Allied Air Enterprises Upflow specifications Safety

Page 2

SAFETY

The following is a list of safety precautions and their locations in this manual.

These safety rules and precautions must be followed when installing this furnace.

1.Use only with type of gas approved for this furnace. Refer to the furnace rating plate.

2.Install this furnace only in a location and position as specified in The Location/Placement Section on page 7 of these instructions.

3.Provide adequate combustion and ventilation air to the furnace space as specified in Air for Combustion and Ventilation section on page 8 of these instructions.

4.Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in Venting on page 12 of these instructions.

5.Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in The Gas Connection section on page 16 of these instructions.

6.Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Furnace Specifications on page 3 of these instructions. See furnace rating plate.

7.When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See page 11 for Ducting.

8.A gas-fired furnace for installation in a residential garage must be installed as specified in The Location / Placement section on page 7 of these instructions.

9.It is not recommended that this furnace be used as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit. The unit may only be used for heating of buildings or structures under construction, if the conditions listed on page 6 in the "Introduction" section of these instructions are met.

20571201

Issue 0527

Page 2 of 28

Image 2
Contents Table of Contents What to do if YOU Smell GASSafety Furnace Specifications Blower Motor Specifications and Airflow Adjusting Data Adjusting AirflowFurnace Wiring Specifications Introduction Horizontal Line Contact Location / PlacementInstallation Positions Adequate Ventilation and Combustion Air AIR for Combustion and VentilationContaminated Combustion Air Confined Space / Indoor AIR Confined Space / Outdoor AIRAIR Through Horizontal Ducts From AtticConfined Space / Outdoor Confined Space / Outdoor AIR From Attic & Crawl SpaceDuctwork Recommendation Special Base InstallationDucting Bottom Panel RemovalFilters Pre-Installation Vent System InspectionVenting External Filter Rack SizeHorizontal Venting Masonry ChimneyType B Vent Auxiliary Draft InducersVent Pipe Guard KIT Vent Exit OptionsTo Convert to Side Flue Exit For Horizontal PositionsThermostat Electrical ConnectionsCarbon Monoxide Poisoning Hazard Single Stage Thermostat OperationAutomatic Heat Staging Jumper GAS Control Piping Typical GAS Service ConnectionGAS Connections Fire or Explosion HazardControl Board & Variable Speed Motor Features Heres How Your Heating System Works Cooling ModeUnit Sequence of Operation Typical Flame Appearance GAS Control DiagramStartup and Operational Checkout Main BurnersDetermining Furnace Input Natural Gas Only Gas Rate Cubic Feet per HourBurner Orifice Selection Blower Adjustment CheckoutBurner Orifice Sizing NaturalPressure Switch Check Flame Rollout SwitchFlame Rollout Switch Limit Control CheckoutSequence of Operation Electrical SHOCK, Fire or Explosion Hazard Manifold or Burner/Manifold Removal/ReplacementServicing the Furnace Combustion Component CheckLubricating Motors Blower Removal/ReplacementBlower Removal and Replacement CFM LED Wiring Diagram Issue