Allied Air Enterprises Upflow Confined Space / Indoor AIR, Confined Space / Outdoor AIR

Page 9

If the installation area meets the definition of "Unconfined Space" and does not have additional air requirements as described, the furnace may be installed without making special provisions for combustion and ventilation air.

Whenever this furnace is installed in an area along with one or more gas appliances, the total Btu/hr input of all appliances must be included when determining the free area requirements for combustion and ventilation air openings.

Do not block the combustion or ventilation air openings in the furnace. Any blockage will result in improper combustion and may result in a fire hazard or unsafe condition.

If ventilation and/or combustion air must be supplied to the "Confined Space" from inside the building structure, two permanent openings to an additional room of sufficient volume as to combine the volumes of the spaces to meet the criteria for an "Unconfined Space" must be created. Each opening must have a free area of not less than one square inch per 1000 Btu per hour of total input of all appliances within the "Confined Space" (but not less than 100 square inches). These openings must be located 12 inches from the top and bottom of the furnace area respectively and must be at least 3 inches long on the smaller side of the opening (See Figure 2). Neither opening can be blocked at any time.

Figure 2

CONFINED SPACE / INDOOR AIR

 

 

 

TOTAL INPUT

MIN. FREE AREA

ROUND DUCT

 

(Btuh)

(Sq. In.)

(Dia. In.)

 

40,000

100

12

 

60,000

100

12

 

80,000

100

12

 

100,000

100

12

 

120,000

120

13

 

140,000

140

14

 

160,000

160

15

 

EXAMPLE:

 

 

 

50,000 Btuh Furnace & 10,000 Btuh Water

 

Heater = 60,000 Btuh Total Input = 12"

 

Dia. Round Duct.

 

If ventilation and/or combustion air must be supplied to the "Confined Space" from outside the building structure, two permanent openings to the outdoors must be created. Each opening must have a free area of not less than one square inch per 4000 Btu per hour of total input of all appliances within the "Confined Space". These openings must be located 12 inches from the top and bottom of the furnace area respectively (See Figures 3, 4, and 5). Neither opening can be blocked at any time.

Figure 3

CONFINED SPACE / OUTDOOR AIR

 

 

 

TOTAL INPUT

MIN. FREE AREA

ROUND DUCT

 

(Btuh)

(Sq. In.)

(Dia. In.)

 

40,000

10

4

 

60,000

15

5

 

80,000

20

5

 

100,000

25

6

 

120,000

30

6

 

140,000

35

7

 

160,000

40

8

 

EXAMPLE:

 

 

 

50,000 Btuh Furnace & 10,000 Btuh Water

 

Heater = 60,000 Btuh Total Input = 5" Dia.

 

Round Duct.

 

 

20571201

Issue 0527

Page 9 of 28

Image 9
Contents What to do if YOU Smell GAS Table of ContentsSafety Furnace Specifications Adjusting Airflow Blower Motor Specifications and Airflow Adjusting DataFurnace Wiring Specifications Introduction Location / Placement Installation PositionsHorizontal Line Contact AIR for Combustion and Ventilation Contaminated Combustion AirAdequate Ventilation and Combustion Air Confined Space / Outdoor AIR Confined Space / Indoor AIRConfined Space / Outdoor From AtticAIR Through Horizontal Ducts Confined Space / Outdoor AIR From Attic & Crawl SpaceDucting Special Base InstallationDuctwork Recommendation Bottom Panel RemovalVenting Pre-Installation Vent System InspectionFilters External Filter Rack SizeType B Vent Masonry ChimneyHorizontal Venting Auxiliary Draft InducersTo Convert to Side Flue Exit Vent Exit OptionsVent Pipe Guard KIT For Horizontal PositionsCarbon Monoxide Poisoning Hazard Electrical ConnectionsThermostat Single Stage Thermostat OperationGAS Connections GAS Control Piping Typical GAS Service ConnectionAutomatic Heat Staging Jumper Fire or Explosion HazardControl Board & Variable Speed Motor Features Cooling Mode Unit Sequence of OperationHeres How Your Heating System Works Startup and Operational Checkout GAS Control DiagramTypical Flame Appearance Main BurnersGas Rate Cubic Feet per Hour Determining Furnace Input Natural Gas OnlyBurner Orifice Sizing Blower Adjustment CheckoutBurner Orifice Selection NaturalFlame Rollout Switch Flame Rollout SwitchPressure Switch Check Limit Control CheckoutSequence of Operation Servicing the Furnace Manifold or Burner/Manifold Removal/ReplacementElectrical SHOCK, Fire or Explosion Hazard Combustion Component CheckBlower Removal/Replacement Blower Removal and ReplacementLubricating Motors CFM LED Wiring Diagram Issue