Allied Air Enterprises Masonry Chimney, Type B Vent, Horizontal Venting, Auxiliary Draft Inducers

Page 13

vent. If deterioration is discovered, the chimney must be repaired or the "B" vent must be replaced.

2.Inspection to ascertain that the vent system is clear and free of obstructions. Any blockage must be cleared before installing this furnace.

3.Cleaning the chimney or "B" vent if previously used for venting a solid fuel burning appliance or fireplace.

4.Confirming that all unused chimney or "B" vent connections are properly sealed.

5.Verification that the chimney is properly lined and sized per the applicable codes.

Masonry Chimney:

This furnace can be common vented into an existing tile lined masonry chimney provided:

1.The chimney is currently serving at least one drafthood equipped appliance.

2.The vent connectors and chimney are sized in accordance with the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.

This furnace must NOT vented ALONE into an existing masonry chimney (either tile lined or unlined) unless the chimney is also lined with either a type B vent system or a listed single wall, metal lining system. Both of these systems must be sized in accordance with the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.

Before venting this furnace into a chimney, check the chimney for deterioration and repair if necessary. This furnace must not be vented into a chimney serving a separate appliance designed to burn solid fuel. Type"B" vent connectors must be used on all installations and it must be sized per the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.

Type "B" Vent:

The furnace is also approved for use with a "B" vent that terminates through the roof. Refer to the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes for proper sizing and set-up of this furnace with "B" vent for a dedicated vent system or a common vented system.

Horizontal Venting:

This furnace is design certified by CSA International for horizontal venting through an outside wall by use of one of the following auxiliary draft inducer kits:

Table 4 AUXILIARY DRAFT INDUCERS

Vent Kit MFR

Model

* Furnace Input

 

 

 

Field Controls Co.

SWG-4G

50000, 75000, 100000 or

 

125000

 

 

 

 

 

 

SS1 OR SS1C

50000, 75000, 100000 or

Tjernlund Products Inc.

125000

 

 

 

 

GPAK-J

50000, 75000 or 100000

 

 

 

 

GPAK-1

100000 or 125000

 

 

 

* See rating label on this furnace for input

Vent Length: Max. 60 ft. - Min. 12 ft.

Vent Diameter: 4 in.

Follow instructions included with venting kit for proper installation and setup.

Location Requirements for Horizontal Venting:

Locate the vent terminal adhering to the following minimum clearances and as specified in the auxiliary draft inducer vent kit:

1.Vent terminal must be located at least one (1') foot above the grade or at least one (1') foot above the normal expected snowfall.

2.Avoid installing vent terminal above public walkways. If this is not possible, install the terminal at least seven (7') feet above the walkway.

3.Vent terminal should be at least four (4') feet to the side of and at least one (1') foot above doors and windows.

4.Vent terminal should be at least three (3') feet above any forced air inlet located within ten (10') feet.

5.Vent terminal should be located at least six (6') feet from the combustion air intake of another appliance.

6.Vent terminal should be located at least four (4') feet above any electric or gas meters, regulators, and relief equipment.

General Venting Requirements:

This furnace may be common vented only with other Category I appliances. Common venting is allowed as permitted by National and/or local codes. Refer to the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes for proper sizing and set up.

The vent must be terminated with a listed vent cap. This venting must be installed in accordance with the vent manufacturer's instructions and be in accordance with all local codes and/or National Codes. Follow Figure 9 for vent exit options.

The following requirements are provided for a proper venting system:

1.Be sure that the chimney flue is clear of any dirt or debris.

2.Be sure that the chimney is not servicing an open fireplace.

3.Never reduce the pipe size below the outlet size of the furnace without checking the applicable sections

of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.

20571201

Issue 0527

Page 13 of 28

Image 13
Contents What to do if YOU Smell GAS Table of ContentsSafety Furnace Specifications Adjusting Airflow Blower Motor Specifications and Airflow Adjusting DataFurnace Wiring Specifications Introduction Installation Positions Location / PlacementHorizontal Line Contact Contaminated Combustion Air AIR for Combustion and VentilationAdequate Ventilation and Combustion Air Confined Space / Outdoor AIR Confined Space / Indoor AIRConfined Space / Outdoor From AtticAIR Through Horizontal Ducts Confined Space / Outdoor AIR From Attic & Crawl SpaceDucting Special Base InstallationDuctwork Recommendation Bottom Panel RemovalVenting Pre-Installation Vent System InspectionFilters External Filter Rack SizeType B Vent Masonry ChimneyHorizontal Venting Auxiliary Draft InducersTo Convert to Side Flue Exit Vent Exit OptionsVent Pipe Guard KIT For Horizontal PositionsCarbon Monoxide Poisoning Hazard Electrical ConnectionsThermostat Single Stage Thermostat OperationGAS Connections GAS Control Piping Typical GAS Service ConnectionAutomatic Heat Staging Jumper Fire or Explosion HazardControl Board & Variable Speed Motor Features Unit Sequence of Operation Cooling ModeHeres How Your Heating System Works Startup and Operational Checkout GAS Control DiagramTypical Flame Appearance Main BurnersGas Rate Cubic Feet per Hour Determining Furnace Input Natural Gas OnlyBurner Orifice Sizing Blower Adjustment CheckoutBurner Orifice Selection NaturalFlame Rollout Switch Flame Rollout SwitchPressure Switch Check Limit Control CheckoutSequence of Operation Servicing the Furnace Manifold or Burner/Manifold Removal/ReplacementElectrical SHOCK, Fire or Explosion Hazard Combustion Component CheckBlower Removal and Replacement Blower Removal/ReplacementLubricating Motors CFM LED Wiring Diagram Issue