INSTALLATION AND SERVICING INSTRUCTIONS

UPFLOW, DOWNFLOW OR HORIZONTAL

TWO STAGE HEAT VARIABLE SPEED

GAS-FIRED NON-CONDENSING

WARM AIR FURNACE

Issue 0527

TABLE OF CONTENTS

Safety

2

Gas Connections

16

Furnace Specifications

3

Control Board & Variable Speed Motor Features

17

Furnace Wiring Specifications

5

Unit Sequence of Operation

18

Introduction

6

Start-Up Operation & Checkout

19

Location/Placement

7

Sequence of Operation

23

Air for Combustion & Ventilation

8

Servicing The Furnace

24

Ducting

11

Control System Diagnostics

26

Venting

12

Wiring Diagram

27

Electrical Connections

15

 

 

RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

Installation and service must be performed

WHAT TO DO IF YOU SMELL GAS:

 

by a qualified installer, service agency or

Do not try to light any appliance.

the gas supplier. Installation by an

Extinguish any open flame.

unqualified person may lead to equipment

Do not touch any electrical switch; do

damage and/or a hazardous condition

not use any phone in your building.

which may cause bodily injury and harm

Immediately call your gas supplier from

and, as such, at the sole discretion of the

a neighbor's phone. Follow the gas

manufacturer, the entire warranty may be

supplier's instructions.

voided and be of no further force and

If you cannot reach your gas supplier,

effect.

call the fire department.

20571201

Issue 0527

Page 1 of 28

Image 1
Contents What to do if YOU Smell GAS Table of ContentsSafety Furnace Specifications Adjusting Airflow Blower Motor Specifications and Airflow Adjusting DataFurnace Wiring Specifications Introduction Installation Positions Location / PlacementHorizontal Line Contact Contaminated Combustion Air AIR for Combustion and VentilationAdequate Ventilation and Combustion Air Confined Space / Outdoor AIR Confined Space / Indoor AIRConfined Space / Outdoor From AtticAIR Through Horizontal Ducts Confined Space / Outdoor AIR From Attic & Crawl SpaceDucting Special Base InstallationDuctwork Recommendation Bottom Panel RemovalVenting Pre-Installation Vent System InspectionFilters External Filter Rack SizeType B Vent Masonry ChimneyHorizontal Venting Auxiliary Draft InducersTo Convert to Side Flue Exit Vent Exit OptionsVent Pipe Guard KIT For Horizontal PositionsCarbon Monoxide Poisoning Hazard Electrical ConnectionsThermostat Single Stage Thermostat OperationGAS Connections GAS Control Piping Typical GAS Service ConnectionAutomatic Heat Staging Jumper Fire or Explosion HazardControl Board & Variable Speed Motor Features Unit Sequence of Operation Cooling ModeHeres How Your Heating System Works Startup and Operational Checkout GAS Control DiagramTypical Flame Appearance Main BurnersGas Rate Cubic Feet per Hour Determining Furnace Input Natural Gas OnlyBurner Orifice Sizing Blower Adjustment CheckoutBurner Orifice Selection NaturalFlame Rollout Switch Flame Rollout SwitchPressure Switch Check Limit Control CheckoutSequence of Operation Servicing the Furnace Manifold or Burner/Manifold Removal/ReplacementElectrical SHOCK, Fire or Explosion Hazard Combustion Component CheckBlower Removal and Replacement Blower Removal/ReplacementLubricating Motors CFM LED Wiring Diagram Issue