
Cooling Mode:
The units are factory set for the highest airflow for each model. Adjustments can be made to the cooling airflow by repositioning the jumper plug marked COOL - A, B, C, D (see AirFlow Adjustment Table on page 4) based on the information found in the table.
By moving the ADJUST jumper plug (see Table on page 4) from the NORM position to the (+) or
The TEST position on the ADJUST tap is not used.
To determine what CFM the motor is delivering at any time, count the number of times the amber LED on the control board flashes. Each flash signifies 100 CFM; count the flashes and multiply by 100 to determine the actual CFM delivered (for example: 10 flashes x 100 = 1000 CFM).
UNIT SEQUENCE OF OPERATION
Here's How Your Heating System Works:
Standby Mode
When the control is in standby mode, it continually monitors thermostat input, rollout switch, and flame sense.
Call For Heat
On a call for 1st stage heat (W1) from the room thermostat, the ignition control performs a
If 1st stage heating operation is not sufficient to satisfy the heating demand, the room thermostat initiates a call for 2nd stage heat (W1 and W2). The control changes the inducer from low to high speed and confirms the
When the 2nd stage call for heat is satisfied, the control shuts off the gas valve and runs the combustion air blower for a post purge period of 5 seconds. The circulating air blower continues to run for approximately 3 minutes before ramping down. If the thermostat W2 call ends and W1 remains, the control
In the event the unit loses ignition, the control will attempt to recycle up to five times before it goes into a 1- hour lockout. Lockout may be manually reset by removing power from the control for more than 1 second or removing the thermostat call for heat for more than 3 seconds.
If during a heating cycle the limit control senses an abnormally high temperature and opens, the ignition control
Should overheating occur, or the gas supply fail to shut OFF, turn OFF the manual gas valve to the appliance BEFORE turning OFF the electrical supply. A failure to adhere to this warning can result in a fire or explosion and bodily harm.
Fan "ON"
A call for continuous fan from the thermostat closes R to G on the control board. The control waits for a 1- second debounce delay before responding by energizing the circulating air blower at 50% of the cooling speed. When the call for fan is turned off, the control de- energizes the circulating blower.
Cooling
A call for cooling from the thermostat closes R to Y and R to G on the blower control board. The control waits for a
speed. After 7.5 minutes, the circulating blower automatically ramps up to 100% of the cooling speed. When a call for cooling is satisfied, the circulating blower ramps back down to 82% of the cooling speed for 60 seconds then shuts off.
20571201 | Issue 0527 | Page 18 of 28 |