Allied Air Enterprises Upflow Venting, Filters, External Filter Rack Size, Vent Adaptor Mounting

Page 12

Filters:

Air filters must be used in every installation. For side return installations, air filters must be installed external to the furnace casing. An external filter rack kit with filter (parts No. 20069901 or Cat. No. 68L75 12 / 15½" x 25" sizes and 20069902 or Cat. No. 68L76 for 15½" / 19" x 25" sizes) is available as an optional accessory.

For bottom (end) return installations, the above optional external rack may be used, if the unit was not provided with a internal filter. Minimum filter size and suggested filter materials are shown in Table 3. (If different type filter is used, it must be an equivalent high airflow capacity.)

Table 3

EXTERNAL FILTER RACK SIZE

MODEL

 

SIDE

BOTTOM/END

 

RETURN

RETURN

 

 

 

 

 

 

 

050-3

 

15 ½ X 25

12 X 25

075-3

 

 

 

 

 

 

 

 

 

 

100-4

 

15 ½

X 25

15 ½ X 25

 

 

 

 

 

125-5

 

15 ½

X 25

19 X 25

 

 

 

 

 

This furnace may use either a disposable filter, permanent filter, electronic or high efficiency media air

cleaner. Consult filter/cleaner manufacturers for maintience service and static pressure drop for air moving requirements.

When installing the furnace with cooling equipment for year round operation, the following recommendations must be followed for series or parallel air flow:

1.In series flow applications, the evaporator coil is mounted after the furnace in an enclosure in the supply air stream. The furnace blower is used for both heating and cooling airflow.

2.In parallel flow installation, dampers must be provided to direct air over the furnace heat exchanger when heat is desired and over the cooling when cooling is desired. At no time may the evaporator coil be located on the return air side of the heat exchanger.

IMPORTANT: The dampers should be adequate to prevent cooled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either the cooling unit or furnace unless the damper is in the full cool or full heat position.

The coil MUST be installed on the air discharge side of the furnace. Under no circumstances should the air flow be such that cooled, conditioned air can pass over the furnace heat exchanger. This will cause condensation in the heat exchanger and possible failure of the heat exchanger that could lead to a fire hazard and/or hazardous conditions that may lead to bodily harm. Heat exchanger failure due to improper installation will not be covered by warranty.

VENTING

Venting for this category I furnace must be to the outside and in accordance with local codes or requirements of the local utility. In the absence of local codes, venting must conform to the applicable sections of the latest edition of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes, and the vent manufacturers instructions.

This furnace is CSA International certified as a Category I forced air appliance and can not be vented into a vent system with any Category II, III or IV appliance. It must be vented vertically, or nearly vertically, unless installed with a listed mechanical venter in accordance with horizontal venting instructions. It must not be connected to any portion of a mechanical draft system operating under positive pressure

The 3" (in.) to 4" (in.) vent adaptor coupling (supplied with unit) MUST BE USED. It must be connected directly to the outlet of the combustion blower using a field supplied corrosion resistant sheet metal screw (See Figure 8).

Figure 8

VENT ADAPTOR MOUNTING

Pre-Installation Vent System Inspection:

Before this furnace is installed, it is highly recommended that any existing vent system be completely inspected.

For a chimney or "B" vent, this should include the following:

1. Inspection for any deterioration in the chimney or "B"

20571201

Issue 0527

Page 12 of 28

Image 12
Contents Table of Contents What to do if YOU Smell GASSafety Furnace Specifications Blower Motor Specifications and Airflow Adjusting Data Adjusting AirflowFurnace Wiring Specifications Introduction Location / Placement Installation PositionsHorizontal Line Contact AIR for Combustion and Ventilation Contaminated Combustion AirAdequate Ventilation and Combustion Air Confined Space / Indoor AIR Confined Space / Outdoor AIRFrom Attic Confined Space / OutdoorAIR Through Horizontal Ducts Confined Space / Outdoor AIR From Attic & Crawl SpaceSpecial Base Installation DuctingDuctwork Recommendation Bottom Panel RemovalPre-Installation Vent System Inspection VentingFilters External Filter Rack SizeMasonry Chimney Type B VentHorizontal Venting Auxiliary Draft InducersVent Exit Options To Convert to Side Flue ExitVent Pipe Guard KIT For Horizontal PositionsElectrical Connections Carbon Monoxide Poisoning HazardThermostat Single Stage Thermostat OperationGAS Control Piping Typical GAS Service Connection GAS ConnectionsAutomatic Heat Staging Jumper Fire or Explosion HazardControl Board & Variable Speed Motor Features Cooling Mode Unit Sequence of OperationHeres How Your Heating System Works GAS Control Diagram Startup and Operational CheckoutTypical Flame Appearance Main BurnersDetermining Furnace Input Natural Gas Only Gas Rate Cubic Feet per HourBlower Adjustment Checkout Burner Orifice SizingBurner Orifice Selection NaturalFlame Rollout Switch Flame Rollout SwitchPressure Switch Check Limit Control CheckoutSequence of Operation Manifold or Burner/Manifold Removal/Replacement Servicing the FurnaceElectrical SHOCK, Fire or Explosion Hazard Combustion Component CheckBlower Removal/Replacement Blower Removal and ReplacementLubricating Motors CFM LED Wiring Diagram Issue