Goodman Mfg CVC9/95, MVC95 Coupling Degree elbow Inch close nipple, PropaneGasInstallationTyp

Page 33

GAS SUPPLY AND PIPING

DIRECT/STANDARDINLETPIPING

WARNING

EDGES OF SHEET METAL HOLES MAY BE SHARP. USE GLOVES AS A PRECAUTION WHEN REMOVING HOLE PLUGS.

When gas piping enters directly to the gas valve through the stan- dard inlet hole, the installer must supply straight pipe with a ground joint union to reach the exterior of the furnace. The rigid pipe must be long enough to reach the outside of the cabinet to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.

INDIRECT/ALTERNATEINLETPIPING

When gas piping enters indirectly to the gas valve through the alternate gas inlet hole the following fittings (starting from the gas valve) to reach the outside of the cabinet must be supplied:

Coupling.

90 degree elbow.

2 inch close nipple.

90 degree elbow.

Straight pipe, with a ground joint union, to reach the exterior of the furnace. The rigid pipe must be long enough to reach the outside of the cabinet so as to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.

GAS PIPING CHECKS

Before placing unit in operation, leak test the unit and gas connec- tions.

WARNING

TO AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.

Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved testing methods.

NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.

Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pressures in excess of 1/2 psig (3.48 kPa).

Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressures equal to or less than 1/2 psig (3.48 kPA).

PROPANEGASTANKSANDPIPING

WARNING

IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.

SINCE PROPANE GAS IS HEAVIER THAN AIR, ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES.

PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE.

A gas detecting warning system is the only reliable way to detect a propane gas leak. Rust can reduce the level of odorant in pro- pane gas. Do not rely on your sense of smell. Contact a local propane gas supplier about installing a gas detecting warning sys- tem. If the presence of gas is suspected, follow the instructions listed in the Safety Precautions section of this manual.

All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters, NBFU Manual 58.

For satisfactory operation, propane gas pressure must be 11 inch WC at the furnace manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:

1.Vaporization rate, depending on temperature of the liquid, and “wetted surface” area of the container or containers.

2.Proper pressure regulation. (Two-stage regulation is recommended for both cost and efficiency).

3.Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size will depend on length of pipe run and total load of all appliances.

Complete information regarding tank sizing for vaporization, rec- ommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas suppliers.

Since propane gas will quickly dissolve white lead and most stan- dard commercial compounds, special pipe dope must be used. Shellac-based compounds resistant to the actions of liquefied pe- troleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.

Refer to the following illustration for typical propane gas installa- tions and piping.

First Stage

5 to 15 PSIG

 

(20 PSIG Max.)

 

Regulator

Continuous

 

 

 

11" W.C.

200 PSIG

 

Second Stage

Maximum

 

Regulator

PropaneGasInstallation(Typ.)

33

Image 33
Contents Type FSP Category IV Direct or Non Direct Vent Air Furnace Product Description Normal Sequence of Operation Troubleshooting What to do if YOU Smell GAS Safety PrecautionsTotheinstaller ElectrostaticdischargeesdprecautionsProduct Description & Application ShippinginspectionFeatures Product DescriptionProductapplication Location Requirements & Considerations Clearancesandaccessibility FurnacesuspensionExistingfurnaceremoval Installation Positions Combustion & Ventilation AIR RequirementsThermostatlocation AlternateVent/FlueLocation RecommendedInstallationPositions Horizontal Applications & ConsiderationsHorizontalFurnace VENT/FLUE Pipe & Combustion AIR Pipe Propane GAS/HIGH Altitude InstallationsMaterialsandjoiningmethods PROPERVENT/FLUEANDCOMBUSTIONAIRPIPINGPRACTICESTerminationlocations Vent Termination Clearances Increased Clearance ConfigurationCanadianventingrequirements StandardfurnaceconnectionsAlternatefurnaceconnections Vent/FluePipeCutsRemove Pipe Relocate NON-DIRECTVENTSINGLEPIPEPIPING UpflowAlternate Vertical Termination Single Pipe Vertical Termination Single PipeHorizontalTerminationSinglePipe DirectventdualpipepipingStandard Horizontal Terminations Dual Pipe Vertical Terminations Dual PipeHorizontalVentingOfMultipleUnits Alternate Horizontal Vent Termination Dual PipeConcentricventtermination Side Wall Vent KITCondensate Drain Lines & Drain Trap Hose and Tube IdentificationStandardrightorleftsidedrainhoseconnections Drain Trap Mounting UPRIGHTINSTALLATIONS-TRAPONRIGHTSIDEExternally UPRIGHTINSTALLATIONS-TRAP on Leftside Counterflow furnaces HorizontalinstallationsCut Electrical Connections WiringharnessJunctionbox Relocation 115VOLT Line ConnectionsThermostat Wiring Diagrams 24VOLTTHERMOSTATWIRINGSINGLE-STAGE Heatingthermostatapplication Fossilfuelapplications Accessory load specifications are as followsGAS Supply and Piping Accessories Wiring24VOLTHUMIDIFIER HighaltitudederateNatural Gas Capacity of Pipe Cubic Feet of Gas Per Hour CFH GaspipingconnectionsGas Piping Connections Horizontal Upflow ModelPropaneGasInstallationTyp Coupling Degree elbow Inch close nipplePropanegastanksandpiping Circulating AIR & Filters Propane Gas Piping ChartDuct Work -AIR Flow Checking Duct StaticChecking Static Pressure 80% Furnace Shown, 90% Similar Consult proper tables for the quantity of airDuctFlangeCutOuts BottomreturnairopeningupflowmodelsStartup Procedure & Adjustment Startup Procedure &ADJUSTMENTFollowing figure shows possible filter locations Set the thermostat to the lowest setting TemperatureIf you smell gas after five minutes, immediately follow White-Rodgers Model 36G54 Two-StageTurn on the gas supply GasmanifoldpressuremeasurementandadjustmentHoneywell Model VR9205 Connected to Manometer Measuring Inlet Gas Pressure Alt. MethodGasinputratemeasurementnaturalgasonly TemperatureriseCirculatorblowerspeeds Temperature Rise MeasurementAirflowTable Blowerheat Offdelay Timings Heat Off Delay DipswitchesComfortnet System OverviewSystem System Operating System Wiring using Four-WiresComfortnetsystemadvancedfeatures Touch To step through the list of installed equipPear. Use Value. TouchConfiguration Is 30 seconds Non-CT compatible single stage AC unit NetworktroubleshootingPower UP SystemtroubleshootingNormal Sequence of Operation HeatingmodeOperational Checks & Safety Circuit Description CoolingmodeFanonlymode Troubleshooting & Maintenance Operational Checks Safety Circuit DescriptionTroubleshooting Troubleshooting & Maintenance MaintenanceFollow the manufacturer’s directions for service Repair and Replacement Parts Before Leaving AN InstallationInduced Draft Blower Transformer Door Switch MiscellaneousBank DIP SwitchesInternal Troubleshooting ChartLimit Message ChartInvalid Trips Status Codes CVC9AA, *MVC95AA Wiring DiagramCVC9AB, *MVC95AB

MVC95, CVC9/95 specifications

Goodman Manufacturing has established itself as a leader in the HVAC industry, and among its stellar lineup, the Goodman CVC9/95 and MVC95 stand out for their remarkable features, technologies, and efficiency.

The Goodman CVC9/95 is a high-performance gas furnace, designed for homeowners seeking reliability and cost-effective heating solutions. It operates with an impressive 95% Annual Fuel Utilization Efficiency (AFUE), which means that a significant portion of the fuel it consumes is converted into heat. This level of efficiency not only contributes to lower energy bills but also reduces greenhouse gas emissions, making it an environmentally friendly choice.

One of the standout features of the CVC9/95 is its multi-speed ECM blower motor. This technology adjusts the airflow according to the heating demands of the home, ensuring consistent and comfortable temperatures. The ECM motor also operates quietly, enhancing the comfort of your living space without the disruptive noise often associated with traditional furnaces.

The MVC95, on the other hand, offers similar efficiency with its also 95% AFUE rating. This model is equipped with a patented ignition system that enhances reliability with minimal maintenance needs. Its durable construction includes a heavy-gauge steel cabinet and an insulated blower compartment that minimizes heat loss. This design not only supports optimal performance but also contributes to its longevity.

Both models come with a self-diagnostic control board that provides straightforward troubleshooting capabilities, making it easier for technicians to ensure that your system is operating at peak performance. This feature aids in timely maintenance, which is crucial for extending the lifespan of the unit.

Additionally, Goodman backs their products with a strong warranty, offering a lifetime limited warranty on the heat exchanger and a 10-year limited parts warranty. This assurance provides homeowners peace of mind regarding their investment.

In the landscape of HVAC solutions, the Goodman CVC9/95 and MVC95 models exemplify a commitment to quality, efficiency, and advanced technology. Whether for new constructions or replacements, these furnaces offer superior heating performance coupled with modern conveniences, making them an invaluable choice for homeowners seeking effective climate control solutions. With their low emissions and high efficiency, choosing Goodman means investing in both comfort and sustainability.