Goodman Mfg CVC9/95, MVC95 installation instructions Gaspipingconnections

Page 31

GAS SUPPLY AND PIPING

Contact your distributor for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude installa- tions. The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a quali- fied installer, or service agency.

GAS VALVE

This unit is equipped with a 24 volt gas valve controlled during furnace operation by the integrated control module. As shipped, the valve is configured for natural gas. The valve is field convertible for use with propane gas by replacing the regulator spring with a propane gas spring from an appropriate manufacturer’s propane gas conversion kit. Taps for measuring the gas supply pressure and manifold pressure are provided on the valve.

The gas valve has a manual ON/OFF control located on the valve itself. This control may be set only to the “ON” or “OFF” position. Refer to the lighting instructions label or Startup Procedure & Adjustment for use of this control during start up and shut down periods.

GASPIPINGCONNECTIONS

WARNING

TO AVOID POSSIBLE UNSATISFACTORY OPERATION OF EQUIPMENT DAMAGE DUE TO UNDERFIRING OR EQUIPMENT, USE THE PROPER SIZE OF NATURAL/PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE METER/TANK TO THE FURNACE.

When sizing a trunk line, be sure to include all appliances which will operate simultaneously when sizing a trunk line.

The gas piping supplying the furnace must be properly sized based on the gas flow required, specific gravity of the gas, and length of the run. The gas line installation must comply with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, NFPA54/ANSI Z223.1.

Natural Gas Capacity of Pipe

In Cubic Feet of Gas Per Hour (CFH)

Length of

 

Nominal Black Pipe Size

 

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on 0.60 Specific Gravity Gas)

CFH = BTUH Furnace Input

Heating Value of Gas (BTU/Cubic Foot)

To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the

installer may also need to supply a transition piece from 1/2" pipe to a larger pipe size.

The following stipulations apply when connecting gas piping. Re- fer to Gas Piping Connections figure for typical gas line connec- tions to the furnace.

Use black iron or steel pipe and fittings for building piping. Where possible, use new pipe that is properly chamfered, reamed, and free of burrs and chips. If old pipe is used, be sure it is clean and free of rust, scale, burrs, chips, and old pipe joint compound.

Use pipe joint compound on male threads ONLY. Always use pipe joint compound (pipe dope) that is APPROVED FORALLGASSES. DO NOT apply compound to the first two threads.

Use ground joint unions.

Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.

Install a 1/8" NPT pipe plug fitting, accessible for test gage connection, immediately upstream of the gas supply connection to the furnace.

Always use a back-up wrench when making the connection to the gas valve to keep it from turning. The orientation of thegasvalveonthemanifoldmustbemaintainedasshipped from the factory. Maximum torque for the gas valve connection is 375 in-lbs; excessive over-tightening may damage the gas valve.

Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is installed, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace.

Tighten all joints securely.

Connect the furnace to the building piping by one of the following methods:

Rigid metallic pipe and fittings.

Semi-rigid metallic tubing and metallic fittings.

Aluminum alloy tubing must not be used in exterior locations. In order to seal the grommet cabinet penetration,rigidpipemustbeusedtoreachtheoutside of the cabinet. Asemi-rigid connector to the gas piping may be used from there.

Use listed gas appliance connectors in accordance with their instructions. Connectors must be fully in the same room as the furnace.

Protect connectors and semirigid tubing against physical and thermal damage when installed. Ensure aluminum- alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.

31

Image 31
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting What to do if YOU Smell GAS Safety PrecautionsShippinginspection ElectrostaticdischargeesdprecautionsTotheinstaller Product Description & ApplicationProduct Description FeaturesProductapplication Location Requirements & Considerations Furnacesuspension ClearancesandaccessibilityExistingfurnaceremoval Combustion & Ventilation AIR Requirements Installation PositionsThermostatlocation Horizontal Applications & Considerations AlternateVent/FlueLocation RecommendedInstallationPositionsHorizontalFurnace VENT/FLUE Pipe & Combustion AIR Pipe Propane GAS/HIGH Altitude InstallationsPROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES MaterialsandjoiningmethodsTerminationlocations Standardfurnaceconnections Increased Clearance ConfigurationVent Termination Clearances CanadianventingrequirementsAlternatefurnaceconnections Vent/FluePipeCutsRemove Pipe Relocate NON-DIRECTVENTSINGLEPIPEPIPING UpflowDirectventdualpipepiping Vertical Termination Single PipeAlternate Vertical Termination Single Pipe HorizontalTerminationSinglePipeStandard Horizontal Terminations Dual Pipe Vertical Terminations Dual PipeSide Wall Vent KIT Alternate Horizontal Vent Termination Dual PipeHorizontalVentingOfMultipleUnits ConcentricventterminationHose and Tube Identification Condensate Drain Lines & Drain TrapStandardrightorleftsidedrainhoseconnections Drain Trap Mounting UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDEExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Counterflow furnaces HorizontalinstallationsCut 115VOLT Line Connections WiringharnessElectrical Connections Junctionbox Relocation24VOLTTHERMOSTATWIRING Thermostat Wiring DiagramsSINGLE-STAGE Heatingthermostatapplication Fossilfuelapplications Accessory load specifications are as followsHighaltitudederate Accessories WiringGAS Supply and Piping 24VOLTHUMIDIFIERNatural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFH GaspipingconnectionsGas Piping Connections Horizontal Upflow ModelCoupling Degree elbow Inch close nipple PropaneGasInstallationTypPropanegastanksandpiping Checking Duct Static Propane Gas Piping ChartCirculating AIR & Filters Duct Work -AIR FlowBottomreturnairopeningupflowmodels Consult proper tables for the quantity of airChecking Static Pressure 80% Furnace Shown, 90% Similar DuctFlangeCutOutsStartup Procedure &ADJUSTMENT Startup Procedure & AdjustmentFollowing figure shows possible filter locations White-Rodgers Model 36G54 Two-Stage TemperatureSet the thermostat to the lowest setting If you smell gas after five minutes, immediately followMeasuring Inlet Gas Pressure Alt. Method GasmanifoldpressuremeasurementandadjustmentTurn on the gas supply Honeywell Model VR9205 Connected to ManometerGasinputratemeasurementnaturalgasonly TemperatureriseCirculatorblowerspeeds Temperature Rise MeasurementAirflowTable Overview Heat Off Delay DipswitchesBlowerheat Offdelay Timings Comfortnet SystemSystem System Operating System Wiring using Four-WiresValue. Touch Touch To step through the list of installed equipComfortnetsystemadvancedfeatures Pear. UseConfiguration Is 30 seconds Non-CT compatible single stage AC unit NetworktroubleshootingHeatingmode SystemtroubleshootingPower UP Normal Sequence of OperationCoolingmode Operational Checks & Safety Circuit DescriptionFanonlymode Safety Circuit Description Troubleshooting & Maintenance Operational ChecksTroubleshooting Maintenance Troubleshooting & MaintenanceFollow the manufacturer’s directions for service Miscellaneous Before Leaving AN InstallationRepair and Replacement Parts Induced Draft Blower Transformer Door SwitchBank DIP SwitchesInternal Troubleshooting ChartLimit Message ChartInvalid Trips Status Codes CVC9AA, *MVC95AA Wiring DiagramCVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.