

NOTE: MAKE SMALL LOOP IN HOSE TO SERVE AS “P-TRAP”

VENT-DRAIN

 

4 3/4" MINIMUM

 

DRAIN TRAP

GAS LINE WITH

CLEARANCE

DRIP LEG (3" MINIMUM)

 

DRAIN PAN

DRAIN LINE WITH 1/4" PER FOOT

DOWNWARD SLOPE

 

FURNACE MUST BE SUPPORTED

36" MINIMUM SERVICE

AT BOTH ENDS AND MIDDLE

CLEARANCE REQUIRED

HorizontalFurnace

DRAINTRAPANDLINES

In horizontal applications the condensate drain trap is secured to the furnace side panel, suspending it below the furnace. A mini- mum clearance of 4 3/4 inches below the furnace must be pro- vided for the drain trap. Additionally, the appropriate downward piping slope must be maintained from the drain trap to the drain location. Refer to Condensate Drain Trap and Lines for further de- tails. If the drain trap and drain line will be exposed to temperatures near or below freezing, adequate measures must be taken to pre- vent condensate from freezing.

LEVELING

Leveling ensures proper condensate drainage from the heat ex- changer and induced draft blower. For proper flue pipe drainage, the furnace must be level lengthwise from end to end. The furnace should also be level from back to front or have a slight tilt with the access doors downhill (approximately 3/4 inches) from the back panel. The slight tilt allows the heat exchanger condensate, gen- erated in the recuperator coil, to flow forward to the recuperator coil front cover.

ALTERNATEVENT/FLUEANDCOMBUSTIONAIRCONNECTIONS

In horizontal installations provisions for alternate flue and combus- tion air piping are available for upflow furnaces with left discharge and counterflow furnaces with right air discharge. This configura- tion allows the flue and combustion air piping to be run vertically through the side of the furnace. Refer to the “Recommended In- stallation Positions” figure for further detail. The standard piping connections may also be used in these positions. Refer to Vent/ Flue Pipe and Combustion Air Pipe for details concerning the conversion to the alternate vent/flue and combustion air connec- tions.

AlternateVent/FlueLocation

RecommendedInstallationPositions

NOTE: Alternate “vertical” piping connections can not be used when an upflow furnace is installed with supply air discharging to the right, or when a counterflow furnace is installed with supply air discharging to the left. In either case, use the standard flue and combustion air piping connections.

11

Image 11
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting What to do if YOU Smell GAS Safety PrecautionsShippinginspection ElectrostaticdischargeesdprecautionsTotheinstaller Product Description & ApplicationProductapplication FeaturesProduct Description Location Requirements & Considerations Existingfurnaceremoval ClearancesandaccessibilityFurnacesuspension Thermostatlocation Installation PositionsCombustion & Ventilation AIR Requirements HorizontalFurnace AlternateVent/FlueLocation RecommendedInstallationPositionsHorizontal Applications & Considerations VENT/FLUE Pipe & Combustion AIR Pipe Propane GAS/HIGH Altitude InstallationsTerminationlocations MaterialsandjoiningmethodsPROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES Standardfurnaceconnections Increased Clearance ConfigurationVent Termination Clearances CanadianventingrequirementsAlternatefurnaceconnections Vent/FluePipeCutsRemove Pipe Relocate NON-DIRECTVENTSINGLEPIPEPIPING UpflowDirectventdualpipepiping Vertical Termination Single PipeAlternate Vertical Termination Single Pipe HorizontalTerminationSinglePipeStandard Horizontal Terminations Dual Pipe Vertical Terminations Dual PipeSide Wall Vent KIT Alternate Horizontal Vent Termination Dual PipeHorizontalVentingOfMultipleUnits ConcentricventterminationStandardrightorleftsidedrainhoseconnections Condensate Drain Lines & Drain TrapHose and Tube Identification Drain Trap Mounting UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDEExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Counterflow furnaces HorizontalinstallationsCut 115VOLT Line Connections WiringharnessElectrical Connections Junctionbox RelocationSINGLE-STAGE Heatingthermostatapplication Thermostat Wiring Diagrams24VOLTTHERMOSTATWIRING Fossilfuelapplications Accessory load specifications are as followsHighaltitudederate Accessories WiringGAS Supply and Piping 24VOLTHUMIDIFIERNatural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFH GaspipingconnectionsGas Piping Connections Horizontal Upflow ModelPropanegastanksandpiping PropaneGasInstallationTypCoupling Degree elbow Inch close nipple Checking Duct Static Propane Gas Piping ChartCirculating AIR & Filters Duct Work -AIR FlowBottomreturnairopeningupflowmodels Consult proper tables for the quantity of airChecking Static Pressure 80% Furnace Shown, 90% Similar DuctFlangeCutOutsFollowing figure shows possible filter locations Startup Procedure & AdjustmentStartup Procedure &ADJUSTMENT White-Rodgers Model 36G54 Two-Stage TemperatureSet the thermostat to the lowest setting If you smell gas after five minutes, immediately followMeasuring Inlet Gas Pressure Alt. Method GasmanifoldpressuremeasurementandadjustmentTurn on the gas supply Honeywell Model VR9205 Connected to ManometerGasinputratemeasurementnaturalgasonly TemperatureriseCirculatorblowerspeeds Temperature Rise MeasurementAirflowTable Overview Heat Off Delay DipswitchesBlowerheat Offdelay Timings Comfortnet SystemSystem System Operating System Wiring using Four-WiresValue. Touch Touch To step through the list of installed equipComfortnetsystemadvancedfeatures Pear. UseConfiguration Is 30 seconds Non-CT compatible single stage AC unit NetworktroubleshootingHeatingmode SystemtroubleshootingPower UP Normal Sequence of OperationFanonlymode Operational Checks & Safety Circuit DescriptionCoolingmode Troubleshooting Troubleshooting & Maintenance Operational ChecksSafety Circuit Description Follow the manufacturer’s directions for service Troubleshooting & MaintenanceMaintenance Miscellaneous Before Leaving AN InstallationRepair and Replacement Parts Induced Draft Blower Transformer Door SwitchBank DIP SwitchesInternal Troubleshooting ChartLimit Message ChartInvalid Trips Status Codes CVC9AA, *MVC95AA Wiring DiagramCVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.