Goodman Mfg MVC95, CVC9/95 Turn on the gas supply, Honeywell Model VR9205 Connected to Manometer

Page 38

STARTUP PROCEDURE & ADJUSTMENT

Honeywell Model VR9205 (Two-Stage)

Gas Line

Open to

Manometer

Atmosphere

Hose

i

Manometer

Common

Gas

Terminal(C)

High Fire Coil

Shutoff

Valve

Terminal (HI)

 

Low Fire Coil

 

Terminal (LO)

Gas Line

 

 

To Furnace

Inlet Pressure Tap

Open To

Atmosphere

1/8 NPT

Drip Leg Cap

 

 

With Fitting

 

Manometer Hose

Outlet Pressure Tap 1/8 NPT

Honeywell Model VR9205 Connected to Manometer

1.Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.

2.Connect a calibrated water manometer (or appropriate gas pressure gauge) at either the gas valve inlet pressure boss or the gas piping drip leg. See Honeywell VR9205 gas valve figure or White-Rodgers 36G54 gas valve figure for location of inlet pressure boss.

NOTE: If measuring gas pressure at the drip leg or Honeywell VR9205gasvalve,afield-suppliedhosebarbfittingmustbeinstalled prior to making the hose connection. If using the inlet pressure boss on the White-Rodgers 36G54 gas valve, then use the 36G Valve Pressure Check Kit, Goodman Part No. 0151K00000S.

3.Turn ON the gas supply and operate the furnace and all other gas consuming appliances on the same gas supply line.

4.Measure furnace gas supply pressure with burners firing. Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table.

Inlet Gas Supply Pressure

Natural Gas

Minimum: 5.0" w.c.

Maximum:10.0" w.c.

Propane Gas

Minimum: 11.0" w.c.

Maximum:13.0" w.c.

If supply pressure differs from table, make the necessary adjust- ments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.

5.Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer. Reinstall plug before turning on gas to furnace.

6.Turn OFF any unnecessary gas appliances stated in step 3.

Manometer

Measuring Inlet Gas Pressure (Alt. Method)

GASMANIFOLDPRESSUREMEASUREMENTANDADJUSTMENT

CAUTION

TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE. ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR.

Only small variations in gas pressure should be made by adjusting the gas valve pressure regulator. The manifold pressure must be measured with the burners operating. To measure and adjust the manifold pressure, use the following procedure.

1.Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.

2.Turn off all electrical power to the system.

3.Outlet pressure tap connections:

a.Honeywell VR9205 valve: Remove the outlet pressure boss plug. Install an 1/8" NPT hose barb fitting into the outlet pressure tap.

b.White-Rodgers 36G54 valve: Back outlet pressure test screw (inlet/outlet pressure boss) out one turn (counterclockwise, not more than one turn).

4.Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or outlet pressure boss (White- Rodgersvalve).

5.Turn ON the gas supply.

6.Turn on power and close thermostat “R” and “W1” contacts to provide a call for low stage heat.

7.Measure the gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table shown below.

8.Remove regulator cover screw from the low (LO) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw.

38

Image 38
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting Safety Precautions What to do if YOU Smell GASProduct Description & Application ElectrostaticdischargeesdprecautionsTotheinstaller ShippinginspectionProductapplication FeaturesProduct Description Location Requirements & Considerations Existingfurnaceremoval ClearancesandaccessibilityFurnacesuspension Thermostatlocation Installation PositionsCombustion & Ventilation AIR Requirements HorizontalFurnace AlternateVent/FlueLocation RecommendedInstallationPositionsHorizontal Applications & Considerations Propane GAS/HIGH Altitude Installations VENT/FLUE Pipe & Combustion AIR PipeTerminationlocations MaterialsandjoiningmethodsPROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES Canadianventingrequirements Increased Clearance ConfigurationVent Termination Clearances StandardfurnaceconnectionsVent/FluePipeCuts AlternatefurnaceconnectionsRemove Pipe Relocate Upflow NON-DIRECTVENTSINGLEPIPEPIPINGHorizontalTerminationSinglePipe Vertical Termination Single PipeAlternate Vertical Termination Single Pipe DirectventdualpipepipingVertical Terminations Dual Pipe Standard Horizontal Terminations Dual PipeConcentricventtermination Alternate Horizontal Vent Termination Dual PipeHorizontalVentingOfMultipleUnits Side Wall Vent KITStandardrightorleftsidedrainhoseconnections Condensate Drain Lines & Drain TrapHose and Tube Identification UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDE Drain Trap MountingExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Horizontalinstallations Counterflow furnacesCut Junctionbox Relocation WiringharnessElectrical Connections 115VOLT Line ConnectionsSINGLE-STAGE Heatingthermostatapplication Thermostat Wiring Diagrams24VOLTTHERMOSTATWIRING Accessory load specifications are as follows Fossilfuelapplications24VOLTHUMIDIFIER Accessories WiringGAS Supply and Piping HighaltitudederateGaspipingconnections Natural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFHHorizontal Upflow Model Gas Piping ConnectionsPropanegastanksandpiping PropaneGasInstallationTypCoupling Degree elbow Inch close nipple Duct Work -AIR Flow Propane Gas Piping ChartCirculating AIR & Filters Checking Duct StaticDuctFlangeCutOuts Consult proper tables for the quantity of airChecking Static Pressure 80% Furnace Shown, 90% Similar BottomreturnairopeningupflowmodelsFollowing figure shows possible filter locations Startup Procedure & AdjustmentStartup Procedure &ADJUSTMENT If you smell gas after five minutes, immediately follow TemperatureSet the thermostat to the lowest setting White-Rodgers Model 36G54 Two-StageHoneywell Model VR9205 Connected to Manometer GasmanifoldpressuremeasurementandadjustmentTurn on the gas supply Measuring Inlet Gas Pressure Alt. MethodTemperaturerise GasinputratemeasurementnaturalgasonlyTemperature Rise Measurement CirculatorblowerspeedsAirflowTable Comfortnet System Heat Off Delay DipswitchesBlowerheat Offdelay Timings OverviewSystem Wiring using Four-Wires System System OperatingPear. Use Touch To step through the list of installed equipComfortnetsystemadvancedfeatures Value. TouchConfiguration Networktroubleshooting Is 30 seconds Non-CT compatible single stage AC unitNormal Sequence of Operation SystemtroubleshootingPower UP HeatingmodeFanonlymode Operational Checks & Safety Circuit DescriptionCoolingmode Troubleshooting Troubleshooting & Maintenance Operational ChecksSafety Circuit Description Follow the manufacturer’s directions for service Troubleshooting & MaintenanceMaintenance Induced Draft Blower Transformer Door Switch Before Leaving AN InstallationRepair and Replacement Parts MiscellaneousDIP Switches BankTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes Wiring Diagram CVC9AA, *MVC95AACVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.