Goodman Mfg MVC95, CVC9/95 Thermostat Wiring Diagrams, 24VOLTTHERMOSTATWIRING

Page 28

ELECTRICAL CONNECTIONS

1.Measure resistance between the neutral (white) connection and one of the burners.

2.Resistance should measure 10 ohms or less.

This furnace is equipped with a blower door interlock switch which interrupts unit voltage when the blower door is opened for servicing. Do not defeat this switch.

24VOLTTHERMOSTATWIRING

IMPORTANT NOTE

WIRE ROUTING MUST NOT INTERFERE WITH CIRCULATOR BLOWER OPERATION, FILTER REMOVAL OR ROUTINE MAINTENANCE.

A REMOVABLE PLUG CONNECTOR IS PROVIDED WITH THE CONTROL TO MAKE THERMOSTAT WIRE CONNECTIONS. THIS PLUG MAY BE REMOVED, WIRE CONNECTIONS MADE TO THE PLUG, AND REPLACED. IT IS STRONGLY RECOMMENDED THAT MULTIPLE WIRES INTO A SINGLE TERMINAL BE TWISTED TOGETHER PRIOR TO INSERTING INTO THE PLUG CONNECTOR. FAILURE TO DO SO MAY RESULT IN INTERMITTENT OPERATION.

As a two-stage non-communicating furnace, the furnace integrated control module provides terminals for both “W1” and “W2”, and “Y1” and “Y2” thermostat connections. This allows the furnace to support the following system applications: ‘Two-Stage Heating Only’, ‘Two-Stage Heating with Single Stage Cooling’, and ‘Two- Stage Heating with Two-Stage Cooling’. Refer to the following fig- ures for proper connections to the integrated control module.

Low voltage connections can be made through either the right or left side panel. Thermostat wiring entrance holes are located in the blower compartment. The following figure shows connections for a “heat/cool system”.

This furnace is equipped with a 40 VAtransformer to facilitate use with most cooling equipment. Consult the wiring diagram, located on the blower compartment door, for further details of 115 Volt and 24 Volt wiring.

NOTE: For single stage cooling applications, a jumper must be located between Y1 and Y2 at the furnace control in order to achieve the desired single stage cooling airflow. Use of ramping profiles and dehumidification features require a jumper between Y1 and O and Y1 and DEHUM, respectively.

NOTE: Thermostat “R” required if outdoor unit is equipped with a Comfort Alert™ module or if the out door unit is a part of the ComfortNet family of equipment AND is wired as a legacy system.

Thermostat

RSingle Stage Heating with

Single Stage Cooling

RFurnace Integrated

Control Module

NEU

Y C

Dehumidistat

Remote[Optional]

Condensing Unit

(Single-Stage Cooling)

Single Stage Heating with Single Stage Cooling

NOTE: To apply a single-stage Heating Thermostat,

the thermostat selector switch on the Integrated Control Module must be set on single-stage.

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two-Stage Heating

 

 

 

 

 

 

 

R

 

 

 

 

 

with

 

 

 

 

 

 

 

 

 

 

 

 

Single-Stage Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Furnace Integrated

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y C

 

 

NEU

Dehumidistat

 

 

 

 

 

 

 

 

 

 

 

Remote

 

 

 

 

 

[Optional]

 

 

 

 

 

 

 

 

 

 

 

Condensing Unit

 

 

 

 

 

 

 

 

(Single-Stage Cooling)

 

 

 

 

 

 

 

 

Two-Stage Heating with Single-Stage Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two-Stage Heating

 

Y2

W1

W2

(Two-StagewithCooling

)

 

 

 

 

 

 

 

 

 

 

 

 

 

Y2

W1

W2

Furnace Integrated

Control Module

 

Y2

NEU

Dehumidistat

 

Remote

[Optional]

 

Condensing Unit

 

(Two-Stage Cooling)

 

Two-Stage Heating with Two-Stage Cooling

Thermostat Wiring Diagrams

SINGLE-STAGE HEATINGTHERMOSTATAPPLICATION

A single-stage thermostat with only one heating stage may be used to control this furnace. The application of a single-stage thermostat offers a timed transition from low to high fire. The furnace will run on low stage for a fixed period of time before step- ping up to high stage to satisfy the thermostat’s call for heat. The delay period prior to stepping up can be set at either a fixed 5 minute time delay or a load based variable time between 1 and 12 minutes (AUTO mode). If theAUTO mode is selected, the control averages the cycle times of the previous three cycles and uses the average to determine the time to transition from low stage to high stage.

28

Image 28
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting Safety Precautions What to do if YOU Smell GASElectrostaticdischargeesdprecautions TotheinstallerProduct Description & Application ShippinginspectionProduct Description FeaturesProductapplication Location Requirements & Considerations Furnacesuspension ClearancesandaccessibilityExistingfurnaceremoval Combustion & Ventilation AIR Requirements Installation PositionsThermostatlocation Horizontal Applications & Considerations AlternateVent/FlueLocation RecommendedInstallationPositionsHorizontalFurnace Propane GAS/HIGH Altitude Installations VENT/FLUE Pipe & Combustion AIR PipePROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES MaterialsandjoiningmethodsTerminationlocations Increased Clearance Configuration Vent Termination ClearancesCanadianventingrequirements StandardfurnaceconnectionsVent/FluePipeCuts AlternatefurnaceconnectionsRemove Pipe Relocate Upflow NON-DIRECTVENTSINGLEPIPEPIPINGVertical Termination Single Pipe Alternate Vertical Termination Single PipeHorizontalTerminationSinglePipe DirectventdualpipepipingVertical Terminations Dual Pipe Standard Horizontal Terminations Dual PipeAlternate Horizontal Vent Termination Dual Pipe HorizontalVentingOfMultipleUnitsConcentricventtermination Side Wall Vent KITHose and Tube Identification Condensate Drain Lines & Drain TrapStandardrightorleftsidedrainhoseconnections UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDE Drain Trap MountingExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Horizontalinstallations Counterflow furnacesCut Wiringharness Electrical ConnectionsJunctionbox Relocation 115VOLT Line Connections24VOLTTHERMOSTATWIRING Thermostat Wiring DiagramsSINGLE-STAGE Heatingthermostatapplication Accessory load specifications are as follows FossilfuelapplicationsAccessories Wiring GAS Supply and Piping24VOLTHUMIDIFIER HighaltitudederateGaspipingconnections Natural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFHHorizontal Upflow Model Gas Piping ConnectionsCoupling Degree elbow Inch close nipple PropaneGasInstallationTypPropanegastanksandpiping Propane Gas Piping Chart Circulating AIR & FiltersDuct Work -AIR Flow Checking Duct StaticConsult proper tables for the quantity of air Checking Static Pressure 80% Furnace Shown, 90% SimilarDuctFlangeCutOuts BottomreturnairopeningupflowmodelsStartup Procedure &ADJUSTMENT Startup Procedure & AdjustmentFollowing figure shows possible filter locations Temperature Set the thermostat to the lowest settingIf you smell gas after five minutes, immediately follow White-Rodgers Model 36G54 Two-StageGasmanifoldpressuremeasurementandadjustment Turn on the gas supplyHoneywell Model VR9205 Connected to Manometer Measuring Inlet Gas Pressure Alt. MethodTemperaturerise GasinputratemeasurementnaturalgasonlyTemperature Rise Measurement CirculatorblowerspeedsAirflowTable Heat Off Delay Dipswitches Blowerheat Offdelay TimingsComfortnet System OverviewSystem Wiring using Four-Wires System System OperatingTouch To step through the list of installed equip ComfortnetsystemadvancedfeaturesPear. Use Value. TouchConfiguration Networktroubleshooting Is 30 seconds Non-CT compatible single stage AC unitSystemtroubleshooting Power UPNormal Sequence of Operation HeatingmodeCoolingmode Operational Checks & Safety Circuit DescriptionFanonlymode Safety Circuit Description Troubleshooting & Maintenance Operational ChecksTroubleshooting Maintenance Troubleshooting & MaintenanceFollow the manufacturer’s directions for service Before Leaving AN Installation Repair and Replacement PartsInduced Draft Blower Transformer Door Switch MiscellaneousDIP Switches BankTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes Wiring Diagram CVC9AA, *MVC95AACVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.