Goodman Mfg CVC9/95, MVC95 Clearancesandaccessibility, Furnacesuspension, Existingfurnaceremoval

Page 9

LOCATION REQUIREMENTS & CONSIDERATIONS

If the furnace is used in connection with a cooling coil unit, install the furnace upstream or in parallel with the cooling coil unit. Premature heat exchanger failure will result if the cooling unit is placed ahead of the furnace.

If the furnace is installed in a residential garage, position the furnace so that the burners and ignition source are located not less than 18 inches (457 mm) above the floor. Protect the furnace from physical damage by vehicles.

If the furnace is installed horizontally, ensure the access doors are not on the “up/top” or “down/bottom” side of the furnace.

Do not connect this furnace to a chimney flue that serves a separate appliance designed to burn solid fuel.

On Counterflow Installations, the air conditioning coil must bedownstreamonthesupply(positive)sideofthefurnace heat exchanger.

Counterflow Installation over a noncombustible floor. Beforesettingthefurnaceovertheplenumopening,ensure the surface around the opening is smooth and level. A tight seal should be made between the furnace base and floor by using a silicone rubber caulking compound or cement grout.

Counterflow Installation over a combustible floor. If installation over a combustible floor becomes necessary, use an accessory subbase (see Specification Sheet applicable for your model for details.) Aspecial accessory subbase must be used for upright counterflow unit installationsoveranycombustiblematerialincludingwood. Refertosubbaseinstructionsforinstallationdetails.Follow the instructions with the subbase for proper installation. Do not install the furnace directly on carpeting, tile, or other combustible material other than wood flooring. (NOTE: The subbase will not be required if an air conditioning coil is installed between the supply air opening on the furnace and the floor.)

CLEARANCESANDACCESSIBILITY

Installations must adhere to the clearances to combustible mate- rials to which this furnace has been design certified. The minimum clearance information for this furnace is provided on the unit’s clear- ance label. These clearances must be permanently maintained. Clearances must also accommodate an installation’s gas, electri- cal, and drain trap and drain line connections. If the alternate combustion air intake or vent/flue connections are used additional clearance must be provided to accommodate these connections. Refer to Vent/FluePipeandCombustionAirPipe for details. NOTE: In addition to the required clearances to combustible materials, a minimum of 24 inches service clearance must be available in front of the unit.

T O P

 

 

 

 

 

T O P

S ID E

S ID E

 

S ID E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B O T T O M

 

 

B O T TO M

 

 

 

U pflow

 

C ou nte rflo w

H orizon tal

Afurnace installed in a confined space (i.e., a closet or utility room) must have two ventilation openings with a total minimum free area of 0.25 square inches per 1,000 BTU/hr of furnace input rating. Refer to Specification Sheet applicable to your model for minimum clearances to combustible surfaces. One of the ventila- tion openings must be within 12 inches of the top; the other open- ing must be within 12 inches of the bottom of the confined space. In a typical construction, the clearance between the door and door frame is usually adequate to satisfy this ventilation requirement.

FURNACESUSPENSION

If suspending the furnace from rafters or joists, use 3/8" threaded rod and 2”x2”x1/8” angle iron as shown in the following diagram. The length of rod will depend on the application and the clearances necessary.

2"X2"X3/8" ANGLE IRON

(3 PLACES)

EXISTINGFURNACEREMOVAL

NOTE: When an existing furnace is removed from a venting sys- tem serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.

The following vent testing procedure is reproduced from theAmerican

NationalStandard/NationalStandardofCanadaforGas-FiredCentral FurnacesANSI Z21.4, CSA-2.3 latest edition Section 1.23.1.

The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:

1. Seal any unused openings in the venting system;

9

Image 9
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting What to do if YOU Smell GAS Safety PrecautionsTotheinstaller ElectrostaticdischargeesdprecautionsProduct Description & Application ShippinginspectionFeatures Product DescriptionProductapplication Location Requirements & Considerations Clearancesandaccessibility FurnacesuspensionExistingfurnaceremoval Installation Positions Combustion & Ventilation AIR RequirementsThermostatlocation AlternateVent/FlueLocation RecommendedInstallationPositions Horizontal Applications & ConsiderationsHorizontalFurnace VENT/FLUE Pipe & Combustion AIR Pipe Propane GAS/HIGH Altitude InstallationsMaterialsandjoiningmethods PROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICESTerminationlocations Vent Termination Clearances Increased Clearance ConfigurationCanadianventingrequirements StandardfurnaceconnectionsAlternatefurnaceconnections Vent/FluePipeCutsRemove Pipe Relocate NON-DIRECTVENTSINGLEPIPEPIPING UpflowAlternate Vertical Termination Single Pipe Vertical Termination Single PipeHorizontalTerminationSinglePipe DirectventdualpipepipingStandard Horizontal Terminations Dual Pipe Vertical Terminations Dual PipeHorizontalVentingOfMultipleUnits Alternate Horizontal Vent Termination Dual PipeConcentricventtermination Side Wall Vent KITCondensate Drain Lines & Drain Trap Hose and Tube IdentificationStandardrightorleftsidedrainhoseconnections Drain Trap Mounting UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDEExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Counterflow furnaces HorizontalinstallationsCut Electrical Connections WiringharnessJunctionbox Relocation 115VOLT Line ConnectionsThermostat Wiring Diagrams 24VOLTTHERMOSTATWIRINGSINGLE-STAGE Heatingthermostatapplication Fossilfuelapplications Accessory load specifications are as followsGAS Supply and Piping Accessories Wiring24VOLTHUMIDIFIER HighaltitudederateNatural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFH GaspipingconnectionsGas Piping Connections Horizontal Upflow ModelPropaneGasInstallationTyp Coupling Degree elbow Inch close nipplePropanegastanksandpiping Circulating AIR & Filters Propane Gas Piping ChartDuct Work -AIR Flow Checking Duct StaticChecking Static Pressure 80% Furnace Shown, 90% Similar Consult proper tables for the quantity of airDuctFlangeCutOuts BottomreturnairopeningupflowmodelsStartup Procedure & Adjustment Startup Procedure &ADJUSTMENTFollowing figure shows possible filter locations Set the thermostat to the lowest setting TemperatureIf you smell gas after five minutes, immediately follow White-Rodgers Model 36G54 Two-StageTurn on the gas supply GasmanifoldpressuremeasurementandadjustmentHoneywell Model VR9205 Connected to Manometer Measuring Inlet Gas Pressure Alt. MethodGasinputratemeasurementnaturalgasonly TemperatureriseCirculatorblowerspeeds Temperature Rise MeasurementAirflowTable Blowerheat Offdelay Timings Heat Off Delay DipswitchesComfortnet System OverviewSystem System Operating System Wiring using Four-WiresComfortnetsystemadvancedfeatures Touch To step through the list of installed equipPear. Use Value. TouchConfiguration Is 30 seconds Non-CT compatible single stage AC unit NetworktroubleshootingPower UP SystemtroubleshootingNormal Sequence of Operation HeatingmodeOperational Checks & Safety Circuit Description CoolingmodeFanonlymode Troubleshooting & Maintenance Operational Checks Safety Circuit DescriptionTroubleshooting Troubleshooting & Maintenance MaintenanceFollow the manufacturer’s directions for service Repair and Replacement Parts Before Leaving AN InstallationInduced Draft Blower Transformer Door Switch MiscellaneousBank DIP SwitchesInternal Troubleshooting ChartLimit Message ChartInvalid Trips Status Codes CVC9AA, *MVC95AA Wiring DiagramCVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.