CONDENSATE DRAIN LINES & DRAIN TRAP

LEFT SIDE DOWN

6. Cut 5

1/2 inches straight length from the long end of each

 

Tube

2 and discard radius ends.

Horizontal installations with the left side panel down will require drain hoses to be connected to the left side front cover drain port and the side drain port on the rubber elbow.

1.Remove the rubber plug/cap from the front cover left (down) side drain port.

2.Relocate the front cover pressure switch hose connection from the right side (as shipped) pressure tap to the left (down) side tap. The pressure switch hose must be connected to the down side to guard against blocked drain conditions. Cut hose to appropriate length to minimize sagging. Plug right (unused) pressure tap with plug removed from left side.

3.Secure Hose A to front cover drain port with a red hose clamp. Route hose to rear left (down) side panel grommet holes. NOTE: For left side drainage, grommets must be relocated to left side panel.

4.Remove the rubber cap from the side drain port on the rubber elbow.

5.Secure the short end of Hose B to rubber elbow side drain port using a green hose clamp. NOTE: For left side drainage, route hose to far left (down) side panel grommet holes. NOTE: Horizontal left side connections (when using new side port drain elbow) does not require connecting a hose to the induced draft blower housing.

7.Insert approximately one inch of each Tube 2 through left side panel grommet hole. Secure tubes to Hose A and Hose B with a green hose clamps. NOTE: Tube must reach bottom of trap. Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.

For details concerning mounting of the drain trap, refer to Con- densate Drain Lines and Drain Trap - Horizontal Drain Trap Mount- ing.

HORIZONTAL DRAIN TRAP MOUNTING (LEFT OR RIGHT SIDE PANEL)

1.Position the drain trap against side panel with drain tubes inserted into trap. Note that the trap may be orientated with the outlet facing either the furnace’s top cover or base pan.

2.Secure drain trap to side panel at the dimples or crosshairs located on either side of the grommet drain holes.

3.Confirm that tubes reach bottom of drain trap and that all hoses maintain a downward slope and are not kinked or binding.

4.Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.

GREEN HOSE

CLAMP

 

FRONT

 

COVER

 

PRESSURE

 

TAP

LEFT SIDE

FRONT COVER

PANEL

 

DRAIN PORT

RED HOSE CLAMP

SIDE PANEL

GROMMET

HOLES

HOSE B

HOSE A

GREEN HOSE

CLAMP

TUBE(S) 2

DRAIN TRAP

Horizontal Connections - Left Side Down (Upflow Shown, Counterflow Similar)

26

Image 26
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting Safety Precautions What to do if YOU Smell GASProduct Description & Application ElectrostaticdischargeesdprecautionsTotheinstaller ShippinginspectionProductapplication FeaturesProduct Description Location Requirements & Considerations Existingfurnaceremoval ClearancesandaccessibilityFurnacesuspension Thermostatlocation Installation PositionsCombustion & Ventilation AIR Requirements HorizontalFurnace AlternateVent/FlueLocation RecommendedInstallationPositionsHorizontal Applications & Considerations Propane GAS/HIGH Altitude Installations VENT/FLUE Pipe & Combustion AIR PipeTerminationlocations MaterialsandjoiningmethodsPROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICES Canadianventingrequirements Increased Clearance ConfigurationVent Termination Clearances StandardfurnaceconnectionsVent/FluePipeCuts AlternatefurnaceconnectionsRemove Pipe Relocate Upflow NON-DIRECTVENTSINGLEPIPEPIPINGHorizontalTerminationSinglePipe Vertical Termination Single PipeAlternate Vertical Termination Single Pipe DirectventdualpipepipingVertical Terminations Dual Pipe Standard Horizontal Terminations Dual PipeConcentricventtermination Alternate Horizontal Vent Termination Dual PipeHorizontalVentingOfMultipleUnits Side Wall Vent KITStandardrightorleftsidedrainhoseconnections Condensate Drain Lines & Drain TrapHose and Tube Identification UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDE Drain Trap MountingExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Horizontalinstallations Counterflow furnacesCut Junctionbox Relocation WiringharnessElectrical Connections 115VOLT Line ConnectionsSINGLE-STAGE Heatingthermostatapplication Thermostat Wiring Diagrams24VOLTTHERMOSTATWIRING Accessory load specifications are as follows Fossilfuelapplications24VOLTHUMIDIFIER Accessories WiringGAS Supply and Piping HighaltitudederateGaspipingconnections Natural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFHHorizontal Upflow Model Gas Piping ConnectionsPropanegastanksandpiping PropaneGasInstallationTypCoupling Degree elbow Inch close nipple Duct Work -AIR Flow Propane Gas Piping ChartCirculating AIR & Filters Checking Duct StaticDuctFlangeCutOuts Consult proper tables for the quantity of airChecking Static Pressure 80% Furnace Shown, 90% Similar BottomreturnairopeningupflowmodelsFollowing figure shows possible filter locations Startup Procedure & AdjustmentStartup Procedure &ADJUSTMENT If you smell gas after five minutes, immediately follow TemperatureSet the thermostat to the lowest setting White-Rodgers Model 36G54 Two-StageHoneywell Model VR9205 Connected to Manometer GasmanifoldpressuremeasurementandadjustmentTurn on the gas supply Measuring Inlet Gas Pressure Alt. MethodTemperaturerise GasinputratemeasurementnaturalgasonlyTemperature Rise Measurement CirculatorblowerspeedsAirflowTable Comfortnet System Heat Off Delay DipswitchesBlowerheat Offdelay Timings OverviewSystem Wiring using Four-Wires System System OperatingPear. Use Touch To step through the list of installed equipComfortnetsystemadvancedfeatures Value. TouchConfiguration Networktroubleshooting Is 30 seconds Non-CT compatible single stage AC unitNormal Sequence of Operation SystemtroubleshootingPower UP HeatingmodeFanonlymode Operational Checks & Safety Circuit DescriptionCoolingmode Troubleshooting Troubleshooting & Maintenance Operational ChecksSafety Circuit Description Follow the manufacturer’s directions for service Troubleshooting & MaintenanceMaintenance Induced Draft Blower Transformer Door Switch Before Leaving AN InstallationRepair and Replacement Parts MiscellaneousDIP Switches BankTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes Wiring Diagram CVC9AA, *MVC95AACVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.