Lenox ML180UHE installation instructions Equipment in Confined Space

Page 8

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)

CHIMNEY OR

GAS VENT

VENTILATION LOUVERS

(Each end of attic)

 

OUTLET

 

FURNACE

AIR

WATER

 

 

HEATER

VENTILATION

 

INLET

 

AIR

LOUVERS

 

 

 

(For unheated crawl space)

 

 

NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 4

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

EQUIPMENT IN

CONFINED SPACE

ALL AIR FROM

CHIMNEY

(All Air Through Ventilated Attic)

OR GAS

 

VENT

 

CHIMNEY OR GAS

OUTSIDE

VENTILATION LOUVERS

(Each end of attic)

OUTLET

AIR

FURNACE

INLET AIR

 

 

(Ends 12 in.

 

above bottom)

 

WATER

 

HEATER

NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equip- ment in the enclosure.

VENT WATER

HEATER

OUTLET AIR

FURNACE

INLET AIR

NOTE − Each air duct opening shall have a free area of at least one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi- cate directly with the outdoors, each opening shall have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.

FIGURE 5

FIGURE 6

Page 8

Image 8
Contents Installation Instructions ML180UHE Table of ContentsUnit Dimensions − inches mm TOP ViewParts Arrangement Make−Up Box Heat Exchanger Combustion Air InducerBurner Box Gas ValveShipping and Packing List Safety InformationML180UHE Gas Furnace Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Setting Equipment Return Air Horizontal Application Installation Clearances Top Left RightEnd Bottom Typical Horizontal ApplicationFilters Duct SystemVenting Upflow PositionTop Vent Discharge Left Side Vent DischargeHorizontal Left Position Horizontal Right Position Horizontal Left PositionSide Vent Discharge Side Vent Discharge − no modifications necessaryVent Connection Upflow and Horizontal Position Common Venting Using Metal−Lined Masonry Chimney −1/2 Cated or common venting system, you must inspect 18 − The common vent diameter must always be at least asFeet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Ers or straps. Install a drip leg in vertical pipe runs to − In some localities, codes may require the installationGas Piping Gas supply piping should not allow more than 0.5W.C. dropRight−Side Air Discharge Horizontal ApplicationLeft−Side Air Discharge Electrostatic Discharge ESD Interior MAKE−UP BOX InstallationElectrical Thermostat Designations ML180UHE Schematic Wiring Diagram and Sequence of Operation Typical ML180UHE Field Wiring Diagram Integrated ControlFor Your Safety Read Before Lighting Unit Start−UpGas Pressure Adjustment GAS Meter Clocking ChartProper Combustion High AltitudeOther Unit Adjustments Manifold Pressure Settings at all AltitudesHeat FAN-OFF Time in Seconds No Jumper1380 995975 115 945 1345Single Side Return Air − Air volumes in bold require field Order to maintain proper air velocity640 1940 420 1750 310 230Service Electrical SHOCK, Fire Or Explosion HazardML180UHE BURNER, Combustion AIR Inducer Assembly Heat Exchanger Removal−090, −110 −135 units −045 and −070 unitsPlanned Service Repair Parts ListIntegrated Control Diagnostic Codes RED LEDNormal Heating Mode Abnormal Heating Mode Heating Sequence of OperationHeating Sequence Normal Cooling Mode Abnormal Cooling Mode Cooling Sequence of OperationContinuous FAN Sequence of Operation Start−Up & Performance Check List Cooling Mode Temperature RiseUnit Operation Drain Line