Goodman Mfg MVC95 GAS Supply and Piping, Accessories Wiring, 24VOLTHUMIDIFIER, Highaltitudederate

Page 30

GAS SUPPLY AND PIPING

Accessories Wiring

If it is necessary for the installer to supply additional line voltage wiring to the inside of the furnace, the wiring must conform to all local codes, and have a minimum temperature rating of 105°C. All line voltage wire splices must be made inside the furnace junction box.

The integrated control module humidifier terminals (HUM) are en- ergized with 115 volts whenever the induced draft blower is ener- gized. The integrated control module electronic air cleaner termi- nals (EAC) are energized with 115 volts whenever the circulator blower is energized.

24VOLTHUMIDIFIER

A 5" long brown wire in the wire harness at the low fire pressure switch provides 24 VAC humidifier control. This wire is powered any time the pressure switch is closed. To connect 24 VAC HUM, connect the 24 VAC line of the humidifier to the 5” brown wire. The connection can be made by either stripping the wire and using a wire nut or by using a field supplied quick connect terminal. The wiring must conform to all local and national codes. Connect the COM side of the humidifier to the C terminal on the furnace control board (or to the COM side of the 24 VAC transformer). Do not connect 115V humidifier to these terminals.

GAS SUPPLY AND PIPING

The furnace rating plate includes the approved furnace gas input rating and gas types. The furnace must be equipped to operate on the type of gas applied. This includes any conversion kits required for alternate fuels and/or high altitude.

CAUTION

TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.

Inlet gas supply pressures must be maintained within the ranges specified in the following table. The supply pressure must be constant and available with all other household gas fired appli- ances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must not be exceeded to prevent unit overfiring.

Inlet Gas Supply Pressure

Natural Gas

Minimum: 5.0" w.c.

Maximum:10.0" w.c.

Propane Gas

Minimum: 11.0" w.c.

Maximum:13.0" w.c.

HIGHALTITUDEDERATE

When this furnace is installed at high altitude, the appropriate High Altitude orifice kit must be applied. This is required due to the natural reduction in the density of both the gas fuel and combus- tion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range.

High altitude kits are purchased according to the installation alti- tude and usage of either natural or propane gas. Contact your distributor for a tabular listing of appropriate altitude ranges and corresponding manufacturer’s high altitude (Natural, propane gas, and/or Pressure Switch) kits.

Do not derate the furnace by adjusting the manifold pressure to a lower pressure than specified on the furnace rating plate. The combination of the lower air density and a lower manifold pressure will prohibit the burner orifice from drawing the proper amount of air into the burner. This may cause incomplete combustion, flash- back, and possible yellow tipping.

In some areas the gas supplier may artificially derate the gas in an effort to compensate for the effects of altitude. If the gas is artifi- cially derated, the appropriate orifice size must be determined based upon the BTU/ft3 content of the derated gas and the alti- tude. Refer to the National Fuel Gas Code, NFPA54/ANSI Z223.1, andinformationprovidedbythegassuppliertodeterminetheproper orifice size.

A different pressure switch may be required at high altitude regard- less of the BTU/ft3 content of the fuel used. Contact your distribu- tor for a tabular listing of appropriate altitude ranges and corre- sponding manufacturer’s pressure switch kits.

PROPANEGASCONVERSION

WARNING

POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED. THE APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION. ALL CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE AGENCY.

This unit is configured for natural gas. The appropriate manufacturer’s propane gas conversion kit, must be applied for propane gas installations. Refer to the Propane Gas and/or High Altitude Installations for details.

30

Image 30
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting Safety Precautions What to do if YOU Smell GASProduct Description & Application ElectrostaticdischargeesdprecautionsTotheinstaller ShippinginspectionFeatures Product DescriptionProductapplication Location Requirements & Considerations Clearancesandaccessibility FurnacesuspensionExistingfurnaceremoval Installation Positions Combustion & Ventilation AIR RequirementsThermostatlocation AlternateVent/FlueLocation RecommendedInstallationPositions Horizontal Applications & ConsiderationsHorizontalFurnace Propane GAS/HIGH Altitude Installations VENT/FLUE Pipe & Combustion AIR PipeMaterialsandjoiningmethods PROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICESTerminationlocations Canadianventingrequirements Increased Clearance ConfigurationVent Termination Clearances StandardfurnaceconnectionsVent/FluePipeCuts AlternatefurnaceconnectionsRemove Pipe Relocate Upflow NON-DIRECTVENTSINGLEPIPEPIPINGHorizontalTerminationSinglePipe Vertical Termination Single PipeAlternate Vertical Termination Single Pipe DirectventdualpipepipingVertical Terminations Dual Pipe Standard Horizontal Terminations Dual PipeConcentricventtermination Alternate Horizontal Vent Termination Dual PipeHorizontalVentingOfMultipleUnits Side Wall Vent KITCondensate Drain Lines & Drain Trap Hose and Tube IdentificationStandardrightorleftsidedrainhoseconnections UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDE Drain Trap MountingExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Horizontalinstallations Counterflow furnacesCut Junctionbox Relocation WiringharnessElectrical Connections 115VOLT Line ConnectionsThermostat Wiring Diagrams 24VOLTTHERMOSTATWIRINGSINGLE-STAGE Heatingthermostatapplication Accessory load specifications are as follows Fossilfuelapplications24VOLTHUMIDIFIER Accessories WiringGAS Supply and Piping HighaltitudederateGaspipingconnections Natural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFHHorizontal Upflow Model Gas Piping ConnectionsPropaneGasInstallationTyp Coupling Degree elbow Inch close nipplePropanegastanksandpiping Duct Work -AIR Flow Propane Gas Piping ChartCirculating AIR & Filters Checking Duct StaticDuctFlangeCutOuts Consult proper tables for the quantity of airChecking Static Pressure 80% Furnace Shown, 90% Similar BottomreturnairopeningupflowmodelsStartup Procedure & Adjustment Startup Procedure &ADJUSTMENTFollowing figure shows possible filter locations If you smell gas after five minutes, immediately follow TemperatureSet the thermostat to the lowest setting White-Rodgers Model 36G54 Two-StageHoneywell Model VR9205 Connected to Manometer GasmanifoldpressuremeasurementandadjustmentTurn on the gas supply Measuring Inlet Gas Pressure Alt. MethodTemperaturerise GasinputratemeasurementnaturalgasonlyTemperature Rise Measurement CirculatorblowerspeedsAirflowTable Comfortnet System Heat Off Delay DipswitchesBlowerheat Offdelay Timings OverviewSystem Wiring using Four-Wires System System OperatingPear. Use Touch To step through the list of installed equipComfortnetsystemadvancedfeatures Value. TouchConfiguration Networktroubleshooting Is 30 seconds Non-CT compatible single stage AC unitNormal Sequence of Operation SystemtroubleshootingPower UP HeatingmodeOperational Checks & Safety Circuit Description CoolingmodeFanonlymode Troubleshooting & Maintenance Operational Checks Safety Circuit DescriptionTroubleshooting Troubleshooting & Maintenance MaintenanceFollow the manufacturer’s directions for service Induced Draft Blower Transformer Door Switch Before Leaving AN InstallationRepair and Replacement Parts MiscellaneousDIP Switches BankTroubleshooting Chart InternalLimit Chart MessageInvalid Trips Status Codes Wiring Diagram CVC9AA, *MVC95AACVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.