Allied Air Enterprises Upflow From Attic, Confined Space / Outdoor, AIR Through Horizontal Ducts

Page 10

Figure 4

When horizontal ducts are used to supply air from the

CONFINED SPACE / OUTDOOR AIR

outdoors, they must be of the same cross sectional area

 

as the free area of the openings to which they connect.

FROM ATTIC

The minimum dimension of rectangular air ducts must not

 

be less than 3 inches. Each opening must have a free

 

area of not less than one square inch per 2,000 Btu per

 

hour of total input of all appliances within the "Confined

 

Space". These openings must be located 12 in. from the

 

top and bottom of the furnace area. Neither opening can

 

be blocked at any time (See Figure 6).

 

Figure 6

 

CONFINED SPACE / OUTDOOR

 

AIR THROUGH HORIZONTAL DUCTS

Figure 5

CONFINED SPACE / OUTDOOR AIR

FROM ATTIC & CRAWL SPACE

For an attic installation it is important to keep insulation 12" or more away from any furnace openings. Some types of insulating materials may be combustible.

Furnaces installed with combustion air drawn from a heated space which includes exhaust fans, fireplaces, or other devices that may produce a negative pressure should be considered confined space installations.

20571201

Issue 0527

Page 10 of 28

Image 10
Contents Table of Contents What to do if YOU Smell GASSafety Furnace Specifications Blower Motor Specifications and Airflow Adjusting Data Adjusting AirflowFurnace Wiring Specifications Introduction Installation Positions Location / PlacementHorizontal Line Contact Contaminated Combustion Air AIR for Combustion and VentilationAdequate Ventilation and Combustion Air Confined Space / Indoor AIR Confined Space / Outdoor AIRAIR Through Horizontal Ducts From AtticConfined Space / Outdoor Confined Space / Outdoor AIR From Attic & Crawl SpaceDuctwork Recommendation Special Base InstallationDucting Bottom Panel RemovalFilters Pre-Installation Vent System InspectionVenting External Filter Rack SizeHorizontal Venting Masonry ChimneyType B Vent Auxiliary Draft InducersVent Pipe Guard KIT Vent Exit OptionsTo Convert to Side Flue Exit For Horizontal PositionsThermostat Electrical ConnectionsCarbon Monoxide Poisoning Hazard Single Stage Thermostat OperationAutomatic Heat Staging Jumper GAS Control Piping Typical GAS Service ConnectionGAS Connections Fire or Explosion HazardControl Board & Variable Speed Motor Features Unit Sequence of Operation Cooling ModeHeres How Your Heating System Works Typical Flame Appearance GAS Control DiagramStartup and Operational Checkout Main BurnersDetermining Furnace Input Natural Gas Only Gas Rate Cubic Feet per HourBurner Orifice Selection Blower Adjustment CheckoutBurner Orifice Sizing NaturalPressure Switch Check Flame Rollout SwitchFlame Rollout Switch Limit Control CheckoutSequence of Operation Electrical SHOCK, Fire or Explosion Hazard Manifold or Burner/Manifold Removal/ReplacementServicing the Furnace Combustion Component CheckBlower Removal and Replacement Blower Removal/ReplacementLubricating Motors CFM LED Wiring Diagram Issue