ELECTRICAL CONNECTIONS

To use a single-stage thermostat, turn off power to the furnace, move the thermostat selection DIP switch to the OFF position. Set the desired transition time by setting the transition delay DIP switch to the desired ON/OFF position. Turn power back on. Refer to the following figure.

temperature sensor to determine the most cost efficient means of heating (heat pump or gas furnace).

A heat pump thermostat with three stages of heat is required to properly use a two-stage furnace in conjunction with a heat pump. Refer to the fossil fuel kit installation instructions for additional

Heat OFF Delay DIP Switches

OFF

 

ON

3

 

 

 

 

 

 

Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

Stage Delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S1

 

Move to the ON position to select two-stage thermostat or OFF to select single stage thermostat

Move to the ON position to select Auto transition delay or OFF for 5 minute transition delay

thermostat requirements.

Strictly follow the wiring guidelines in the fossil fuel kit installation instructions. All furnace connections must be made to the furnace two-stage integrated control module and the “FURNACE” terminal strip on the fossil fuel control board.

115VOLTLINECONNECTIONOFACCESSORIES (HUMIDIFIERAND ELECTRONICAIRCLEANER)

24VOLTDEHUMIDISTATWIRING

The optional usage of a dehumidistat allows the furnace’s circula- tor blower to operate at a slightly lower speed (85% of desired speed) during a combined thermostat call for cooling and dehumi- distat call for dehumidification. This can be done through an inde- pendent dehumidistat or through a thermostat’s DEHUM terminal (if available). This lower blower speed enhances dehumidification of the conditioned air as it passes through theAC coil. For proper function, a dehumidistat applied to this furnace must operate on 24 VAC and utilize a switch which opens on humidity rise. Refer to the “Thermostat Wiring Diagrams” figure for additional wir- ing details.

To install/connect a dehumidistat:

1.Turn OFF power to furnace.

2.Secure the dehumidistat neutral wire (typically the white lead) to the terminal marked “DEHUM” on the furnace integrated control module.

3.Secure the dehumidistat hot wire (typically the black lead) to the terminal marked “R” on the furnace integrated control module.

4.Secure the dehumidistat ground wire (typically the green lead) to the ground screw on the furnace junction box. NOTE: Ground wire may not be present on all dehumidistats.

5.Turn ON power to furnace.

To enable the dehumidify function on the integrated control mod- ule, set the dehumidification ENABLE dipswitch from OFF to ON.

Once the switch is set, the dehumidify function is enabled during a combination call for cooling (T-Stat) and dehumidification (DEHUM- Stat).

 

OFF ON

 

9

 

 

 

 

 

 

DEHUM

Move to the ON position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

Unused

to enable dehumidification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S5

FOSSILFUELAPPLICATIONS

This furnace can be used in conjunction with a heat pump in a fossil fuel application. Afossil fuel application refers to a combined gas furnace and heat pump installation which uses an outdoor

WARNING

HIGH VOLTAGE !

TO AVOID PERSONAL INJURY OR DEATH DUE TO

ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER

BEFORE SERVICING OR CHANGING ANY ELECTRICAL

WIRING.

The furnace integrated control module is equipped with line voltage accessory terminals for controlling power to an optional field-sup- plied humidifier and/or electronic air cleaner.

The accessory load specifications are as follows:

Humidifier

1.0 Amp maximum at 120 VAC

Electronic Air Cleaner

1.0 Amp maximum at 120 VAC

Turn OFF power to the furnace before installing any accessories. Follow the humidifier or air cleaner manufacturers’ instructions for locating, mounting, grounding, and controlling these accessories. Accessory wiring connections are to be made through the 1/4" quick connect terminals provided on the furnace integrated control module. The humidifier and electronic air cleaner hot terminals are identified as HUM and EAC. The humidifier and electronic air cleaner neutral terminals are identified as NEUTRAL.All field wir- ing must conform to applicable codes. Connections should be made as shown.

29

Image 29
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting What to do if YOU Smell GAS Safety PrecautionsTotheinstaller ElectrostaticdischargeesdprecautionsProduct Description & Application ShippinginspectionProductapplication FeaturesProduct Description Location Requirements & Considerations Existingfurnaceremoval ClearancesandaccessibilityFurnacesuspension Thermostatlocation Installation PositionsCombustion & Ventilation AIR Requirements HorizontalFurnace AlternateVent/FlueLocation RecommendedInstallationPositionsHorizontal Applications & Considerations VENT/FLUE Pipe & Combustion AIR Pipe Propane GAS/HIGH Altitude InstallationsTerminationlocations MaterialsandjoiningmethodsPROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES Vent Termination Clearances Increased Clearance ConfigurationCanadianventingrequirements StandardfurnaceconnectionsAlternatefurnaceconnections Vent/FluePipeCutsRemove Pipe Relocate NON-DIRECTVENTSINGLEPIPEPIPING UpflowAlternate Vertical Termination Single Pipe Vertical Termination Single PipeHorizontalTerminationSinglePipe DirectventdualpipepipingStandard Horizontal Terminations Dual Pipe Vertical Terminations Dual PipeHorizontalVentingOfMultipleUnits Alternate Horizontal Vent Termination Dual PipeConcentricventtermination Side Wall Vent KITStandardrightorleftsidedrainhoseconnections Condensate Drain Lines & Drain TrapHose and Tube Identification Drain Trap Mounting UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDEExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Counterflow furnaces HorizontalinstallationsCut Electrical Connections WiringharnessJunctionbox Relocation 115VOLT Line ConnectionsSINGLE-STAGE Heatingthermostatapplication Thermostat Wiring Diagrams24VOLTTHERMOSTATWIRING Fossilfuelapplications Accessory load specifications are as followsGAS Supply and Piping Accessories Wiring24VOLTHUMIDIFIER HighaltitudederateNatural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFH GaspipingconnectionsGas Piping Connections Horizontal Upflow ModelPropanegastanksandpiping PropaneGasInstallationTypCoupling Degree elbow Inch close nipple Circulating AIR & Filters Propane Gas Piping ChartDuct Work -AIR Flow Checking Duct StaticChecking Static Pressure 80% Furnace Shown, 90% Similar Consult proper tables for the quantity of airDuctFlangeCutOuts BottomreturnairopeningupflowmodelsFollowing figure shows possible filter locations Startup Procedure & AdjustmentStartup Procedure &ADJUSTMENT Set the thermostat to the lowest setting TemperatureIf you smell gas after five minutes, immediately follow White-Rodgers Model 36G54 Two-StageTurn on the gas supply GasmanifoldpressuremeasurementandadjustmentHoneywell Model VR9205 Connected to Manometer Measuring Inlet Gas Pressure Alt. MethodGasinputratemeasurementnaturalgasonly TemperatureriseCirculatorblowerspeeds Temperature Rise MeasurementAirflowTable Blowerheat Offdelay Timings Heat Off Delay DipswitchesComfortnet System OverviewSystem System Operating System Wiring using Four-WiresComfortnetsystemadvancedfeatures Touch To step through the list of installed equipPear. Use Value. TouchConfiguration Is 30 seconds Non-CT compatible single stage AC unit NetworktroubleshootingPower UP SystemtroubleshootingNormal Sequence of Operation HeatingmodeFanonlymode Operational Checks & Safety Circuit DescriptionCoolingmode Troubleshooting Troubleshooting & Maintenance Operational ChecksSafety Circuit Description Follow the manufacturer’s directions for service Troubleshooting & MaintenanceMaintenance Repair and Replacement Parts Before Leaving AN InstallationInduced Draft Blower Transformer Door Switch MiscellaneousBank DIP SwitchesInternal Troubleshooting ChartLimit Message ChartInvalid Trips Status Codes CVC9AA, *MVC95AA Wiring DiagramCVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.