Allied Air Enterprises Upflow specifications GAS Connections, Automatic Heat Staging Jumper

Page 16

Figure 11

AUTOMATIC HEAT STAGING JUMPER

When installing optional accessories to this appliance, follow the manufacturer's installation instructions included with the accessory.

The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or approved conduit when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning can result in an electrical shock, fire, bodily harm, or loss of life.

GAS CONNECTIONS

Gas piping shall be of such size and so installed as to provide a supply of gas sufficient to meet maximum demands without undue loss of pressure between the gas meter and the furnace. It is recommended that the gas line to the furnace shall be a separate line direct from the meter, unless the existing gas line is of ample capacity. Refer to gas pipe capacity table in the National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.

If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do no use a connector which has previously serviced another gas appliance.

Use a joint compound (pipe dope) that is resistant to the action of liquefied petroleum gases or any other chemical constituents of the gases to be conducted through the piping.

For proper furnace operation the maximum gas supply pressure is 14" w.c. and the minimum gas supply pressure is 4.5" w.c. - Natural (11" w.c. - LP) as shown on rating label.

Before any system of gas piping is finally put into service, it should be carefully tested to determine if it is gas tight. Check all piping for leaks using soapy water and a brush. The piping must stand a pressure of six (6) inches of mercury (3 PSIG) for a period of ten (10) minutes or as required by local authority.

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.

The furnace and its individual shutoff valve must be disconnected from the supply piping system during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.5kPa or 14"w.c.).

The furnace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 PSIG (3.5kPa or 14"w.c.). Failure to follow the above procedures could lead to a hazardous condition and bodily harm.

Figure 12-A

GAS CONTROL PIPING

Figure 12-B

TYPICAL GAS SERVICE CONNECTION

20571201

Issue 0527

Page 16 of 28

Image 16
Contents Table of Contents What to do if YOU Smell GASSafety Furnace Specifications Blower Motor Specifications and Airflow Adjusting Data Adjusting AirflowFurnace Wiring Specifications Introduction Installation Positions Location / PlacementHorizontal Line Contact Contaminated Combustion Air AIR for Combustion and VentilationAdequate Ventilation and Combustion Air Confined Space / Indoor AIR Confined Space / Outdoor AIRFrom Attic Confined Space / OutdoorAIR Through Horizontal Ducts Confined Space / Outdoor AIR From Attic & Crawl SpaceSpecial Base Installation DuctingDuctwork Recommendation Bottom Panel RemovalPre-Installation Vent System Inspection VentingFilters External Filter Rack SizeMasonry Chimney Type B VentHorizontal Venting Auxiliary Draft InducersVent Exit Options To Convert to Side Flue ExitVent Pipe Guard KIT For Horizontal PositionsElectrical Connections Carbon Monoxide Poisoning HazardThermostat Single Stage Thermostat OperationGAS Control Piping Typical GAS Service Connection GAS ConnectionsAutomatic Heat Staging Jumper Fire or Explosion HazardControl Board & Variable Speed Motor Features Unit Sequence of Operation Cooling ModeHeres How Your Heating System Works GAS Control Diagram Startup and Operational CheckoutTypical Flame Appearance Main BurnersDetermining Furnace Input Natural Gas Only Gas Rate Cubic Feet per HourBlower Adjustment Checkout Burner Orifice SizingBurner Orifice Selection NaturalFlame Rollout Switch Flame Rollout SwitchPressure Switch Check Limit Control CheckoutSequence of Operation Manifold or Burner/Manifold Removal/Replacement Servicing the FurnaceElectrical SHOCK, Fire or Explosion Hazard Combustion Component CheckBlower Removal and Replacement Blower Removal/ReplacementLubricating Motors CFM LED Wiring Diagram Issue