Goodman Mfg MVC95, CVC9/95 installation instructions Remove Pipe Relocate

Page 16

VENT/FLUE PIPE & COMBUSTION AIR PIPE

8.Upflow and Counterflow units.

For horizontal installations, externally secure the field- supplied vent/flue pipe directly to the vent/flue coupling using a PVC or ABS coupling or elbow.

ALTERNATECOMBUSTIONAIRINTAKELOCATION

The alternate combustion air intake location consists of a large, unobstructed hole (alternate vent connection is aligned with the Induced Draft Blower). To use the alternate combustion air intake location, refer to the following steps, and the “Alternate Combus- tionAir Intake Location” figure.

1.Remove and save the four screws securing the combustion air intake coupling to the basepan. Remove an additional three screws securing the furnace’s internal combustion air intake pipe to the blower deck.

2.Remove the combustion air intake pipe from the furnace and cut the pipe at the basepan coupling. Save the basepan coupling and gasket from the blower deck coupling for use in the alternate location. Discard the remaining pipe.

3.Remove plastic plug from alternate combustion air intake location. Relocate and install plug in standard air intake location (basepan). Plug the remaining hole in the blower deck with the plastic plug included in the drain kit bag.

4.With the gasket facing the cabinet side panel, and the flange’s flat spot facing forward, secure the combustion air intake coupling to the cabinet using the screws removed in step 1 or with field-supplied 3/8” #8 self -drilling screws.

CAUTION

BE SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS WHEN REINSTALLING COUPLING AND SCREWS.

5.For non-direct vent installations installed horizontally, a minimum of one 90° elbow should be installed on the combustion air intake coupling to guard against inadvertent blockage. No elbow is required on the alternate combustion air intake of upright installations, however, a minimum clearance of 2 inches is required to assure proper air supply.

6.For direct vent installations, secure field-supplied combustion air intake pipe directly to the air intake coupling. NOTE: APVC coupling or elbow is required on counterflow units.

3

 

REMOVE

 

PIPE

 

5

 

REMOVE

 

AND RELOCATE

 

2

 

DETACH RUBBER

 

ELBOW FROM

 

ID BLOWER AND

 

VENT/FLUE

 

PIPE

 

5

 

ADDITIONAL PLUG

6

FROM DRAIN KIT

SECURE TO

 

ID BLOWER WITH

 

RUBBER COUPLING

7

AND HOSE

EXTERNALLY

CLAMPS

MOUNT

 

RUBBER ELBOW

 

6

 

SECURE TO

 

ID BLOWER WITH

 

RUBBER COUPLING

 

AND HOSE

 

CLAMPS

 

3

REMOVE

PIPE

1

REMOVE

3 SCREWS

5

REMOVE

AND RELOCATE

2

DETATCH RUBBER

ELBOW FROM ID BLOWER AND VENT/FLUE PIPE

6

SECURE TO

CABINET WITH

SCREWS

16

Image 16
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting Safety Precautions What to do if YOU Smell GASElectrostaticdischargeesdprecautions TotheinstallerProduct Description & Application ShippinginspectionProduct Description FeaturesProductapplication Location Requirements & Considerations Furnacesuspension ClearancesandaccessibilityExistingfurnaceremoval Combustion & Ventilation AIR Requirements Installation PositionsThermostatlocation Horizontal Applications & Considerations AlternateVent/FlueLocation RecommendedInstallationPositionsHorizontalFurnace Propane GAS/HIGH Altitude Installations VENT/FLUE Pipe & Combustion AIR PipePROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES MaterialsandjoiningmethodsTerminationlocations Increased Clearance Configuration Vent Termination ClearancesCanadianventingrequirements StandardfurnaceconnectionsVent/FluePipeCuts AlternatefurnaceconnectionsRemove Pipe Relocate Upflow NON-DIRECTVENTSINGLEPIPEPIPINGVertical Termination Single Pipe Alternate Vertical Termination Single PipeHorizontalTerminationSinglePipe DirectventdualpipepipingVertical Terminations Dual Pipe Standard Horizontal Terminations Dual PipeAlternate Horizontal Vent Termination Dual Pipe HorizontalVentingOfMultipleUnitsConcentricventtermination Side Wall Vent KITHose and Tube Identification Condensate Drain Lines & Drain TrapStandardrightorleftsidedrainhoseconnections UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDE Drain Trap MountingExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Horizontalinstallations Counterflow furnacesCut Wiringharness Electrical ConnectionsJunctionbox Relocation 115VOLT Line Connections24VOLTTHERMOSTATWIRING Thermostat Wiring DiagramsSINGLE-STAGE Heatingthermostatapplication Accessory load specifications are as follows FossilfuelapplicationsAccessories Wiring GAS Supply and Piping24VOLTHUMIDIFIER HighaltitudederateGaspipingconnections Natural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFHHorizontal Upflow Model Gas Piping ConnectionsCoupling Degree elbow Inch close nipple PropaneGasInstallationTypPropanegastanksandpiping Propane Gas Piping Chart Circulating AIR & FiltersDuct Work -AIR Flow Checking Duct StaticConsult proper tables for the quantity of air Checking Static Pressure 80% Furnace Shown, 90% SimilarDuctFlangeCutOuts BottomreturnairopeningupflowmodelsStartup Procedure &ADJUSTMENT Startup Procedure & AdjustmentFollowing figure shows possible filter locations Temperature Set the thermostat to the lowest settingIf you smell gas after five minutes, immediately follow White-Rodgers Model 36G54 Two-StageGasmanifoldpressuremeasurementandadjustment Turn on the gas supplyHoneywell Model VR9205 Connected to Manometer Measuring Inlet Gas Pressure Alt. MethodTemperaturerise GasinputratemeasurementnaturalgasonlyTemperature Rise Measurement CirculatorblowerspeedsAirflowTable Heat Off Delay Dipswitches Blowerheat Offdelay TimingsComfortnet System OverviewSystem Wiring using Four-Wires System System OperatingTouch To step through the list of installed equip ComfortnetsystemadvancedfeaturesPear. Use Value. TouchConfiguration Networktroubleshooting Is 30 seconds Non-CT compatible single stage AC unitSystemtroubleshooting Power UPNormal Sequence of Operation HeatingmodeCoolingmode Operational Checks & Safety Circuit DescriptionFanonlymode Safety Circuit Description Troubleshooting & Maintenance Operational ChecksTroubleshooting Maintenance Troubleshooting & MaintenanceFollow the manufacturer’s directions for service Before Leaving AN Installation Repair and Replacement PartsInduced Draft Blower Transformer Door Switch MiscellaneousDIP Switches BankTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes Wiring Diagram CVC9AA, *MVC95AACVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.